| 2016-10-27 15:31:27 | MECHANICAL PROVISOS | | | 10/27/16 | | | | | | 1) THE UPLOADED ENGINEERING DOCUMENTS FOR ANCHORING THE | | | CARRIER, MITSUBISHI, AND FIRST COMPANY EXTERIOR UNITS | | | MUST BEAR THE ORIGINAL SIGNATURES AND SEALS OF THE | | | ENGINEERS WHO PREPARED THE DOCUMENTS. | | | | | | 2) PROVIDE AHRI CERTIFICATES FOR THE THORUGH THE WALL | | | APARTMENT AC SYSTEMS. | | | | | | 3) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE | | | KITCHEN HOOD AND FIRE SUPPRESSION SYSTEM IN THE | | | CLUBHOUSE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|