Plan Review Notes
Plan Review Notes For Permit 16020238
Permit Number 16020238
Review Stop B
Sequence Number 2
Notes
Date Text
2016-11-17 16:31:45 
 MAIN HOUSE:
 RESIDENTIAL (R3) ALTERATIONS SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) PROVIDE MANUFACTURER'S INFORMATION FOR THE WINDOWS
 AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7.
 NOTE: THIS IS REQUIRED WHEN THE PERSON PREPARING THE
 CALCULATIONS IS TAKING A FACTOR OTHER THAN THE DEFAULT
 FACTOR OF THE ENERGY CALCULATIONS SOFTWARE.
 SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) REVISE ITEM #10 R-30 INSULATION DOESN'T FIT ON 2X8
 ROOF JOIST. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 E) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 F) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4.
 ACCORDING TO PLANS SUBMITTED THIS IS NOT A HIP ROOF.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) REVISE INSULATION TYPE SHOWN ON THE CEILING
 INFORMATION ON PAGE 2 OF 4. ACCORDING TO PLANS
 SUBMITTED THERE IS NOT BLOWN INSULATION. SEE PLANS AND
 REVISE AS REQUIRED. COORDINATE WITH ITEM #1(D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 I) SPECIFY THE BUILDING ORIENTATION OF THE WALLS, DOORS
 AND WINDOWS ON PAGE 3 OF 4. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 J) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 K) COMPLETE THE INSPECTION CHECKLIST (TABLE 402.4.1.1
 SUBMITTED) AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
 2- PLANS SUBMITTED ARE NOT LEGIBLE. THERE IS TOO MUCH
 OVERLAPPING BACKGROUND INFORMATION THAT DOESN'T ALLOW
 PLANS AND LETTERING TO BE READ. REVISE AS REQUIRED.
 SEC. 107.2.1.4 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- SPECIFY ALL THE STRUCTURAL CONNECTORS ON THE TYPICAL
 GABLE WALL FRAMING DETAIL. SEC. R601.2 AND R801.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE:
 THERE ARE TWO DIFFERENT GABLE END DETAILS ON SHEET "B".
 ONE SHOWS AN EXISTING CONCRETE BEAM AND THE OTHER ONE
 SHOWS AN EXISTING WOOD BEAM.
 A) GABLE END WITH EXISTING CONCRETE BEAM DETAIL:
 (1) IT IS NOT CLEAR HOW THE SIMPSON H10A CONNECTOR IS
 INSTALLED AT THE BOTTOM OF 2X4 STUD. PROVIDE DETAIL
 SHOWING HOW THE SIMPSON H10A CONNECTOR IS INSTALLED AT
 THE BOTTOM 2X4 STUD. SEC. R301.1 FBC-RESIDENTIAL.
  
 (2) INFORMATION SHOWN AT THE ROOF JOIST SECTION IS NOT
 LEGIBLE. REVISE AS REQUIRED. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 (3) R-30 BATT INSULATION DOESN'T FIT ON THE SIZE OF
 ROOF JOIST SPECIFIED. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
 NOTE: REVISE INSULATION R-VALUE SHOWN ON THE TYPICAL
 WALL SECTION ALSO.
  
 B) GABLE END WITH EXISTING WOOD BEAM DETAIL:
 (1) SPECIFY FRAMING CONNECTORS FOR ALL STRUCTURAL
 FRAMING MEMBERS. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL NUMBER
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT:
 B) GLASS BLOCK AS SHOWN ON REVISED PLANS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 NEW COMMENTS:
 6- WINDOW DETAILS ON SHEET "B": SPECIFY ALL CONNECTORS
 OF THE WOOD FRAMING MEMBERS ON THE HEAD DETAIL. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 7- SHEET "A":
 A) CLARIFY SECOND NOTE SHOWN ON THE MIDDLE TOP OF SHEET
 "A". IF EXTERIOR DOORS AE NOT REPLACED, WHY IS THIS
 NOTE INCLUDED. ALSO, CLARIFY WHY ARE THE DOORS RATED
 FOR 140 MPH WIND LOAD?. SEE DESIGN STANDARDS ON SAME
 DRAWING. ALSO, CLARIFY WHAT IS "(AS PER ASD)"?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) CLARIFY STRUCTURAL NOTES BELOW THE "DESIGN
 STANDARDS". TYPICALLY, SPECIFICATIONS FOR THE
 ATTACHMENT OF DOORS AND WINDOWS TO THE SUBSTRATE ARE
 INCLUDED IN THE PRODUCT APPROVALS. WHAT ARE THESE NOTES
 FOR?. IS THE ENGINEER OF RECORD CHANGING THE PRODUCT
 APPROVAL SPECIFICATIONS? IF SO, THEN COMPLETE
 ENGINEERING ANALYSIS IS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  