2016-03-02 06:11:55INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE PROVIDE A PANEL LOAD SCHEDULE REFLECTING ALL
 LOADS. FBC 107.3.5
 2.ADDRESS RECEPTACLE SPACING IN KITCHEN COUNTERTOP
 AREA. FBC RES E3901.2.4
 3.ADDRESS RECEPTACLE WALL SPACING IN BEDROOM #2 PER FBC
 RES E3901.2.2
 4.GFCI PROTECTION REQUIRED FOR ALL RECEPTACLES IN
 BATHROOM AREA, SEE GUEST BATH. FBC RES E3902.1
 5.PROVIDE NOTES ON PLANS TO REFLECT AFCI AND TAMPER
 RESISTANT RECEPTACLE REQUIREMENTS. FBC RES E3902.12,
 FBC RES E4002.14
 6.PROVIDE AND SHOW OUTDOOR RECEPTACLES OUTLETS AT THE
 FRONT AND BACK OF THE DWELLING PER. FBC RES E3901.7
 7.PROVIDE A HVAC OUTLET PER. FBC RES E3902.12 WITHIN
 25FT OF UNIT.
 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  