2016-02-19 09:07:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIREMENTS OF
 NEC 300.5 D3 FOR THE SERVICE CONDUCTORS. A NOTE WILL
 SUFFICE.
 2. PLEASE CLARIFY THE MAIN PV/AC DISCONNECT SHOWN AFTER
 PAD TRANSFORMER, IS THIS A FUSED DISCONNECT? GROUNDING
 ELECTRODE CONDUCTOR ARRANGEMENT SHOWN AT THIS
 DISCONNECT BUT NO EQUIPMENT GROUNDING CONDUCTOR SHOWN
 TO COMBINER PANEL BOARD. LABEL ON ONE-LINE EQUIPMENT TO
 BE RATED FOR SERVICE ENTRANCE.
 3. PROVIDE CUT SHEETS FOR THE PANEL BOARD PV/AC
 COMBINER (HPVA) WHERE THE BACK FEED BREAKERS ARE
 LOCATED. FBC 107.3.5
 4. PLEASE ADDRESS ZONING COMMENTS BEFORE COMPLETE
 ELECTRICAL APPROVAL.
 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  