2016-09-12 14:05:143RDT REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHT. A-10.6 PLEASE SHOW COMPLIANCE WITH FBC ACC.
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 2. THE KITCHEN SINK IN CH 103 SHALL DRAIN THRU GREASE
 INTERCEPTOR. PER FBC PL 1003.1
  
 3. SHT.P2.1B ON THE OUTLET SIDE OF GREASE INTERCEPTOR A
 ONE DIRECTIONAL CLEAN IS SHOWN PLEASE SHOW A TWO WAY
 CLEAN OUT. ALSO DOWN STEAM OF THE CLEANOUT WE REQUIRE A
 TEST PORT MIN SIZE IS 6IN. PER WPB UTIL. DEPT.
  