| Plan Review Notes For Permit 16020285 |
| Permit Number |
16020285 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-19 09:07:37 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIREMENTS OF | | | NEC 300.5 D3 FOR THE SERVICE CONDUCTORS. A NOTE WILL | | | SUFFICE. | | | 2. PLEASE CLARIFY THE MAIN PV/AC DISCONNECT SHOWN AFTER | | | PAD TRANSFORMER, IS THIS A FUSED DISCONNECT? GROUNDING | | | ELECTRODE CONDUCTOR ARRANGEMENT SHOWN AT THIS | | | DISCONNECT BUT NO EQUIPMENT GROUNDING CONDUCTOR SHOWN | | | TO COMBINER PANEL BOARD. LABEL ON ONE-LINE EQUIPMENT TO | | | BE RATED FOR SERVICE ENTRANCE. | | | 3. PROVIDE CUT SHEETS FOR THE PANEL BOARD PV/AC | | | COMBINER (HPVA) WHERE THE BACK FEED BREAKERS ARE | | | LOCATED. FBC 107.3.5 | | | 4. PLEASE ADDRESS ZONING COMMENTS BEFORE COMPLETE | | | ELECTRICAL APPROVAL. | | | 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|