Plan Review Notes
Plan Review Notes For Permit 16020194
Permit Number 16020194
Review Stop P
Sequence Number 2
Notes
Date Text
2016-06-15 16:09:58 
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 FAIR HOUSING AND ACCESSIBILITY COMMENTS:
  
 PREVIOUS COMMENTS
 #3. DID NOT COMPLY PLEASE SHOW THE MIN AND MAX
 DIMINSIONS OF THE REINFORCEMENT FOR THE GRAB BARS
 MEASURED FROM FINISHED FLOOR TO THE BOTTOM AND TOP OF
 REINFORCEMENT. PER FHA DESIGN MANUAL REQUIREMENT 6
  
 #8 DID NOT COMPLY PLEASE SHOW DEMINSIONS OF VANITY FROM
 FRONT TO BACK NOT SIDE TO SIDE. PER FHA DESIGN MANUAL
 REQUIREMENT 5
  
 #10 DID NOT COMPLY PLEASE SHOW DEMINSION OF THE WING
 WALL ON RIGHT SIDE OF TOILET FROM BACK OF TOILET TO THE
 END OF THE WALL. PER FHA DESIGN MANUAL REQUIREMENT 7
 PART B
  
 NEW COMMENTS:
 1. SHT. A-5.1.5 SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES IN EACH BATHROOM AND BREAKROOM SINK
 IN LEASING OFFICE. PER FBC ACC. SEC. 305
  
 2. SHT. A-5.1.5 DETAIL A THE URINAL IS SHOWN AS
 STANDARD PER ACCESSIBILITY LEGEND IT NEEDS TO BE SHOWN
 AS ACCESSIBLE. PER FBC ACC. SEC 605
  
 3. THE BREAKROOM SINK IN LEASING OFFICE SHALL COMPLY
 WITH FBC ACC. SEC. 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENTS:
  
 #11 DID NOT COMPLY SHT. P-6.2 DETAIL #2 STILL SHOWS
 SUCTION AS 5IN EVERYTHING ELSE IS SHOWN AS 6IN. PLEASE
 CLARIFY. PER WPB AMEND. TO FBC SEC.107.2.1
  
 # 18 DID NOT COMPLY PROVIDE DETAIL WITH THE DEMISIONS
 AND THE SQUARE FOOTAGE THAT IT IS SERVING FOR OVERFLOW
 SCUPPERS. PER WPB AMEND. TO FBC SEC.107.2.1
  
 #20 DID NOT COMPLY PLEASE PROVIDE DEMINSIONS OF STORM
 SUMP PIT. PER WPB AMEND. TO FBC SEC.107.2.1
  
 NEW COMMENTS:
  
 1. CUB HOUSE KITCHEN SINK AND MOP SINK ALONG WITH 3
 COMPARTMENT SINK SHALL DRAIN THROUGH GREASE
 INTERCEPTOR. PER FBC PL SEC. 1003.1 WHERE REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER,
 THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE TREATMENT PLANT
 OR PROCESSES.
  
 2. SHT. P-2.1B MATCHLINE P-2.1B APPEARS TO BE INCORRECT
 IT SHOULD BE P-2.1A PLEASE CLARIFY. PER WPB AMEND. TO
 FBC SEC.107.2.1
  
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  