| 2016-07-01 13:37:02 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | GOVERNING CODE: FBC 5TH EDITION (FBC 2014) |
| | |
| | 1-6. OK; ALSO SEE THRESHOLD AND IMPACT FEE REVIEWS. |
| | |
| | 7. TWO DOCUMENTS WERE UPLOADED AS LAND AND TITLE SURVEY |
| | (003-01 AND 004-02) BUT BOTH DOCUMENTS ARE ONE PAGE, |
| | FIRST PAGE OF A TWO PAGE SURVEY. PROVIDE THE SECOND |
| | PAGE, FBC 107. |
| | |
| | 8-10. OK |
| | |
| | 11. LS0.1, A SURFACE MOUNT FIRE EXTINGUISHER IS |
| | DEPICTED ON THE RAMP (S2 TO BUSINESS/RESIDENTIAL) BUT |
| | DOES NOT APPEAR ON SHEET A2.1; THIS DOES NOT APPEAR TO |
| | COMPLY WITH FBC 1003.3, 1012.8, FBC 5TH ED. |
| | ACCESSIBILITY 405.5. |
| | |
| | 2ND REVIEW, RESPONSE STATES THAT THIS WAS RELOCATED BUT |
| | A SFE IS NOW SHOWN ON THE LANDING OF THE RAMP ON LS0.1, |
| | BUT IS NOT ON SHEET A2.1 (AND RESPONSE LETTER APPEARS |
| | TO IMPLY THAT INTENT WAS TO REMOVE IT FROM THE RAMP); |
| | SAME COMMENTS APPLY. EITHER REMOVE OR CORRELATE WITH |
| | A2.1 AND PROVIDE DIMENSIONS TO CLARIFY COMPLIANCE. |
| | |
| | 12-16. OK |
| | |
| | 17. LS 0.1, IT APPEARS THAT INTERMEDIATE HANDRAILS ARE |
| | REQUIRED AT THE STAIR AT DOOR 115, FBC 1012.9. REVISE |
| | THIS SHEET AND PROVIDE A DIMENSIONED DETAIL FOR THE |
| | STAIR, FBC 107. |
| | |
| | RESPONSE LETTER STATES THAT THIS WAS ADDED, BUT LS0.1 |
| | AND A2.1 DO NOT APPEAR TO BE REVISED AT THIS LOCATION, |
| | PLEASE CORRELATE. |
| | |
| | 18-20. OK |
| | |
| | 21. LS 0.1, REVISE PLAN TO CLARIFY THE NUMBER OF |
| | OCCUPANTS EXITING THROUGH GATE 160. EXIT STAIR 4, EXIT |
| | STAIR 6, POOL AREA, CLUBHOUSE, 1ST FLOOR RESIDENTIAL |
| | LEAD TO THIS EXIT. |
| | |
| | 2ND REVIEW, OCCUPANCY CALCS AND RESPONSE LETTER SHOW AN |
| | OCCUPANT LOAD OF 395. PLEASE REVISE; PLAN SHOWS AT |
| | LEAST 468 (POOL DECK 375, POOL 50, GRILL AREA 20, A3 |
| | COVERED 23) OR CLARIFY. ALSO INCLUDE THE AREA WHICH IS |
| | NOT DESIGNATED ON THE LIFE SAFETY PLAN BUT IS SHOWN ON |
| | A2.1 AS OUTDOOR LIVING. |
| | LS0.1 EGRESS CAPACITY TABULATIONS INDICATE THAT THERE |
| | IS A 38IN EXIT IN ADDITION TO TWO 68IN EXITS. I WAS |
| | UNABLE TO LOCATE THE 38IN EXIT FOR THIS AREA, PLEASE |
| | CLARIFY OR REVISE. NOTE THAT EXITING APPEARS COMPLIANT |
| | WITHOUT THE THIRD EXIT. |
| | |
| | 22-25. OK |
| | |
| | 26. LS 0.2 AND OTHER SHEETS, A SURFACE MOUNT FIRE |
| | EXTINGUISHER IS SHOWN WHERE IT APPEARS TO OBSTRUCT THE |
| | ACCESSIBLE PARKING ACCESS AISLE. PROVIDE DIMENSIONS TO |
| | SHOW THAT THE ACCESS AISLE IS NOT OBSTRUCTED. |
| | |
| | 2ND REVIEW, RESPONSE LETTER STATES THIS WAS MOVED BUT |
| | THIS STILL APPEARS ON LS0.2, PLEASE CHECK ALL FLOORS |
| | AND REVISE. |
| | |
| | 27. LS 0.2, LS 0.4, UNITS A1 AND C2, TENANT / OCCUPANCY |
| | SEPARATION BETWEEN THE R2 UNITS AND THE A2 CORRIDOR IS |
| | LACKING, FBC TABLE 508.4. |
| | |
| | 2ND REVIEW, RESPONSE LETTER STATES THIS WAS PROVIDED |
| | BUT PLAN WAS NOT REVISED. PLEASE SEE WALL BETWEEN S2 |
| | AND R2 ADJACENT TO STAIR 2. |
| | |
| | 28. LS 0.4, THE DOORS SERVING THE NORTH ROOF DECK ARE |
| | TO SWING IN THE DIRECTION OF EGRESS TRAVEL, FBC |
| | 1008.1.10. |
| | |
| | 2ND REVIEW, PLEASE ALSO CLARIFY COMPLIANCE WITH FBC |
| | 1015.2.1. 11FT IS SHOWN BETWEEN THE TWO EXITS, BUT IT |
| | APPEARS THAT THE DIAGONAL IS GREATER THAN 33. |
| | |
| | 29-30. OK |
| | |
| | 31. SHEET S1 2A, SPECIFY FLOOR LOADS FOR THE ASSEMBLY |
| | AREAS (CLUBHOUSE ROOF DECK, GYM, EXERCISE ROOM). |
| | |
| | 2ND REVIEW, RESPONSE LETTER REFERS TO LS SHEETS BUT I |
| | WAS UNABLE TO LOCATE THIS REVISION. PLEASE ALSO |
| | INCORPORATE INTO THE APPLICABLE STRUCTURAL SHEET. |
| | |
| | 33-36. OK |
| | |
| | 36. S6.0, WALL PRESSURES SPECIFIED AND SOME PRODUCT |
| | APPROVALS WERE SUBMITTED BUT THE CHART IS A GENERAL |
| | ONE, NOT SPECIFIC TO EACH OPENING. THE PRODUCT |
| | APPROVALS ARE NOT MARKED TO INDICATE WHICH OF THE |
| | OPTIONS IS PROPOSED. EITHER PROVIDE A SCHEDULE TO SHOW |
| | DESIGN PRESSURES FOR EACH OPENING AND PRODUCT APPROVALS |
| | MARKED TO SHOW WHICH OPTION PROPOSED FOR EACH OPENING |
| | (OR ONE TO BE USED FOR ALL OPENINGS TO COMPLY WITH |
| | WORST CASE), OR THIS WILL BE A PROVISO ITEM (PROVIDE |
| | FOR REVIEW PRIOR TO INSTALLATION). |
| | |
| | 2ND REVIEW, RESPONSE LETTER DIRECTED ME TO THE PAGE |
| | WHERE FOUR PRODUCTS ARE REFERENCED. THE FOLLOWING |
| | ISSUES ARE NOTED: |
| | |
| | THE FIXED WINDOW PRODUCT APPROVAL REFERENCED ON SHEET |
| | A4.7 IS FOR SMALL MISSILE IMPACT; LMI REQUIRED BELOW |
| | 30FT (LMI NOA NOT INCLUDED IN THE PRODUCTS REVIEWED, |
| | BUT NOA UPLOADED, PLEASE CORRELATE). |
| | |
| | THE SERIES 9500 LMI FIXED WINDOW WAS UPLOADED, BUT IS |
| | NOT INCLUDED IN THE PRODUCTS REVIEWED (SHEET A4.7). |
| | |
| | THE FRENCH DOOR NOA 150611.10 PROVIDED DOES NOT APPEAR |
| | TO INCLUDE PANIC BAR HARDWARE OPTION, SO THIS PRODUCT |
| | CANNOT BE USED IN THE MEANS OF EGRESS FOR ASSEMBLY |
| | OCCUPANCY. THIS HAS BEEN INCLUDED IN THE PROVISO LIST |
| | (SUBMIT PRIOR TO INSTALLATION). |
| | |
| | ALL PRODUCT APPROVALS WERE REVIEWED FOR COMPLIANCE WITH |
| | WORST CASE DESIGN PRESSURES. MOST OPTIONS COMPLY. |
| | PROVISO; COMPONENT AND CLADDING TO COMPLY WITH WORST |
| | CASE DESIGN PRESSURES OR SUBMIT A SCHEDULE OF |
| | APPLICABLE OPENINGS AND PROPOSED INSTALLATION. |
| | |
| | 37. 2ND REVIEW, THE SOFFIT DETAIL LACKS A BOND BREAK |
| | REQUIRED (TWO LAYERS VAPOR BARRIER); PLEASE REVISE |
| | DETAIL ACCORDINGLY, FBC 1403.2, ASTM C926. |
| | |
| | 38-40. OK |
| | |
| | 41. SEE PLUMBING COMMENTS REGARDING FAIR HOUSING. ALL |
| | COMMENTS ARE ALSO APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 42. REGARDING ENERGY CALCS, IT APPEARS THAT THERE IS A |
| | 47,771 SF DISCREPANCY BETWEEN THE AREA ON THE ENERGY |
| | CALCS (CONDITIONED AREA 312,869) AND THE A SHEETS. |
| | NUMBER OF STORIES ON EC IS 5, NOT CONSISTENT WITH PLAN. |
| | THE DIGITAL SIGNATURE IS FOR VIVIANA FRANYIE, BUT THE |
| | PRINTED SEAL IS FOR ALEJANDRO FRANYIE (THIS APPLIES TO |
| | SOME OF THE FMEP SHEETS AS WELL, PLEASE CORRECT, |
| | FS471). |
| | |
| | 43-46. OK |
| | |
| | 47. SIGNED & SEALED SOILS REPORT WAS NOT UPLOADED BUT |
| | AN ORIGINAL WAS SUBMITTED WITH THE (ISSUED) |
| | VIBROFLOTATION PERMIT, SO NOT REQUIRED FOR THIS PERMIT. |
| | |
| | THE STRUCTURAL CALCS ARE NOT DIGITALLY SIGNED AND |
| | SEALED; PLEASE ADDRESS. |
| | |
| | 48-49. OK |
| | |
| | 49. PROVISO; |
| | |
| | 50. ADVISORY ONLY; SOME (BUT NOT ALL) PRODUCT APPROVALS |
| | HAVE BEEN SUBMITTED. APPLICANT MAY ELECT TO DEFER |
| | PRODUCT APPROVAL SUBMITTAL. THEY CAN BE SUBMITTED AFTER |
| | PERMIT ISSUANCE, PRIOR TO INSTALLATION, WITH NO |
| | ADDITIONAL FEES. |
| | |
| | 51. SEE ROOF REVIEW COMMENTS: |
| | |
| | ROOF NOAS FOR JM TPO SUBMITTED; 14-0618.03, 13-0529.02 |
| | |
| | A. ROOF PRODUCT APPROVALS WERE SUBMITTED BUT THE |
| | ASSEMBLY PROPOSED WAS NOT SELECTED AND ENGINEERING FOR |
| | ENHANCED FASTENING (WOOD DECK) WAS NOT PROVIDED. IF |
| | THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT |
| | ISSUANCE, THE INFORMATION WILL BE REQUIRED AT TIME OF |
| | ROOF SUB PERMIT SUBMITTAL. AN "N" WILL BE ENTERED FOR |
| | THE ROOF PLAN REVIEW. |
| | |
| | ROOF ASSEMBLIES SELECTED TO COMPLY WITH THE (VULT) |
| | PRESSURES SPECIFIED ON SHEET S6-1. |
| | |
| | B. SHEET S6-1, CLARIFY THE DIFFERENCE BETWEEN THE "ROOF |
| | MEMBRANE DESIGN PRESSSURE" VS. "GROSS UPLIFT DESIGN |
| | PRESSURES." THE DESIGN PRESSURES TO BE UTILIZED FOR THE |
| | TPO ROOF IS NOT CLEAR. |
| | |
| | C. SHEET S6-1, IT APPEARS THAT ROOF PRESSURES SPECIFIED |
| | USE ZONE 2 PRESSURES FOR ZONE 3. THE STAIR ROOFS, |
| | ELEVATOR ROOFS, CANOPIES (DETAIL 1-S4.1, A SHEETS |
| | BUILDING SECTIONS, OTHER PLACES) DO NOT INCLUDE A 3FT |
| | PARAPET, FBC 1609, ASCE7 10 30.6-1 NOTE 7. SEE ALSO |
| | ROOF REVIEW COMMENTS. IT IS NOT CLEAR WHICH DESIGN |
| | PRESSURES ARE SPECIFIED FOR THE ROOF. |
| | |
| | D. PLAN SHEET S1.9C AND OTHER SHEETS INCLUDE AN |
| | INDICATOR FOR DETAIL 1 S9.1A; UNABLE TO LOCATE THIS |
| | SHEET (S9.1A). PLEASE PROVIDE SHEET OR REVISE DETAIL |
| | INDICATOR TO CORRECT LOCATION. |
| | |
| | 54-56. OK |
| | |
| | RESPONSE LETTER STOPS AT COMMENT #56. AS IT IS NOT |
| | CLEAR WHICH OF THE ITEMS HAVE BEEN REVISED, OR WHERE, |
| | COMMENTS REMAIN. |
| | |
| | 58. A2.1, THE DOOR FOR UNIT 140 AND OTHER UNITS ARE NOT |
| | LABELED, FBC 107. THE INDEX SHOWS A DOOR SCHEDULE FOR |
| | THE AMENITY AREA. PLEASE ADVISE AS TO WHERE THE UNIT |
| | ENTRY DOOR SCHEDULE IS LOCATED OR PROVIDE. |
| | |
| | 59. FBC 424.1.3.1.9, 424.2.17, POOL BARRIER PROPOSED IS |
| | NOT CLEAR (WINDOWS LOCATED IN THE WALL WHICH SERVES AS |
| | THE POOL BARRIER). |
| | |
| | 2ND REVIEW; A NOTE WAS ADDED TO STATE THAT ALL UNIT |
| | BALCONY RAILINGS ARE AT 48IN (LS0.1). PLEASE REVISE |
| | PLAN TO SHOW INTENT FOR POOL BARRIER FOR THE FIRST |
| | FLOOR WINDOWS WHICH DIRECTLY FACE THE POOL. |
| | |
| | 60. SHEET A6.1, ITEM 68 SPECIFIES RIGID INSULATION, NOA |
| | 11-0516.02; THIS IS THE NOA NUMBER FOR WATERPROOFING, |
| | REVISE; ALSO SEE OTHER COMMENTS REGARDING NOA NUMBERS |
| | ON THE PLAN. |
| | |
| | 61. PROVIDE A GRAB BAR BACKING DETAIL, FBC 107. |
| | |
| | 62. FHA, NOT ALL OF THE SLIDING GLASS DOORS PROPOSED |
| | ARE 6FT; FOR INSTANCE, SEE UNIT S2, SHEET A4.1. SEE |
| | PAGE 3.10 OF THE FAIR HOUSING ACT DESIGN MANUAL AND THE |
| | GUIDANCE REGARDING SLIDING GLASS PATIO DOORS (SECONDARY |
| | DOOR) AND REVISE PLAN TO DEMONSTRATE COMPLIANCE. |
| | |
| | 63. DETAIL 2-S4.1 GRAPHICALLY DEPICTS AN EMBEDDED STRAP |
| | BUT DOES NOT SPECIFY. PLEASE EITHER PROVIDE INFORMATION |
| | AS TO WHERE THIS INFORMATION CAN BE FOUND OR REVISE |
| | PLAN TO SPECIFY CONNECTORS. |
| | |
| | 64. DETAILS 1 AND 2, S4.1, PLEASE PROVIDE DIRECTION AS |
| | TO WHICH PLAN VIEW SHEET THE DETAIL INDICATOR FOR THESE |
| | DETAILS ARE LOCATED. |
| | |
| | 65. FIRST FLOOR (LS 0.1 AND OTHER SHEETS), ADJACENT TO |
| | STAIR 3, A RAMP IS SHOWN BUT NO STAIR TO ACCESS THE |
| | RESIDENTIAL CORRIDOR FROM THE GARAGE. IT IS SUGGESTED |
| | THAT AN ACCESSIBLE STAIR BE ADDED. THE RAMP ADDS |
| | DISTANCE TO THE PATH OF TRAVEL WHICH COULD BE A |
| | HARDSHIP FOR SOMEONE WHO IS DISABLED OR COMPROMISED, |
| | DOES NOT USE A WHEELCHAIR AND IS ABLE TO NAVIGATE A |
| | STAIR. |
| | |
| | 66. OK |
| | |
| | NEW COMMENT: |
| | |
| | 67. WHEN RESUBMITTING, PLEASE PROVIDE AN UPDATED INDEX |
| | SPREADSHEET TO INDICATE WHICH SHEETS CHANGED IN THIS |
| | AND NEXT REVIEWS. ALL SHEETS HAVE NOT BEEN REVIEWED AT |
| | THIS TIME AS ALL SHEETS WERE REPLACED DUE TO DIGITAL |
| | SIGNATURE, ONLY SHEETS WHICH WERE AFFECTED BY THIS |
| | COMMENT LIST. IF PROVIDED WITH A LIST OF ALL SHEETS |
| | WITH CHANGES FOR THIS SUBMITTAL, THIS WILL EXPEDITE THE |
| | LAST REVIEW AS ALL SHEETS WILL BE CHECKED PRIOR TO |
| | ISSUANCE. |
| | |
| | THIS LIST MAY BE SENT TO ME VIA EMAIL PRIOR TO |
| | RESUBMITTAL AND THE SHEETS WILL BE REVIEWED IN THIS |
| | CYCLE. |
| | |
| | THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS: |
| | |
| | 1. PER FS 553.79, ALL SHORING/RE-SHORE ENGINEERING IS |
| | TO BE REVIEWED BY ENGINEER OF RECORD AND THREE SIGNED |
| | AND SEALED ORIGINAL SETS ARE TO BE SUBMITTED FOR PLAN |
| | REVIEW. THE SHORING/RESHORE ENGINEERING IS TO BE |
| | REVIEWED AND APPROVED PRIOR TO INSPECTION. THE CITY |
| | APPROVED (CITY STAMPED) SHORING/RE-SHORE ENGINEERING IS |
| | TO BE AVAILABLE ON THE JOB AT THE TIME OF INSPECTION. |
| | |
| | 2. PRIOR TO INSTALLATION, A SHORING/RESHORE GUARD RAIL |
| | DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD |
| | BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. |
| | |
| | 3. A REPLAT IS REQUIRED PRIOR TO C.O. AS THE PROPOSED |
| | CONSTRUCTION CROSSES PROPERTY LINE, FBC 705.8. PROVIDE |
| | THE BOOK AND PAGE WHERE THIS HAS BEEN RECORDED WHEN |
| | AVAILABLE. |
| | |
| | 4. PROVISO, ACCESSIBLE MEANS OF EGRESS, FBC 5TH EDITION |
| | ACCESSIBILITY 207, NO METHOD SELECTED; COMPLIANCE WITH |
| | BOTH REQUIRED OR, IF ANY FIELD ISSUES ARISE, A REVISION |
| | IS REQUIRED. |
| | |
| | 5. PROVISO, A SEPARATE ROOF PERMIT IS REQUIRED. PRODUCT |
| | APPROVALS REVIEWED BY DESIGNER OF RECORD IS TO BE |
| | SUBMITTED WITH A PERMIT APPLICATION. CONTRACTOR IS TO |
| | INDICATE ASSEMBLY PROPOSED AND, IF APPLICABLE, PROVIDE |
| | ENGINEERING. |
| | |
| | 6. PROVISO; COMPONENT AND CLADDING TO COMPLY WITH WORST |
| | CASE DESIGN PRESSURES OR SUBMIT AS A REVISION; PROVIDE |
| | A SCHEDULE OF APPLICABLE OPENINGS AND PROPOSED |
| | INSTALLATION. |
| | |
| | 7. PROVISO; SEPARATE PERMITS (APPLICATION, PLANS, FEES, |
| | REVIEW) REQUIRED FOR POOL. THE PLANS HAVE BEEN MARKED |
| | ?VOID? AND HAVE NOT BEEN REVIEWED. |
| | |
| | 8. PROVISO; THE FOLLOWING PRODUCT APPROVALS OR SITE |
| | SPECIFIC ENGINEERING ARE REQUIRED TO BE SUBMITTED AS A |
| | REVISION AND REVIEWED PRIOR TO INSTALLATION: |
| | |
| | PRODUCT APPROVALS: |
| | MECHANICAL LOUVERS |
| | WINDOWS (WITH EXCEPTION OF NOAS ALREADY SUBMITTED) |
| | SERIES 8000 ALUMINUM WINDOW WALL SYSTEM (15-0727.05, |
| | SHEET A5.5) |
| | EXTERIOR DOORS |
| | ASSEMBLY OCCUPANCY EXTERIOR DOORS |
| | GENSTORM OPTION #1 LOUVER OUTSWING STEEL DOOR, DOUBLE |
| | (A5.4) |
| | OHD |
| | BAR TELS FRAMELESS DOORS (A5.4) |
| | ALL OTHER COMPONENTS AND CLADDING NOT SUBMITTED AND |
| | REVIEWED PRIOR TO PERMIT ISSUANCE |
| | |
| | DELEGATED ENGINEERING: |
| | GREEN SCREEN ALUMINUM FRAME SYSTEM |
| | 2ND LEVEL METAL CANOPY |
| | TRELLIS |
| | SHADE STRUCTURES |
| | RAILINGS |
| | PRECAST CONCRETE (S7.0, DELEGATED ENGINEERING |
| | CONNECTIONS) |
| | PRECAST STAIRS AND LANDINGS |
| | AWNINGS AND CANOPIES |
| | OTHER DELEGATED ENGINEERING ITEMS |
| | |
| | 9. PROVISO, ALL PRODUCT APPROVALS TO BE PRINTED IN AN |
| | EASILY LEGIBLE FORMAT (PLAN PAGES MINIMUM OF 8.5X11IN |
| | FULL SHEET OR, PREFERABLY 11X17). |
| | |
| | 10. PROVISO, THE FOLLOWING TEST REPORTS FOR THE |
| | FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO |
| | INSTALLATION (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR |
| | SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR |
| | LESS ARE ACCEPTABLE): STC (FBC 1207.2), IIC (FBC |
| | 1207.3), ASTM E 84 (FBC 603.1). |
| | |
| | 11. FS 553.79(7)(C) ALL SHORING AND RESHORING |
| | PROCEDURES, PLANS, AND DETAILS BE SUBMITTED TO THE |
| | ENFORCEMENT AGENCY FOR RECORDKEEPING. SHORING/RESHORE |
| | ENGINEERING IS TO BE SUBMITTED AT EACH LIFT. FAILURE TO |
| | SUBMIT SHORING/RESHORE PLANS TO THE BUILDING DIVISION |
| | FOR PLAN REVIEW AT THE TIME OF EACH LIFT MAY RESULT IN |
| | A STOP WORK ORDER. AS THIS ISSUE HAS BEEN PROBLEMATIC |
| | IN THE PAST, IT IS RECOMMENDED THAT A NOTE BE |
| | INCORPORATED INTO THE PLAN. |
| | |
| | 12. PROVISO, ALL DOORS AND GATES IN THE MEANS OF EGRESS |
| | FOR ASSEMBLY OCCUPANCY SHALL HAVE PANIC DEVICES OR FIRE |
| | EXIT HARDWARE, FBC 1008. A REVISION INCLUDING PRODUCT |
| | APPROVALS WITH PANIC DEVICES PROPOSED IS TO BE |
| | SUBMITTED PRIOR TO INSTALLATION. |
| | |