| Plan Review Notes For Permit 16020194 |
| Permit Number |
16020194 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-11 14:14:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ROOF NOAS FOR JM TPO SUBMMITTED; 14-0618.03, 13-0529.02 | | | | | | 1. ROOF PRODUCT APPROVALS WERE SUBMITTED BUT THE | | | ASSEMBLY PROPOSED WAS NOT SELECTED AND ENGINEERING FOR | | | ENHANCED FASTENING (WOOD DECK) WAS NOT PROVIDED. IF | | | THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT | | | ISSUANCE, THE INFORMATION WILL BE REQUIRED AT TIME OF | | | ROOF SUB PERMIT SUBMITTAL. AN "N" WILL BE ENTERED FOR | | | THE ROOF PLAN REVIEW. | | | | | | ROOF ASSEMBLIES SELECTED TO COMPLY WITH THE (VULT) | | | PRESSURES SPECIFIED ON SHEET S6-1. | | | | | | 2. SHEET S6-1, CLARIFY PURPOSE OF "ROOF MEMBRANE DESIGN | | | PRESSSURE" VS. "GROSS UPLIFT DESIGN PRESSURES." THE | | | DESIGN PRESSURES TO BE UTILIZED FOR THE TPO ROOF IS NOT | | | CLEAR. | | | | | | 3. SHEET S6-1, ROOF PRESSURES SPECIFIED USE ZONE 2 | | | PRESSURES FOR ZONE 3. IT APPEARS THAT THE STAIR ROOF, | | | ELEVATOR ROOF DO NOT INCLUDE A 3FT PARAPET, FBC 1609, | | | ASCE7 10 30.6-1 NOTE 7. | | | | | | | | | |
|