| Plan Review Notes For Permit 16020257 |
| Permit Number |
16020257 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-09 17:19:52 | RESIDENTIAL (R3) ROOFING, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- METAL ROOF: | | | A) FLORIDA PRODUCT APPROVAL FL16980.2 SUBMITTED DOESN'T | | | MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE PRODUCT | | | APPROVAL THAT MEETS THE DESIGN PRESSURES OF ALL ROOF | | | ZONES. | | | RESPONSE: METAL ROOF NOA 15-0421.02 SUBMITTED DON'T | | | MEET THE DESIGN PRESSURES. NOTE: SEE STRUCTURAL PLANS | | | FOR REQUIRED DESIGN PRESSURES. | | | | | | 2- MODIFIED BITUMEN ROOF SYSTEMS: | | | A) FLORIDA PRODUCT APPROVAL FL16709-R3 SUBMITTED IS NOT | | | APPROVED YET. NEED TO PROVIDE CURRENT APPROVED PRODUCT | | | APPROVAL AS REQUIRED BY F.A.C. 61G20-3.02(33). | | | RESPONSE: SAME FLORIDA PRODUCT APPROVAL FL16709-R3 WAS | | | RESUBMITTED. THIS PRODUCT APPROVAL IS NOT APPROVED YET. | | | | | | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE AS REQUIRED | | | BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | RESPONSE: PRODUCT APPROVALS STILL ARE NOT REVIEWED BY | | | THE ENGINEER OF RECORD. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | |
|