| Plan Review Notes For Permit 16020303 |
| Permit Number |
16020303 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-18 08:38:13 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE SIZE OF THE SERVICE CONDUCTORS FOR | | | THE NEW SERVICE SHOWN, FBC 107.3.5 | | | 2. SHOW ACTUAL AIC CALCULATIONS FOR THE NEW SERVICE | | | SHOWN. FBC 107.3.5 | | | 3. PROVIDE PER FBC EC 405.7 FEEDER VOLTAGE DROP | | | CALCULATIONS | | | 4. GENERAL NOTES TO INDICATE REQUIREMENTS OF FBC EC | | | 405.4 COMPLETION DOCUMENTS SEE VERBIAGE IN THE CODE. A | | | NOTE WILL SUFFICE. | | | 5. CLARIFY AS THE RISER DIAGRAM REFLECTING THE ONE-LINE | | | FOR THE NEW ELECTRICAL SERVICE DOES NOT HAVE CONDUCTOR | | | SIZES; SIZE OF THE MCB, SIZE OF THE GROUNDING ELECTRODE | | | CONDUCTOR AND SIZE OF THE FEEDER CONDUCTORS. PROVIDE | | | ALL FOR A COMPLETE REVIEW OF ELECTRICAL SERVICE. NEC | | | 250.66, 310.15B16 FBC 107.3.5 | | | 6. PROVIDE DATA SHEETS FOR ALL ELECTRICAL EQUIPMENT | | | THAT IS PART OF THIS PROJECT. | | | 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|