| 2016-06-15 16:09:58 | |
| | 2ND REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | FAIR HOUSING AND ACCESSIBILITY COMMENTS: |
| | |
| | PREVIOUS COMMENTS |
| | #3. DID NOT COMPLY PLEASE SHOW THE MIN AND MAX |
| | DIMINSIONS OF THE REINFORCEMENT FOR THE GRAB BARS |
| | MEASURED FROM FINISHED FLOOR TO THE BOTTOM AND TOP OF |
| | REINFORCEMENT. PER FHA DESIGN MANUAL REQUIREMENT 6 |
| | |
| | #8 DID NOT COMPLY PLEASE SHOW DEMINSIONS OF VANITY FROM |
| | FRONT TO BACK NOT SIDE TO SIDE. PER FHA DESIGN MANUAL |
| | REQUIREMENT 5 |
| | |
| | #10 DID NOT COMPLY PLEASE SHOW DEMINSION OF THE WING |
| | WALL ON RIGHT SIDE OF TOILET FROM BACK OF TOILET TO THE |
| | END OF THE WALL. PER FHA DESIGN MANUAL REQUIREMENT 7 |
| | PART B |
| | |
| | NEW COMMENTS: |
| | 1. SHT. A-5.1.5 SHOW THE CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE FIXTURES IN EACH BATHROOM AND BREAKROOM SINK |
| | IN LEASING OFFICE. PER FBC ACC. SEC. 305 |
| | |
| | 2. SHT. A-5.1.5 DETAIL A THE URINAL IS SHOWN AS |
| | STANDARD PER ACCESSIBILITY LEGEND IT NEEDS TO BE SHOWN |
| | AS ACCESSIBLE. PER FBC ACC. SEC 605 |
| | |
| | 3. THE BREAKROOM SINK IN LEASING OFFICE SHALL COMPLY |
| | WITH FBC ACC. SEC. 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | PLUMBING COMMENTS: |
| | |
| | PREVIOUS COMMENTS: |
| | |
| | #11 DID NOT COMPLY SHT. P-6.2 DETAIL #2 STILL SHOWS |
| | SUCTION AS 5IN EVERYTHING ELSE IS SHOWN AS 6IN. PLEASE |
| | CLARIFY. PER WPB AMEND. TO FBC SEC.107.2.1 |
| | |
| | # 18 DID NOT COMPLY PROVIDE DETAIL WITH THE DEMISIONS |
| | AND THE SQUARE FOOTAGE THAT IT IS SERVING FOR OVERFLOW |
| | SCUPPERS. PER WPB AMEND. TO FBC SEC.107.2.1 |
| | |
| | #20 DID NOT COMPLY PLEASE PROVIDE DEMINSIONS OF STORM |
| | SUMP PIT. PER WPB AMEND. TO FBC SEC.107.2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. CUB HOUSE KITCHEN SINK AND MOP SINK ALONG WITH 3 |
| | COMPARTMENT SINK SHALL DRAIN THROUGH GREASE |
| | INTERCEPTOR. PER FBC PL SEC. 1003.1 WHERE REQUIRED. |
| | INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO |
| | PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER |
| | SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER, |
| | THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE TREATMENT PLANT |
| | OR PROCESSES. |
| | |
| | 2. SHT. P-2.1B MATCHLINE P-2.1B APPEARS TO BE INCORRECT |
| | IT SHOULD BE P-2.1A PLEASE CLARIFY. PER WPB AMEND. TO |
| | FBC SEC.107.2.1 |
| | |
| | |
| | DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A |
| | COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME, |
| | THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF |
| | PLANS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |