 MAIN HOUSE:
 RESIDENTIAL (R3) ALTERATIONS THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE IF PLANS ARE DENIED THREE OR MORE TIMES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) ENERGY CALCULATIONS AND A/C EQUIPMENT SIZING
 CALCULATIONS NEED TO BE COORDINATED. SEE EQUIPMENT
 SIZING CALCULATIONS FOR COOLING AND HEATING LOADS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: MISSING THE OWNER INFORMATION (REPEAT
 COMMENT).
  
 C) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 REVISE AS REQUIRED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) PROVIDE MANUFACTURER'S INFORMATION FOR THE WINDOWS
 AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7.
 NOTE: THIS IS ONLY REQUIRED WHEN THE PERSON PREPARING
 THE CALCULATIONS IS TAKING A FACTOR OTHER THAN THE
 DEFAULT FACTOR OF THE ENERGY CALCULATIONS SOFTWARE.
 SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 E) REVISE ITEM #10 R-30 INSULATION DOESN'T FIT ON 2X8
 ROOF JOIST. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. R-30 INSULATION DOESN'T FIT.
 R-30 BUTT INSULATION IS +/- 9-1/2" THICK AND NEED A
 MINIMUM OF 1 INCH SPACE BETWEEN THE INSULATION AND THE
 ROOF SHEATHING FOR CROSS VENTILATION. TYPICAL WALL
 SECTION ON SHEET "B" SPECIFIES ADDITIONAL L 2X2
 MAILERS. THE ADDITION OF THESE MAILERS STILL DON'T
 PROVIDE ENOUGH ROOM FOR THE R-30 INSULATION AND
 REQUIRED 1" VENTING SPACE. REVISE AS REQUIRED.
  
 F) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4.
 ACCORDING TO PLANS SUBMITTED THIS IS NOT A HIP ROOF.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. THE PERSON PREPARING THE
 CALCULATIONS NEED TO REVISE THE INFORMATION. HAND
 WRITTEN CHANGES ARE NOT ALLOWED. INFORMATION NEEDS TO
 BE CHANGED ON THE SOFTWARE INPUT NOT BY HAND. REVISE AS
 REQUIRED.
  
 G) REVISE INSULATION TYPE SHOWN ON THE CEILING
 INFORMATION ON PAGE 2 OF 4. ACCORDING TO PLANS
 SUBMITTED THERE IS NOT BLOWN INSULATION. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 H) SPECIFY THE BUILDING ORIENTATION OF THE WALLS, DOORS
 AND WINDOWS ON PAGE 3 OF 4. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 I) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 2- GABLE END SECTION ON SHEET "B":
 A) SPECIFY ALL THE STRUCTURAL CONNECTORS ON THE GABLE
 WALL FRAMING DETAIL. SEC. R601.2 AND R801.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. IT'S NOT CLEAR HOW THE
 SIMPSON H10A CONNECTOR IS INSTALLED AT THE BOTTOM OF
 THE 2X4 STUDS. ALSO, HOW IS THE METAL CONNECTOR #2 (SEE
 METAL CONNECTOR SCHEDULE) IS INSTALLED. #2 CONNECTOR IS
 TO BE EMBEDDED IN CONCRETE. THIS IS AN EXISTING
 CONCRETE BEAM. HOW IS IT EMBEDDED IN THE EXISTING BEAM
 AND CLARIFY HOW IS THIS #2 CONNECTOR INSTALLED AT TOP
 OF THE 2X4 STUD. THERE IS NO WAY TO EMBED THIS
 CONNECTOR IN WOOD FRAMING.
  
 B) INFORMATION SHOWN AT THE ROOF JOIST SECTION IS NOT
 LEGIBLE. THE BACKGROUND DOESN'T ALLOW LETTERING TO BE
 READ. REVISE AS REQUIRED. SEC. 107.2.1.4 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
 C) R-30 BATT INSULATION DOESN'T FIT ON THE SIZE OF ROOF
 JOIST SPECIFIED. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. SEE COMMENT #1(E) ABOVE.
  
 3- WINDOW DETAILS ON SHEET "B": SPECIFY ALL CONNECTORS
 OF THE WOOD FRAMING MEMBERS ON THE HEAD DETAIL. SEC.
 R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 4- SHEET "A":
 A) CLARIFY STRUCTURAL NOTES BELOW THE "DESIGN
 STANDARDS". TYPICALLY, SPECIFICATIONS FOR THE
 ATTACHMENT OF DOORS AND WINDOWS TO THE SUBSTRATE ARE
 INCLUDED IN THE PRODUCT APPROVALS. WHAT ARE THESE NOTES
 FOR?. IS THE ENGINEER OF RECORD CHANGING THE PRODUCT
 APPROVAL SPECIFICATIONS? IF SO, THEN COMPLETE
 ENGINEERING ANALYSIS IS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  