3 |
|
| Notes |
| Date |
Text |
| 2016-08-26 09:57:25 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16020194 | | | 8/26/16 | | | | | | 1) THE REVISED AC COOLING AND HEATING CALCULATIONS ARE | | | MISSING THE A1, A1 COR, A2, AND A3 SYSTEMS. | | | | | | 2) THE ENERGY/GAUGE COMPLIANCE SUBMITTAL IS MISSING THE | | | DATA FOR THE MITSUBISHI SYSTEMS. | | | | | | 3) COMMENT #1 FROM THE PREVIOUS REVIEW HAS NOT | | | COMPLETELY ADDRESSED. A) PROVIDE A REVISED FAN SCHEDULE | | | ON SHEET M-5.2 THAT SHOWS THE NEW, LARGER CAPACITY | | | GARAGE EXHAUST FANS. B) SHEETS M-2.1A & M-2.2A: THE | | | 6000 EXHAUST CFM'S SHOWN AT THE SOUTH SIDE OF THE | | | GARAGE FOR LEVELS 1 & 2 DO NOT MATCH WITH THE EXHAUST | | | CFMS SHOWN ON THE RISER DRAWING ON SHEET M-6.2. | | | | | | 4) COMMENT #15 FROM THE PREVIOUS REVIEW HAS NOT BEEN | | | COMPLETELY ADDRESSED. A) DEMAND CONTROLLED VENTILATION | | | IS REQUIRED FOR THE THEATRE- PLEASE PLACE A NOTE ON THE | | | PLAN AND SHOW THE LOCATIONS OF CO2 SENSORS. B) SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE SENSORS REVIEWED | | | WITH SIGNATURE BY THE EOR. THE SPECS SHALL PROVIDE | | | INSTRUCTIONS FOR INSTALLATION OF THE SENSORS | | | | | | INCLUDING PLACEMENT AND SPACING OF THE DEVICES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|