| Plan Review Notes For Permit 16020238 |
| Permit Number |
16020238 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-02 06:11:55 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE PROVIDE A PANEL LOAD SCHEDULE REFLECTING ALL | | | LOADS. FBC 107.3.5 | | | 2.ADDRESS RECEPTACLE SPACING IN KITCHEN COUNTERTOP | | | AREA. FBC RES E3901.2.4 | | | 3.ADDRESS RECEPTACLE WALL SPACING IN BEDROOM #2 PER FBC | | | RES E3901.2.2 | | | 4.GFCI PROTECTION REQUIRED FOR ALL RECEPTACLES IN | | | BATHROOM AREA, SEE GUEST BATH. FBC RES E3902.1 | | | 5.PROVIDE NOTES ON PLANS TO REFLECT AFCI AND TAMPER | | | RESISTANT RECEPTACLE REQUIREMENTS. FBC RES E3902.12, | | | FBC RES E4002.14 | | | 6.PROVIDE AND SHOW OUTDOOR RECEPTACLES OUTLETS AT THE | | | FRONT AND BACK OF THE DWELLING PER. FBC RES E3901.7 | | | 7.PROVIDE A HVAC OUTLET PER. FBC RES E3902.12 WITHIN | | | 25FT OF UNIT. | | | 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE | | | TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU | | | HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|