Plan Review Notes
Plan Review Notes For Permit 16020194
Permit Number 16020194
Review Stop B
Sequence Number 3
Notes
Date Text
2016-09-09 15:42:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. AS THE POOL COURTYARD OCCUPANT LOAD IS NOW OVER 500
 (WAS 395 IN PREVIOUS REVIEW), THREE MEANS OF EGRESS ARE
 REQUIRED, FBC 1004.5, 1021.2.4.
  
 ALSO SEE FBC 1005.5 REGARDING LOSS OF AN EXIT.
  
 THE RESPONSE LETTER AND EGRESS CAPACITY TABULATIONS
 CALCULATE GATE 161 AS A DOUBLE 4 FT, BUT THE PLANS
 (A2.1, LS 0.1, OTHER SHEETS) DEPICT A SINGLE GATE.
  
 A SINGLE GATE IS SHOWN ADJACENT TO THE DOUBLE GATE 160.
 AS THIS MEANS OF EGRESS IS REQUIRED, REVISE THE EGRESS
 CAPACITY CALCULATIONS TO INCLUDE THIS GATE.
  
 2. THIS REVIEW CAN BE PASSED WITH PROVISO THAT AFFECTED
 SHEETS ARE REVISED PRIOR TO BUILDING DRY IN. ARCHITECT
 IS TO REQUEST PROVISO VIA EMAIL WITH AN EXPLANATION OF
 POOL DECK MEANS OF EGRESS FUTURE REVISION.
  
  
  
  