Text |
| 2016-11-17 16:31:45 | |
| | MAIN HOUSE: |
| | RESIDENTIAL (R3) ALTERATIONS SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) PROVIDE MANUFACTURER'S INFORMATION FOR THE WINDOWS |
| | AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC |
| | FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7. |
| | NOTE: THIS IS REQUIRED WHEN THE PERSON PREPARING THE |
| | CALCULATIONS IS TAKING A FACTOR OTHER THAN THE DEFAULT |
| | FACTOR OF THE ENERGY CALCULATIONS SOFTWARE. |
| | SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | D) REVISE ITEM #10 R-30 INSULATION DOESN'T FIT ON 2X8 |
| | ROOF JOIST. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | E) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | F) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED |
| | BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | G) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4. |
| | ACCORDING TO PLANS SUBMITTED THIS IS NOT A HIP ROOF. |
| | SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | H) REVISE INSULATION TYPE SHOWN ON THE CEILING |
| | INFORMATION ON PAGE 2 OF 4. ACCORDING TO PLANS |
| | SUBMITTED THERE IS NOT BLOWN INSULATION. SEE PLANS AND |
| | REVISE AS REQUIRED. COORDINATE WITH ITEM #1(D) ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | I) SPECIFY THE BUILDING ORIENTATION OF THE WALLS, DOORS |
| | AND WINDOWS ON PAGE 3 OF 4. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | J) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION |
| | SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | K) COMPLETE THE INSPECTION CHECKLIST (TABLE 402.4.1.1 |
| | SUBMITTED) AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | |
| | 2- PLANS SUBMITTED ARE NOT LEGIBLE. THERE IS TOO MUCH |
| | OVERLAPPING BACKGROUND INFORMATION THAT DOESN'T ALLOW |
| | PLANS AND LETTERING TO BE READ. REVISE AS REQUIRED. |
| | SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 3- SPECIFY ALL THE STRUCTURAL CONNECTORS ON THE TYPICAL |
| | GABLE WALL FRAMING DETAIL. SEC. R601.2 AND R801.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | RESPONSE: |
| | THERE ARE TWO DIFFERENT GABLE END DETAILS ON SHEET "B". |
| | ONE SHOWS AN EXISTING CONCRETE BEAM AND THE OTHER ONE |
| | SHOWS AN EXISTING WOOD BEAM. |
| | A) GABLE END WITH EXISTING CONCRETE BEAM DETAIL: |
| | (1) IT IS NOT CLEAR HOW THE SIMPSON H10A CONNECTOR IS |
| | INSTALLED AT THE BOTTOM OF 2X4 STUD. PROVIDE DETAIL |
| | SHOWING HOW THE SIMPSON H10A CONNECTOR IS INSTALLED AT |
| | THE BOTTOM 2X4 STUD. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | (2) INFORMATION SHOWN AT THE ROOF JOIST SECTION IS NOT |
| | LEGIBLE. REVISE AS REQUIRED. SEC. 107.2.1.4 CITY |
| | AMENDMENTS. |
| | |
| | (3) R-30 BATT INSULATION DOESN'T FIT ON THE SIZE OF |
| | ROOF JOIST SPECIFIED. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | NOTE: REVISE INSULATION R-VALUE SHOWN ON THE TYPICAL |
| | WALL SECTION ALSO. |
| | |
| | B) GABLE END WITH EXISTING WOOD BEAM DETAIL: |
| | (1) SPECIFY FRAMING CONNECTORS FOR ALL STRUCTURAL |
| | FRAMING MEMBERS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL NUMBER |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO |
| | LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH |
| | SPECIFIED CONNECTOR. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | B) GLASS BLOCK AS SHOWN ON REVISED PLANS. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | |
| | NEW COMMENTS: |
| | 6- WINDOW DETAILS ON SHEET "B": SPECIFY ALL CONNECTORS |
| | OF THE WOOD FRAMING MEMBERS ON THE HEAD DETAIL. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |
| | 7- SHEET "A": |
| | A) CLARIFY SECOND NOTE SHOWN ON THE MIDDLE TOP OF SHEET |
| | "A". IF EXTERIOR DOORS AE NOT REPLACED, WHY IS THIS |
| | NOTE INCLUDED. ALSO, CLARIFY WHY ARE THE DOORS RATED |
| | FOR 140 MPH WIND LOAD?. SEE DESIGN STANDARDS ON SAME |
| | DRAWING. ALSO, CLARIFY WHAT IS "(AS PER ASD)"?. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B) CLARIFY STRUCTURAL NOTES BELOW THE "DESIGN |
| | STANDARDS". TYPICALLY, SPECIFICATIONS FOR THE |
| | ATTACHMENT OF DOORS AND WINDOWS TO THE SUBSTRATE ARE |
| | INCLUDED IN THE PRODUCT APPROVALS. WHAT ARE THESE NOTES |
| | FOR?. IS THE ENGINEER OF RECORD CHANGING THE PRODUCT |
| | APPROVAL SPECIFICATIONS? IF SO, THEN COMPLETE |
| | ENGINEERING ANALYSIS IS REQUIRED. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |