| Plan Review Notes For Permit 16020305 |
| Permit Number |
16020305 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-10 12:38:23 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | - NEC 230.2 NUMBER OF SERVICES. A BUILDING OR OTHER | | | STRUCTURE | | | SERVED SHALL BE SUPPLIED BY ONLY ONE SERVICE.PROPERLY | | | IDENTIFY EACH SERVICE DISCONNECT. ( LABEL ) | | | | | | - PLEASE TAKE A LOOK AT FPL APROVED RISER DIAGRAMS. | | | | | | - NEC 230.72 ALL DISCONNECTS MUST BE GROUPED. | | | | | | - NEC 250.94 PROVIDE INTERSYSTEM BONDING | | | | | | - NEC 215.5 PROVIDE A SITE PLAN SHOWING LOCATION OF | | | EQUIPMENT RELATIVE TO EACH OTHER, PLEASE SHOW GROUNDING | | | WIRE SIZE AND EXISTING LOAD CALCS. |
|