2016-03-11 14:14:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ROOF NOAS FOR JM TPO SUBMMITTED; 14-0618.03, 13-0529.02
  
 1. ROOF PRODUCT APPROVALS WERE SUBMITTED BUT THE
 ASSEMBLY PROPOSED WAS NOT SELECTED AND ENGINEERING FOR
 ENHANCED FASTENING (WOOD DECK) WAS NOT PROVIDED. IF
 THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT
 ISSUANCE, THE INFORMATION WILL BE REQUIRED AT TIME OF
 ROOF SUB PERMIT SUBMITTAL. AN "N" WILL BE ENTERED FOR
 THE ROOF PLAN REVIEW.
  
 ROOF ASSEMBLIES SELECTED TO COMPLY WITH THE (VULT)
 PRESSURES SPECIFIED ON SHEET S6-1.
  
 2. SHEET S6-1, CLARIFY PURPOSE OF "ROOF MEMBRANE DESIGN
 PRESSSURE" VS. "GROSS UPLIFT DESIGN PRESSURES." THE
 DESIGN PRESSURES TO BE UTILIZED FOR THE TPO ROOF IS NOT
 CLEAR.
  
 3. SHEET S6-1, ROOF PRESSURES SPECIFIED USE ZONE 2
 PRESSURES FOR ZONE 3. IT APPEARS THAT THE STAIR ROOF,
 ELEVATOR ROOF DO NOT INCLUDE A 3FT PARAPET, FBC 1609,
 ASCE7 10 30.6-1 NOTE 7.
  
  
  