| 2016-12-07 12:28:39 | |
| | MAIN HOUSE: |
| | RESIDENTIAL (R3) ALTERATIONS THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE IF PLANS ARE DENIED THREE OR MORE TIMES AS |
| | REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| | |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) ENERGY CALCULATIONS AND A/C EQUIPMENT SIZING |
| | CALCULATIONS NEED TO BE COORDINATED. SEE EQUIPMENT |
| | SIZING CALCULATIONS FOR COOLING AND HEATING LOADS AND |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: MISSING THE OWNER INFORMATION (REPEAT |
| | COMMENT). |
| | |
| | C) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION. |
| | REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | D) PROVIDE MANUFACTURER'S INFORMATION FOR THE WINDOWS |
| | AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC |
| | FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7. |
| | NOTE: THIS IS ONLY REQUIRED WHEN THE PERSON PREPARING |
| | THE CALCULATIONS IS TAKING A FACTOR OTHER THAN THE |
| | DEFAULT FACTOR OF THE ENERGY CALCULATIONS SOFTWARE. |
| | SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | E) REVISE ITEM #10 R-30 INSULATION DOESN'T FIT ON 2X8 |
| | ROOF JOIST. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: REPEAT COMMENT. R-30 INSULATION DOESN'T FIT. |
| | R-30 BUTT INSULATION IS +/- 9-1/2" THICK AND NEED A |
| | MINIMUM OF 1 INCH SPACE BETWEEN THE INSULATION AND THE |
| | ROOF SHEATHING FOR CROSS VENTILATION. TYPICAL WALL |
| | SECTION ON SHEET "B" SPECIFIES ADDITIONAL L 2X2 |
| | MAILERS. THE ADDITION OF THESE MAILERS STILL DON'T |
| | PROVIDE ENOUGH ROOM FOR THE R-30 INSULATION AND |
| | REQUIRED 1" VENTING SPACE. REVISE AS REQUIRED. |
| | |
| | F) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4. |
| | ACCORDING TO PLANS SUBMITTED THIS IS NOT A HIP ROOF. |
| | SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. THE PERSON PREPARING THE |
| | CALCULATIONS NEED TO REVISE THE INFORMATION. HAND |
| | WRITTEN CHANGES ARE NOT ALLOWED. INFORMATION NEEDS TO |
| | BE CHANGED ON THE SOFTWARE INPUT NOT BY HAND. REVISE AS |
| | REQUIRED. |
| | |
| | G) REVISE INSULATION TYPE SHOWN ON THE CEILING |
| | INFORMATION ON PAGE 2 OF 4. ACCORDING TO PLANS |
| | SUBMITTED THERE IS NOT BLOWN INSULATION. SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | H) SPECIFY THE BUILDING ORIENTATION OF THE WALLS, DOORS |
| | AND WINDOWS ON PAGE 3 OF 4. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | I) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION |
| | SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | 2- GABLE END SECTION ON SHEET "B": |
| | A) SPECIFY ALL THE STRUCTURAL CONNECTORS ON THE GABLE |
| | WALL FRAMING DETAIL. SEC. R601.2 AND R801.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. IT'S NOT CLEAR HOW THE |
| | SIMPSON H10A CONNECTOR IS INSTALLED AT THE BOTTOM OF |
| | THE 2X4 STUDS. ALSO, HOW IS THE METAL CONNECTOR #2 (SEE |
| | METAL CONNECTOR SCHEDULE) IS INSTALLED. #2 CONNECTOR IS |
| | TO BE EMBEDDED IN CONCRETE. THIS IS AN EXISTING |
| | CONCRETE BEAM. HOW IS IT EMBEDDED IN THE EXISTING BEAM |
| | AND CLARIFY HOW IS THIS #2 CONNECTOR INSTALLED AT TOP |
| | OF THE 2X4 STUD. THERE IS NO WAY TO EMBED THIS |
| | CONNECTOR IN WOOD FRAMING. |
| | |
| | B) INFORMATION SHOWN AT THE ROOF JOIST SECTION IS NOT |
| | LEGIBLE. THE BACKGROUND DOESN'T ALLOW LETTERING TO BE |
| | READ. REVISE AS REQUIRED. SEC. 107.2.1.4 CITY |
| | AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | C) R-30 BATT INSULATION DOESN'T FIT ON THE SIZE OF ROOF |
| | JOIST SPECIFIED. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. SEE COMMENT #1(E) ABOVE. |
| | |
| | 3- WINDOW DETAILS ON SHEET "B": SPECIFY ALL CONNECTORS |
| | OF THE WOOD FRAMING MEMBERS ON THE HEAD DETAIL. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 4- SHEET "A": |
| | A) CLARIFY STRUCTURAL NOTES BELOW THE "DESIGN |
| | STANDARDS". TYPICALLY, SPECIFICATIONS FOR THE |
| | ATTACHMENT OF DOORS AND WINDOWS TO THE SUBSTRATE ARE |
| | INCLUDED IN THE PRODUCT APPROVALS. WHAT ARE THESE NOTES |
| | FOR?. IS THE ENGINEER OF RECORD CHANGING THE PRODUCT |
| | APPROVAL SPECIFICATIONS? IF SO, THEN COMPLETE |
| | ENGINEERING ANALYSIS IS REQUIRED. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |