Plan Review Notes
Plan Review Notes For Permit 16020194
Permit Number 16020194
Review Stop P
Sequence Number 1
Notes
Date Text
2016-03-10 14:28:401ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 (FHA)
  
 1. SHT. A-10.4 UNIT C2 WHAT SPECIFICATION IS THE MASTER
 BATH.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 2. A CLEAR FLOOR SPACE WITH A PARALLEL APPROACH IS
 REQUIRED FOR ALL SHOWERS.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 3. SHOW HEIGHT OF REINFORCEMENT FOR GRAB BARS AND
 SHOWER SEATS.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT 6
 4. SHT. A-10.4 UNIT C1 ALL SHOWERS SHALL HAVE PARALLEL
 APPROACH CLEAR FLOOR SPACE SHOWERS IN TYPE A BATHROOM
 CANNOT COMPLY.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 5. SHT. A-10.4 UNIT C3 A MEANS OF PROVIDING KNEE SPACE
 FOR LAVATORY'S WITH FRONT APPROACH CLEAR FLOOR SHALL BE
 SHOWN ON PLANS.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 6. SHT. A-10.1 UNITS S1-S2-A4 SHOW CLEAR FLOOR SPACE
 FOR TUBS.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 7. SHT. A10.1 UNIT A1-3 MIN. DIMENSION OF SHOWER DOOR
 SHOULD BE 32IN. WIDE.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 8. PLEASE INDICATE DEPTH OF LAVATORY VANITY MAX. OF
 24IN. .
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT5
 9. SHT.A01.4 UNIT C1 CLEAR FLOOR SPACE FOR TUB SHALL BE
 FLUSH WITH CONTROL WALL OF TUB.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 10. SHT. A-10.4 UNIT C3 WING WALL NEXT TO TOILET SHALL
 BE MAX OF 24IN.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 B
 11. PLEASE SHOW IN ALL KITCHENS A 3'-4" CLEARANCE
 BETWEEN APPOSING CABINETS AND APPLIANCES.
 UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART
 A
  
 (PLUMBING)
  
 1. SHT.P-2.1A STACK B1 SHALL CONNECT TO BUILDING DRAIN
 DOWN STREAN OF THE POOL BATHROOM GROUP MENS BATH.
 PER FBC PL SEC. 912.1
 2. PLEASE PROVIDE MANUFACTURE SPEC SHEETS AND SIZING
 CALCULATIONS FOR GREASE INTERCEPTOR IN KITCHEN OF
 CLUBHOUSE.
 WPB AMEND. TO FBC SEC. 107.2.1.3
 3. THERE IS NO FLOOR DRAIN IN TRASH SHUTE ROOMWHERE
 WILL WATER DRAIN WHEN FLOOR IS DRAINED.
 WPB AMEND. TO FBC SEC. 107.2.1
 4. SHT. P-5.5 MOP SINK IN MAINTANCE ROOM IS NOT SHOWN
 ON RISER DIAGRAM PLEASE CLARIFY.
 WPB AMEND. TO FBC SEC. 107.2.1
 5. SHT. P5.3 STACK C-C1-C2 SHOWS THE WC, SH. AND LAV
 BRANCH FITTINGS ARE STACKED ON TOP OF EACH OTHER, IS
 THIS THE WAY IT WILL BE PIPED UNDER THE SLAB, IT WILL
 BE DEFACUIT TO DO IT THAT WAYPLEASE CLARIFY.
 MAY BE UNDERSIZED.
 PER FBC PL TABLE E201.1
 6. P-5.7 PROVIDE SANITARY AND WATER RISER DIAGRAM
 BATHROOMS IN OFFICES AND LEASING CENTER.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3
 7. SHT. C-09 THE TOTAL DFU'S OF THE BUILDING SEWER
 EXCEEDS THE MAXIMUM ALLOWED ON THE EXISTING 8" CITY
 SEWER LATERAL .
 PER FBC PL TABLE 710.1(1) CONTACT MANUAL GONZALEZ AT
 561-494-1040 EX.1085
 8. SHT. P-5.1 UNIT C1- C2 THE 1/2" COLD WATER LINE
 SUPPLING THE MASTER BATH AND WASHING MACHINE MAY BE
 UNDERSIZED.
 PER FBC PL TABLE E201.1
 9. SHT. P-5.1 UNIT A1-4 THE 1/2" COLD WATERLINE
 SUPPLYING BOTH BATHROOMS MAY BE UNDERSIZED.
 PER FBC PL TABLE E201.1
 10. SHT. P-5.2 RISER #3 MAY BE UNDERSIZED.
 PER FBC PL TABLE E201.1
 11. SHT. P-6.2 DETAIL #2 SHOWS 5" SUCTION AND DISCHARGE
 DETAIL #3 AND SHT.P-5.7 SHOWS 6" PLEASE CLARIFY.
 WPB AMEND. TO FBC SEC. 107.2.1
 12. PLEASE PROVIDE MANUFACTURE SPECS FOR DOMESTIC
 PUMP,WATER HEATERS, SUMP PUMPS, OIL SPILL ALARM.
 WPB AMEND. TO FBC SEC. 107.2.1
 13. SHOW DRAINS FOR ELEVATOR SUMP PITS ON SANITARY
 COLLECTION DIAGRAM.
 WPB AMEND. TO FBC SEC. 107.2.1
 14. SHT. P-2.7A+B THE MATCH LINES REFER TO P-2.6 A+B IS
 THIS CORRECT P-2.7 ARE ROOF PLANS AND P-2.6 ARE EIGHT
 FLOOR PLANS PLEASE CLARIFY.
 WPB AMEND. TO FBC SEC. 107.2.1
 15. SHT. P-2.7 B RD ON TOP OF STAIRWELL #1 IS NOT SHOWN
 ON RISER DIAGRAM PLEASE CLARIFY.
 WPB AMEND. TO FBC SEC. 107.2.1
 16. SHT. P-2.7A WHERE IS THE RAIN WATER FROM ELEVATOR
 SHAFT ROOF DRAIN TO.
 WPB AMEND. TO FBC SEC. 107.2.1
 17. SHOW OVERFLOW SCUPPERS ON ROOF PLAN WITH DETAILS.
 WPB AMEND. TO FBC SEC. 107.2.1
 18. PLEASE CLARIFY HOW ARE YOU DRAINING ROOF OF
 CLUBHOUSE SHT. P-5.8 SHOWS STORM DRAIN FOR CLUB HOUSE
 BUT NO RISER DIAGRAM.
 WPB AMEND. TO FBC SEC. 107.2.1
 19. PROVIDE DETAIL FOR STORM SUMP PIT NEXT TO BICYCLE
 RACK.
 WPB AMEND. TO FBC SEC. 107.2.1
 20. SHT. A-5.1.5 SHOWS TOILET CLEARANCE OFF SIDE WALLAT
 18 MIN. IT SHOULD SHOW 16" MIN 18" MAX TO COMPLY WITH
 FBC ACC. SEC. 604.2 ALL PUBLIC ACC. TOILETS SHALL
 COMPLY.
 21. FLUSHING RING REQUIRED ON TRASH AND RECYCLING
 SHUTE. PROVIDE DETAIL AND SHOW ON WATER RISER DIAGRAM.
 WPB AMEND. TO FBC SEC. 107.2.1
  
 (IRRIGATION)
  
 1. SHT. LR-1 NOTER ON WATER SUPPLY FOR FOUNTAIN TO PUMP
 VAULT CONNECT BETWEEN PVB AND MASTER VALVE IS THAT
 CONNECTION BEING MADE ON THE DOWN STREAM SIDE OF PVB.
 WPB AMEND. TO FBC SEC. 107.2.1
 2. SHOW LOCATION OF RAIN SENSOR.
 WPB AMEND. TO FBC SEC. 107.2.1
 3. SHT. LR-1A CLUBHOUSE DECK IRRIGATION SHALL HAVE
 BACKFLOW PROTECTION IF CONNECTED TO POTABLE WATER
 SYSTEM AND BE SHOWN ON RISER DIAGRAM.
 WPB AMEND. TO FBC SEC. 107.2.1
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  