| 2016-03-10 14:28:40 | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | (FHA) |
| | |
| | 1. SHT. A-10.4 UNIT C2 WHAT SPECIFICATION IS THE MASTER |
| | BATH. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 2. A CLEAR FLOOR SPACE WITH A PARALLEL APPROACH IS |
| | REQUIRED FOR ALL SHOWERS. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 3. SHOW HEIGHT OF REINFORCEMENT FOR GRAB BARS AND |
| | SHOWER SEATS. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT 6 |
| | 4. SHT. A-10.4 UNIT C1 ALL SHOWERS SHALL HAVE PARALLEL |
| | APPROACH CLEAR FLOOR SPACE SHOWERS IN TYPE A BATHROOM |
| | CANNOT COMPLY. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 5. SHT. A-10.4 UNIT C3 A MEANS OF PROVIDING KNEE SPACE |
| | FOR LAVATORY'S WITH FRONT APPROACH CLEAR FLOOR SHALL BE |
| | SHOWN ON PLANS. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 6. SHT. A-10.1 UNITS S1-S2-A4 SHOW CLEAR FLOOR SPACE |
| | FOR TUBS. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 7. SHT. A10.1 UNIT A1-3 MIN. DIMENSION OF SHOWER DOOR |
| | SHOULD BE 32IN. WIDE. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 8. PLEASE INDICATE DEPTH OF LAVATORY VANITY MAX. OF |
| | 24IN. . |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT5 |
| | 9. SHT.A01.4 UNIT C1 CLEAR FLOOR SPACE FOR TUB SHALL BE |
| | FLUSH WITH CONTROL WALL OF TUB. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 10. SHT. A-10.4 UNIT C3 WING WALL NEXT TO TOILET SHALL |
| | BE MAX OF 24IN. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | B |
| | 11. PLEASE SHOW IN ALL KITCHENS A 3'-4" CLEARANCE |
| | BETWEEN APPOSING CABINETS AND APPLIANCES. |
| | UNDER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENT7 PART |
| | A |
| | |
| | (PLUMBING) |
| | |
| | 1. SHT.P-2.1A STACK B1 SHALL CONNECT TO BUILDING DRAIN |
| | DOWN STREAN OF THE POOL BATHROOM GROUP MENS BATH. |
| | PER FBC PL SEC. 912.1 |
| | 2. PLEASE PROVIDE MANUFACTURE SPEC SHEETS AND SIZING |
| | CALCULATIONS FOR GREASE INTERCEPTOR IN KITCHEN OF |
| | CLUBHOUSE. |
| | WPB AMEND. TO FBC SEC. 107.2.1.3 |
| | 3. THERE IS NO FLOOR DRAIN IN TRASH SHUTE ROOMWHERE |
| | WILL WATER DRAIN WHEN FLOOR IS DRAINED. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 4. SHT. P-5.5 MOP SINK IN MAINTANCE ROOM IS NOT SHOWN |
| | ON RISER DIAGRAM PLEASE CLARIFY. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 5. SHT. P5.3 STACK C-C1-C2 SHOWS THE WC, SH. AND LAV |
| | BRANCH FITTINGS ARE STACKED ON TOP OF EACH OTHER, IS |
| | THIS THE WAY IT WILL BE PIPED UNDER THE SLAB, IT WILL |
| | BE DEFACUIT TO DO IT THAT WAYPLEASE CLARIFY. |
| | MAY BE UNDERSIZED. |
| | PER FBC PL TABLE E201.1 |
| | 6. P-5.7 PROVIDE SANITARY AND WATER RISER DIAGRAM |
| | BATHROOMS IN OFFICES AND LEASING CENTER. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.3 |
| | 7. SHT. C-09 THE TOTAL DFU'S OF THE BUILDING SEWER |
| | EXCEEDS THE MAXIMUM ALLOWED ON THE EXISTING 8" CITY |
| | SEWER LATERAL . |
| | PER FBC PL TABLE 710.1(1) CONTACT MANUAL GONZALEZ AT |
| | 561-494-1040 EX.1085 |
| | 8. SHT. P-5.1 UNIT C1- C2 THE 1/2" COLD WATER LINE |
| | SUPPLING THE MASTER BATH AND WASHING MACHINE MAY BE |
| | UNDERSIZED. |
| | PER FBC PL TABLE E201.1 |
| | 9. SHT. P-5.1 UNIT A1-4 THE 1/2" COLD WATERLINE |
| | SUPPLYING BOTH BATHROOMS MAY BE UNDERSIZED. |
| | PER FBC PL TABLE E201.1 |
| | 10. SHT. P-5.2 RISER #3 MAY BE UNDERSIZED. |
| | PER FBC PL TABLE E201.1 |
| | 11. SHT. P-6.2 DETAIL #2 SHOWS 5" SUCTION AND DISCHARGE |
| | DETAIL #3 AND SHT.P-5.7 SHOWS 6" PLEASE CLARIFY. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 12. PLEASE PROVIDE MANUFACTURE SPECS FOR DOMESTIC |
| | PUMP,WATER HEATERS, SUMP PUMPS, OIL SPILL ALARM. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 13. SHOW DRAINS FOR ELEVATOR SUMP PITS ON SANITARY |
| | COLLECTION DIAGRAM. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 14. SHT. P-2.7A+B THE MATCH LINES REFER TO P-2.6 A+B IS |
| | THIS CORRECT P-2.7 ARE ROOF PLANS AND P-2.6 ARE EIGHT |
| | FLOOR PLANS PLEASE CLARIFY. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 15. SHT. P-2.7 B RD ON TOP OF STAIRWELL #1 IS NOT SHOWN |
| | ON RISER DIAGRAM PLEASE CLARIFY. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 16. SHT. P-2.7A WHERE IS THE RAIN WATER FROM ELEVATOR |
| | SHAFT ROOF DRAIN TO. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 17. SHOW OVERFLOW SCUPPERS ON ROOF PLAN WITH DETAILS. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 18. PLEASE CLARIFY HOW ARE YOU DRAINING ROOF OF |
| | CLUBHOUSE SHT. P-5.8 SHOWS STORM DRAIN FOR CLUB HOUSE |
| | BUT NO RISER DIAGRAM. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 19. PROVIDE DETAIL FOR STORM SUMP PIT NEXT TO BICYCLE |
| | RACK. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 20. SHT. A-5.1.5 SHOWS TOILET CLEARANCE OFF SIDE WALLAT |
| | 18 MIN. IT SHOULD SHOW 16" MIN 18" MAX TO COMPLY WITH |
| | FBC ACC. SEC. 604.2 ALL PUBLIC ACC. TOILETS SHALL |
| | COMPLY. |
| | 21. FLUSHING RING REQUIRED ON TRASH AND RECYCLING |
| | SHUTE. PROVIDE DETAIL AND SHOW ON WATER RISER DIAGRAM. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | (IRRIGATION) |
| | |
| | 1. SHT. LR-1 NOTER ON WATER SUPPLY FOR FOUNTAIN TO PUMP |
| | VAULT CONNECT BETWEEN PVB AND MASTER VALVE IS THAT |
| | CONNECTION BEING MADE ON THE DOWN STREAM SIDE OF PVB. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 2. SHOW LOCATION OF RAIN SENSOR. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | 3. SHT. LR-1A CLUBHOUSE DECK IRRIGATION SHALL HAVE |
| | BACKFLOW PROTECTION IF CONNECTED TO POTABLE WATER |
| | SYSTEM AND BE SHOWN ON RISER DIAGRAM. |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |