| 2016-06-23 15:20:27 | ROY LINDOW-6/23/16 |
| | FIRE PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | |
| | 1) SHEET 20?M3.1C, THIS SHEET SHOWS KITCHEN RANGE ON |
| | DRAWING. THE EXHAUST HOOD SHOWN ON PLANS IS NOT SHOWN |
| | OVER RANGE. KITCHEN EXHAUST AND FIRE SUPPRESSION SYSTEM |
| | REQUIRE SEPARATE PERMIT AND DRAWINGS. |
| | 2) SHEET 094-A-5.4 & SHEET 095-A-5.4.1 DOOR SCHEDULE, |
| | THE REMARKS KEY DOES NOT SHOW A SEPARATE KEY ITEM FOR |
| | LISTED FIRE EXIT HARDWARE. PROVIDE A KEY FOR ALL FIRE |
| | RATED DOORS TO HAVE LISTED FIRE EXIT HARDWARE. |
| | |
| | 7.2.1.7.2 ONLY APPROVED PANIC HARDWARE SHALL BE USED ON |
| | DOOR |
| | ASSEMBLIES THAT ARE NOT FIRE-RATED DOOR ASSEMBLIES. |
| | ONLY APPROVED FIRE |
| | EXIT HARDWARE SHALL BE USED ON FIRE-RATED DOOR |
| | ASSEMBLIES. NEW PANIC |
| | HARDWARE AND NEW FIRE EXIT HARDWARE SHALL COMPLY WITH |
| | ANSI/UL |
| | 305, STANDARD FOR SAFETY PANIC HARDWARE, AND ANSI/BHMA |
| | A156.3, EXIT DEVICES. |
| | |
| | 3) SHEET 012-C-09, PROVIDE NO PARKING FIRE LANE SIGNAGE |
| | (SEE PROVISO). |
| | |
| | 4) SHEET 042-LS-0.4, LEVELS 4-7, EXIT DOORS FROM THIS |
| | SPACE ARE NOT REMOTE PER SECTION, |
| | 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION |
| | 9.7, THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS, |
| | EXIT |
| | ACCESSES, OR EXIT DISCHARGES, MEASURED IN ACCORDANCE |
| | WITH 7.5.1.3.2, |
| | SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE |
| | MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE |
| | SERVED. |
| | |
| | 5) SHEET 051-A-2.4, EXIT DOORS FROM ASSEMBLY AREAS AND |
| | OTHER SPACES THAT EXCEED 100 OCCUPANT LOAD ARE NOT |
| | PROVIDED WITH PANIC HARDWARE. COORDINATE WITH DOOR |
| | SCHEDULE TO INDICATE CORRECT HARDWARE IS PROVIDED. |
| | EXAMPLES OF DOORS (412, 413, ST 401, ST 403 AND ST |
| | 406). |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA |
| | HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF |
| | THE LATCH OR |
| | LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING |
| | WITH |
| | 7.2.1.7, UNLESS OTHERWISE PERMITTED BY ONE OF THE |
| | FOLLOWING: |
| | |
| | 6) SHEET 051-A-2.4, EXIT DOOR SHOWN ON PLANS AS ST-405 |
| | SWINGS IN THE WRONG DIRECTION IN ADDITION IT IS NOT |
| | INCLUDED ON THE DOOR SCHEDULE AND WILL ALSO REQUIRE |
| | PANIC HARDWARE. |
| | |
| | 7) SHEET 044-A-2.1, DOORS SHOWN AS DOOR 139, 131 & 132 |
| | APPEAR TO SWING GREATER THAT 50% OF THE REQUIRED EXIT |
| | WIDTH AND EXCEED MAXIMUM PROJECTION PER SECTION, |
| | 7.2.1.4.3 |
| | |
| | 8) THIS IS FROM A PREVIOUS LIST OF COMMENTS #12 ON |
| | PREVIOUS LIST. |
| | SHEET 040-LS-0.2, PROVIDE ONE HOUR RATING TO SEPARATE |
| | CORRIDOR FROM GARAGE. |
| | ARROW POINTS TO AREA IN QUESTION. |
| | |
| | 9) SHEET 092-A-5.2.2, DUPLICATE NOTE. PLEASE REMOVE GAS |
| | FIREPLACE FROM PLANS. |
| | |
| | 10) SHEET 317-FS2.7B, AND SHEET 316-FS2.7A, REQUIRED |
| | FIRE SPRINKLER COVERAGE IS NOT PROVIDED FOR ELEVATOR |
| | MACHINE ROOMS. |
| | |
| | 11) SHEET-044-A-2.1, PROVISO NOTE ADDED TO PLANS. |
| | |
| | 12) GENERAL COMMENT, DO NOT UTILIZE EXIT MARKING |
| | SIGNAGE AS A METHOD TO DIRECT VEHICLES OUT OF GARAGE. |
| | |
| | 13) SHEET 241-E2.7A AND SHEET 242-E2.7B, PROVIDE |
| | REQUIRED EMERGENCY LIGHTING FOR EGRESS FROM ROOF. |
| | |
| | 14) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND |
| | WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL |
| | BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO |
| | CONSTRUCTION WORK. |
| | |
| | 15) REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE |
| | THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF |
| | COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4). |
| | |
| | 16) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | 17) FIRE-RATED WALLS |
| | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE |
| | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED |
| | WALL ASSEMBLY SHALL BE PROTECTED BY A FIRE STOP SYSTEM |
| | OR DEVICE |
| | . |
| | 18) TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT |
| | DOORS. |
| | |
| | |