Plan Review Notes
Plan Review Notes For Permit 16020194
Permit Number 16020194
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-06-23 15:20:27ROY LINDOW-6/23/16
 FIRE PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
  
 1) SHEET 20?M3.1C, THIS SHEET SHOWS KITCHEN RANGE ON
 DRAWING. THE EXHAUST HOOD SHOWN ON PLANS IS NOT SHOWN
 OVER RANGE. KITCHEN EXHAUST AND FIRE SUPPRESSION SYSTEM
 REQUIRE SEPARATE PERMIT AND DRAWINGS.
 2) SHEET 094-A-5.4 & SHEET 095-A-5.4.1 DOOR SCHEDULE,
 THE REMARKS KEY DOES NOT SHOW A SEPARATE KEY ITEM FOR
 LISTED FIRE EXIT HARDWARE. PROVIDE A KEY FOR ALL FIRE
 RATED DOORS TO HAVE LISTED FIRE EXIT HARDWARE.
  
 7.2.1.7.2 ONLY APPROVED PANIC HARDWARE SHALL BE USED ON
 DOOR
 ASSEMBLIES THAT ARE NOT FIRE-RATED DOOR ASSEMBLIES.
 ONLY APPROVED FIRE
 EXIT HARDWARE SHALL BE USED ON FIRE-RATED DOOR
 ASSEMBLIES. NEW PANIC
 HARDWARE AND NEW FIRE EXIT HARDWARE SHALL COMPLY WITH
 ANSI/UL
 305, STANDARD FOR SAFETY PANIC HARDWARE, AND ANSI/BHMA
 A156.3, EXIT DEVICES.
  
 3) SHEET 012-C-09, PROVIDE NO PARKING FIRE LANE SIGNAGE
 (SEE PROVISO).
  
 4) SHEET 042-LS-0.4, LEVELS 4-7, EXIT DOORS FROM THIS
 SPACE ARE NOT REMOTE PER SECTION,
 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION
 9.7, THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS,
 EXIT
 ACCESSES, OR EXIT DISCHARGES, MEASURED IN ACCORDANCE
 WITH 7.5.1.3.2,
 SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE
 MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE
 SERVED.
  
 5) SHEET 051-A-2.4, EXIT DOORS FROM ASSEMBLY AREAS AND
 OTHER SPACES THAT EXCEED 100 OCCUPANT LOAD ARE NOT
 PROVIDED WITH PANIC HARDWARE. COORDINATE WITH DOOR
 SCHEDULE TO INDICATE CORRECT HARDWARE IS PROVIDED.
 EXAMPLES OF DOORS (412, 413, ST 401, ST 403 AND ST
 406).
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING:
  
 6) SHEET 051-A-2.4, EXIT DOOR SHOWN ON PLANS AS ST-405
 SWINGS IN THE WRONG DIRECTION IN ADDITION IT IS NOT
 INCLUDED ON THE DOOR SCHEDULE AND WILL ALSO REQUIRE
 PANIC HARDWARE.
  
 7) SHEET 044-A-2.1, DOORS SHOWN AS DOOR 139, 131 & 132
 APPEAR TO SWING GREATER THAT 50% OF THE REQUIRED EXIT
 WIDTH AND EXCEED MAXIMUM PROJECTION PER SECTION,
 7.2.1.4.3
  
 8) THIS IS FROM A PREVIOUS LIST OF COMMENTS #12 ON
 PREVIOUS LIST.
 SHEET 040-LS-0.2, PROVIDE ONE HOUR RATING TO SEPARATE
 CORRIDOR FROM GARAGE.
 ARROW POINTS TO AREA IN QUESTION.
  
 9) SHEET 092-A-5.2.2, DUPLICATE NOTE. PLEASE REMOVE GAS
 FIREPLACE FROM PLANS.
  
 10) SHEET 317-FS2.7B, AND SHEET 316-FS2.7A, REQUIRED
 FIRE SPRINKLER COVERAGE IS NOT PROVIDED FOR ELEVATOR
 MACHINE ROOMS.
  
 11) SHEET-044-A-2.1, PROVISO NOTE ADDED TO PLANS.
  
 12) GENERAL COMMENT, DO NOT UTILIZE EXIT MARKING
 SIGNAGE AS A METHOD TO DIRECT VEHICLES OUT OF GARAGE.
  
 13) SHEET 241-E2.7A AND SHEET 242-E2.7B, PROVIDE
 REQUIRED EMERGENCY LIGHTING FOR EGRESS FROM ROOF.
  
 14) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND
 WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 15) REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE
 THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF
 COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4).
  
 16) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 17) FIRE-RATED WALLS
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRE STOP SYSTEM
 OR DEVICE
 .
 18) TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT
 DOORS.
  
  