2016-06-09 08:39:502ND REVIEW: FBC 2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #16020194
 6/9/16
  
 1) REFER TO SECTION 404.2: THE TOTAL 153900 SQUARE
 FOOTAGE OF THE GARAGE LEVELS 1-7 WILL REQUIRE AN
 EXHAUST VENTILATION SYSTEM CAPABLE OF PRODUCING A
 MAXIMUM VENTILATION AIR FLOW RATE OF 115,470 CFMS AT
 .75 CFMS PER SF. GEF-3 WHICH HAS A MAX RATE OF 20,000
 CFMS IS ADEQUATELY SIZED FOR THE 2ND LEVEL GARAGE IT IS
 SERVICING, HOWEVER THE ROOF-MOUNTED GEF-1 & 2 DO NOT
 HAVE THE CAPACITIES TO SERVICE THE REMAINING LEVELS.
  
 2) REFER TO SECTION 501.4 AND CLARIFY HOW MAKEUP AIR
 FOR THE GARAGE EXHAUST SYSTEMS IS BEING PROVIDED: THE
 CONTROL DIAGRAM ON M-6.3 DEPICTS NORTH AND SOUTH
 OUTSIDE AIR SHAFTS AND SPECIFES SUPPLY FANS IN THE
 SEQUENCE NOTES, HOWEVER THESE SHAFTS AND SUPPLY FANS DO
 NOT APPEAR TO BE SHOWN ON THE GARAGE MECHANICAL PLANS.
  
 3) SHEETS M-6.3 AND M-2.1A & M-2.2A: THE CONTROLS
 DIAGRAM SHOWS THE AMS AT BOTH NORTH AND SOUTH LOCATIONS
 FOR GARAGE LEVELS 1 & 2, HOWEVER THEY ARE NOT SHOWN ON
 THE MECHANICAL PLANS FOR THE THOSE LEVELS.
  
 4) REFERENCE WAS MADE TO SECTION C403.2.9 FBC-14 ENERGY
 CONSERVATION (COMMENT #18) WHICH REQUIRES COMMISSIONING
 OF THE MECHANICAL SYSTEMS ON THE PROPOSED PROJECT.
 PLEASE REVIEW SECTION C408 AND SUBMIT A COMMISSIONING
 PLAN IN ACCORDANCE WITH SECTION C408.2.1.
  
 5) THE SUBMITTED AC COOLING AND HEATING SUMMARY
 CALCULATIONS FROM DTM TECH INC. MUST BE SIGNED AND
 SEALED BY THE ENGINEER OF RECORD- SECTION C403.2.1.
  
 6) SHEET M3.1A: THE REDCIRCULATION OF AIR FROM THE DOG
 PARLOR IS PROHIBITED PER TABLE 403.3 FOOTNOTE B. PLEASE
 REMOVE THE TRANSFER DUCT.
  
 7) M3.1A: THE SUPPLY AIR STREAM IN THE ZOOM LOCKER ROOM
 SHALL NOT CONTAIN MORE THAN 10% OF REIRCULATED AIR FROM
 THE SPACE. IT APPEARS THAT THE 48X6 RETURN AIR GRILL
 WILL ALLOW RECIRCULATION EXCEEDING THE ALLOWABLE LIMIT.
 PLEASE PROVIDE A CALCULATION TO VERIFY COMPLIANCE.
  
 8) AS PREVIOUSLY REQUESTED, AND IN ACCORDANCE WITH
 ASHRAE 62.1 AND TABLE 403.3, PROVIDE VENTILATION FOR
 THE TELECOM AND STORAGE ROOMS.
  
 9) AS PREVIOUSLY REQUESTED, AND IN ACCORDANCE WITH
 ASHRAE 62.1 AND TABLE 403.3, PROVIDE EXHAUST SYSTEMS
 FOR THE TRASH ROOMS.
  
 10) M-2.2C: REFER TO SECTION 501.3.1(2) AND INDICATE
 ALL REQUIRED CLEARANCE DISTANCES FOR THE TWO EXHAUST
 OUTLETS ON THE NORTH SIDE OF THE BUILDING. AS
 PREVIOUISLY NOTED, FL. PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S MUST BE SUBMITTED FOR THE EXHAUST
 OUTLET LOUVERS WITH APPROVAL SIGNATURE BY THE EOR. THE
 LOUVERS SHALL ALSO COMPLY WITH AMCA STANDARD 550.
  
 11) M-3.1A, 3.1B: REFER TO COMMENT #10 ABOVE AND SHOW
 COMPLIANCE FOR ALL EXHAUST OUTLETS ON THE WEST SIDE,
 AND ALSO SEE SECTION 401.4 AND PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS FOR THE OUTDOOR AIR INLETS FOR
 AC-4, 4A, 5, 6, 7, & 8.
  
 12) M3.2C: PER THE NARRATIVE RESPONSE, THE LOCATION OF
 CU-8 IS SHOWN ON THIS PLAN, HOWEVER THIS PLAN SHEET IS
 NOT IN THE UPLOADED PLAN SETS ON THE INDEX.
  
 13) M-2.7A & 7B: AS PREVIOUSLY REQUESTED PROVIDE SIZING
 CALCULATIONS FOR THE ELEVATOR HOISTWAY VENTS IN
 COMPLIANCE WITH SECTION 3004.3 FBC-14 BUILDING.
  
 14) M-3.1B: IT APPEARS THAT NON-METALLIC FLEXIBLE DUCTS
 ARE BEING USED FOR EXHAUST IN THE POOL BATHROOMS PLEASE
 PROVIDE A MANUFACTURER'S SPECIFICATION SHEET INDICATING
 THE DUCTS CAN BE USED FOR THIS PURPOSE.
  
 15) M-3.1C: PLEASE INDICATE HOW DEMAND CONTROLLED
 VENTILATION IS BEING CONTROLLED AND SHOW THE LOCATION
 OF THE C02 SENSORS.
  
 16) M-7.2: AS PREVIOUSLY NOTED IN THE 1ST REVIEW, NOA
 #07-0509.09 FOR THE ROOF STAND IS EXPIRED. PLEASE
 PROVIDE THE CORRECT NOA # ON THE PLAN, AND THE WIND
 LOAD DESIGN CRITERIA FOR ALL EXTERIOR INSTALLATIONS
 SHOWN ON THE PLAN.
  
 17) PLEASE PROVIDE AN AIR DEVICE SCHEDULE INDICATING
 MAKES, MODELS, AND DIMENSIONS OF ALL SUPPLY DIFFUSERS
 AND RETURN GRILLS, AND ACCESSORIES.
  
 18) PROVIDE CONDENSATE DISPOSAL PLANS AND DETAILS FOR
 ALL AC SYSTEMS SHOWN ON THE PLANS. IF LOCATED IN THE
 PLUMBING DRAWINGS AND RISER DIAGRAMS, PLEASE INDICATE
 ON WHICH PLAN SHEETS.
  
 19) M-4.1, 4.2, & 4.3: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYERS AND KITCHEN EXHAUST
 HOODS. THE DRYER EXHAUST DUCT RUNS FOR ALL UNITS EXCEED
 THE ALLOWABLE 35' MAXIMUM ALLOWABLE BY SECTION
 504.6.4.1, PLEASE NOTE THE DUCT RUN CHART ON SHEET
 M-4.3 DOES NOT INDICATE THE MANUFACTURER.
  
 20) M-4.1, 4.2, & 4.3: THE O/A INTAKES ON MANY OF THE
 UNITS APPEAR TO BE LOCATED IN PROXIMITY OF THE
 CONDENSER EXHAUST GRILLS. REFER TO SECTION 401.4 AND
 ADD CLEARANCE MEASUREMENTS TO VERIFY COMPLIANCE.
  
 21) M-4.2: THE BEDROOM RETURN TRANSFER FOR ALL UNITS ON
 THIS SHEET APPEAR TO BE POINTING IN THE WRONG
 DIRECTION- PLEASE CORRECT.
  
 22) EACH UPLOADED WIND LOAD ENGINEERING DOCUMENT FOR
 THE CARRIER, MITSUBISHI, FIRST COMPANY UNITS, AND THE
 ROOF STANDS AND WALL BRACKETS HAVE SCANNED ENGINEER'S
 SEALS- EACH MUST BE DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER WHO PREPARED THEM. THE DOCUMENTS MUST ALSO BE
 APPROVAL WITH SIGNATURE BY THE PROJECT ENGINEER OF
 RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  