| Plan Review Notes For Permit 16020318 |
| Permit Number |
16020318 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-11 08:31:25 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | PENDING COMMENTS NOT ADDRESSED: | | | | | | 2.CLARIFY IF ELECTRICAL SERVICE IS BEING UPGRADED.- | | | PROVIDE ELECTRICAL PANEL LOAD CALCULATION. AIC RATING | | | OF EQUIPMENT SERVICE. CONDUCTORS FEEDING INTERIOR PANEL | | | SIZE. . CLARIFY NO GROUNDS TO AC, DRYER AND WATER | | | HEATER?? LOADS | | | 3.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES- | | | E3603.1 | | | 4.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES- | | | E3609.3 | | | 6.2ND FLOOR, ADD WITHIN 3FT OF BASIN A RECEPTACLE | | | BATHROOM OUTLET AT THE DOUBLE SINK LOCATION TO COMPLY | | | WITH FBC RES E3901.6 | | | 12.PROVIDE A PANEL SCHEDULE REFLECTING CIRCUIT | | | IDENTIFICATION. FBC RES E3706.3 | | | 13.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|