2016-02-18 08:38:13APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE SIZE OF THE SERVICE CONDUCTORS FOR
 THE NEW SERVICE SHOWN, FBC 107.3.5
 2. SHOW ACTUAL AIC CALCULATIONS FOR THE NEW SERVICE
 SHOWN. FBC 107.3.5
 3. PROVIDE PER FBC EC 405.7 FEEDER VOLTAGE DROP
 CALCULATIONS
 4. GENERAL NOTES TO INDICATE REQUIREMENTS OF FBC EC
 405.4 COMPLETION DOCUMENTS SEE VERBIAGE IN THE CODE. A
 NOTE WILL SUFFICE.
 5. CLARIFY AS THE RISER DIAGRAM REFLECTING THE ONE-LINE
 FOR THE NEW ELECTRICAL SERVICE DOES NOT HAVE CONDUCTOR
 SIZES; SIZE OF THE MCB, SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR AND SIZE OF THE FEEDER CONDUCTORS. PROVIDE
 ALL FOR A COMPLETE REVIEW OF ELECTRICAL SERVICE. NEC
 250.66, 310.15B16 FBC 107.3.5
 6. PROVIDE DATA SHEETS FOR ALL ELECTRICAL EQUIPMENT
 THAT IS PART OF THIS PROJECT.
 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  