| 2016-02-24 16:51:43 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16020194 |
| | 2/23/16 |
| | |
| | 1) DISCREPANCIES BETWEEN THE FIFTH EDITION 2014 ENERGY |
| | EFFICIENCY COMPLIANCE FORM SUBMITTAL AND THE AC PLANS |
| | AND EQUIPMENT SCHEDULES: |
| | A) COMPLIANCE FORM LISTS RTU'S 1-5 AT 338,000 BTUH |
| | COOLING EACH AT 11.30 EER EACH, |
| | -THE AC SCHEDULE INDICATES 322,130 BTUH COOLING AT 12.8 |
| | EER. |
| | B) FORM LISTS THE FITNESS CENTER SPLIT SYSTEM AT |
| | 150,000 BTUH COOLING AT 12 EER, |
| | - THE SCHEDULE INDICATES 120,000 BTUH COOLING AT 11.2 |
| | EER |
| | C) FORM LISTS THE OFFICE 136 AND 137 SPLIT SYSTEMS AT |
| | 42,000 BTUH COOLING AT 14 SEER, |
| | - THE SCHEDULE INDICATES TOTAL COOLING CAPACITY FOR |
| | EACH AT 30,000 BTUH AT 14 SEER. |
| | D) FORM LISTS THE THEATER SPLIT SYSTEM AT 23,000 BTUH |
| | COOLING AT 16 SEER, |
| | - THE SCHEDULE INDICATES 24,000 BTUH COOLING AT 16.5 |
| | SEER. |
| | E) TWO LEASING CENTER SPLIT SYSTEMS ARE INDICATED ON |
| | THE SCHEDULE WITH CAPACITIES AND EFFICIENCY RATINGS |
| | THAT DON'T MATCH THE SINGLE LEASING CENTER SYSTEM |
| | LISTED ON THE COMPLIANCE FORM. |
| | F) FORM LISTS AHU-5 AT 46,000/14 SEER, THE SCHEDULE |
| | LISTS 30,000/14. |
| | G) FORM LISTS RES LOBBY-N & S AT 12,000/14 SEER, |
| | SCHEDULE LISTS 9,000/14.5 SEER. |
| | H) FORM LISTS THE CLUBHOUSE FITNESS AT 90,000/12 EER, |
| | THE SCHEDULE ON SHEET M-5.3 LISTS THRE FITNESS ROOM AT |
| | 2.5TON/15 SEER. |
| | I) FORM LISTS ST1 & ST2 SYSTEMS AT 12,000/14 SEER, THE |
| | SCHEDULE LISTS RESIDENTIAL AC-1.2 AT 15,000/14 SEER. |
| | J) THERE IS NO COMPLIANCE DATA LISTED ON THE ENERGY |
| | FORM FOR RTU'S A & B SHOWN IN THE SCHEDULE ON M-5.3, |
| | AND FOR THE DUCTLESS SYSTEMS AC-1- AC-13 SHOWN ON SHEET |
| | M-5.1. |
| | |
| | 2) THE AC IDENTIFICATION LABELS FOR THE RESIDENTIAL |
| | UNITS USED IN THE ENERGY AND AC COOLING AND HEATING |
| | LOAD SUMMARIES SUBMITTALS DO NOT DIRECTLY CORRELATE |
| | WITH THE LABELING SHOWN IN THE SCHEDULE ON SHEET M-5.1. |
| | THE LOAD SUMMARIES ARE ALSO INDICATING EACH SYSTEM AS A |
| | SINGLE ZONE HOWEVER EACH OF THESE SYSTEMS ARE SHOWN ON |
| | THE PLANS TO BE LOCATED IN MULTIPLE DIRECTIONAL |
| | ORIENTATIONS- PLEASE REFER TO SECTIONS C407.4.2- |
| | C407.5.2.3 FBC-14 ENERGY CONSERVATION- |
| | MULTIFAMILY RESIDENTIAL BUILDINGS. |
| | RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL |
| | BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME |
| | ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE |
| | THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR |
| | FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING |
| | THESE FEATURES. |
| | AS STATED IN THE ABOVE CODE SECTIONS CALCULATIONS SHALL |
| | BE DONE USING THERMAL BLOCKS AND ZONES. REVISE THE |
| | CALCULATIONS ACCORDINGLY AND PROVIDE A THERMAL ZONE |
| | DIAGRAM AND SCHEDULE TO ACCOMPANY THE CALCULATIONS. THE |
| | SCHEDULE SHALL CLEARLY INDICATE WHICH SYSTEMS ARE IN |
| | WHICH BLOCK OR ZONE, AND THE DIRECTIONAL ORIENTATIONS. |
| | A) PLEASE NOTE THAT AC CALCULATIONS HAVE NOT BEEN |
| | SUBMITTED FOR THE DUCTLESS SYSTEMS. |
| | B) THE CALCULATIONS FOR THE FITNESS ROOM INDICATE 127.9 |
| | MBH OR 10.7 TONS, HOWEVER THE SCHEDULE IS INDICATING |
| | 2.5 TONS FOR FITNESS ROOM RTU-A ON SHEET M-5.3. |
| | C) THE SUBMITTED AC SYSTEM SIZING SUMMARY SHEETS MUST |
| | BE SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL |
| | PER SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) SHEET M-5.3, OUTSIDE AIR CALCULATIONS: PROVIDE |
| | CALCULATIONS FOR THE RESIDENTIAL UNITS, THE CORRIDORS, |
| | THE BRIDGE AREA, THE WORK ROOMS, AND THE DOG PARLOR PER |
| | TABLE 403.3 FBC-14 MECHANICAL. |
| | 4) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | TRASH ROOMS, RESIDENTIAL BATHROOMS, POOL BATHROOMS, |
| | POOL EQUIPMENT ROOMS, MAINTENANCE ROOMS, ELECTRICAL |
| | ROOMS, STORAGE ROOMS, PUMP ROOMS, DOG PARLOR, OFFICE |
| | 136 & 137 & OFFICE AREA TOILET ROOMS, SERVICE COURT, |
| | AND THE FITNESS CLUB ROOM. |
| | 5) PROVIDE AIR BALANCE CALCULATIONS. |
| | 6) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR EACH |
| | LEVEL OF THE GARAGE- REFER TO SECTION 404.2 FBC-14 |
| | MECHANICAL. PLEASE NOTE THAT THE GROUND AND SECOND |
| | LEVEL PLANS M-2.1A AND M-2.1A APPEAR TO INDICATE A |
| | SUPPLY AIR FAN "GE-1A" HOWEVER I AM NOT SEEING ANY DATA |
| | FOR THE FANS IN THE SCHEDULES, NOR ARE THESE FANS SHOWN |
| | ON THE 3RD- 8TH LEVELS. |
| | 7) GARAGE- ALL LEVELS: INDICATE HOW ALL THE FANS, AC |
| | CONDENSERS, AND OTHER MECHANICAL EQUIPMENT AND |
| | COMPONENTS WILL BE PROTECTED FROM VEHICLE DAMAGE- |
| | SECTION 303.4 FBC-14 MECHANICAL |
| | 8) SHEETS M-2.1A- M-2.6B: VENTILATION NOT SHOWN FOR THE |
| | ELECTRICAL ROOMS, THE TELECOM ROOMS, AND THE STORAGE |
| | ROOMS ON ANY OF THE MECHANICAL FLOOR PLANS FROM THE |
| | GROUND LEVEL TO LEVEL 8. HOW WILL THESE ROOMS BE |
| | VENTILATED. |
| | 8) SHEET M-2.1A: IT APPEARS THAT THE AMS IS MISSING FOR |
| | THE GARAGE EXHAUST FAN AT THE NORTH END OF THE GARAGE. |
| | 9) SHEET M-2.1A: LABEL THE AC UNIT IN THE TRASH ROOM |
| | AND PROVIDE AN EXHAUST VENTILATION SYSTEM- TABLE 6-4 |
| | ASHRAE 62.1-2010. |
| | 10) M-2.1A: PROVIDE AN EXHAUST VENTILATION SYSTEM FOR |
| | THE ZOOM LOCKERS ROOM- TABLE 6-4 ASHRAE 62.1-2010. |
| | 11) M-2.1A: INDICATE THE HEIGHT FROM THE GARAGE FLOOR |
| | TO THE BOTTOM OF THE RF-1 FAN ON ALL GARAGE FLOOR |
| | LEVELS- SECTION 304.6 FBC-14 MECHANICAL. |
| | 12) M-2.1C: THE NOTE IN THE SERVICE COURT REFERENCES |
| | SHEET M2.2 WHICH IS NOT INCLUDED WITH THE PLAN SETS. |
| | 14) M-2.2A: IT APPEARS THAT THE AMS IS MISSING FOR THE |
| | EXHAUST FAN AT THE NORTH END OF THE GARAGE. |
| | 15) M-2.2C: REFER TO SECTION 501.3.1 FBC-14 MECHANICAL |
| | AND PROVIDE CLEARANCES FOR THE EXHAUST TERMINATIONS ON |
| | THE NORTH SIDE. PLEASE NOTE THAT A FLORIDA PRODUCT |
| | APPROVAL OR MIAMI-DADE NOA FOR THE EXHAUST LOUVER MUST |
| | BE SUBMITTED WITH A REVIEW AND APPROVAL SIGNATURE BY |
| | THE DESIGN PROFESSIONAL OF RECORD. A) INDICATE THE |
| | REQUIRED CLEARANCES FOR THE GARAGE AIR INTAKE ON THE |
| | NORTH SIDE AS REQUIRED BY SECTION 401.4. B) AS |
| | PREVIOUSLY NOTED, THE "GE-1A" TAG BY THE GARAGE INTAKE |
| | GRILL APPEARS TO BE INDICATING A FAN, HOWEVER I AM NOT |
| | SEEING THE FAN IN ANY OF THE HVAC SCHEDULES: PLEASE |
| | CLARIFY. |
| | 16) M-2.2C: THERE IS A NOTE BY THE NORTH TELECOM ROOM |
| | REFERENCING SHEET M3.1 WHICH IS NOT INCLUDED WITH THE |
| | PLAN SETS. |
| | 17) M-2.4B: INDICATE HOW THE BRIDGE WILL BE VENTILATED |
| | 18) REFER TO SECTION C403.2.9 FBC ENERGY CONSERVATION |
| | AND VERIFY COMPLIANCE FOR ALL EXHAUST AND SUPPLY FANS |
| | TO BE USED ON THE PROJECT. |
| | |
| | 19) M-2.6A: IT APPEARS THAT THE AMS EQUIPMENT IS |
| | MISSING FOR THE GARAGE EXHAUST FANS AT THE NORTH AND |
| | SOUTH ENDS. |
| | 20) M-2.7A & 7B: SITE SPECIFIC WIND LOAD ENGINEERING IS |
| | REQUIRED FOR ANCHORING AND TIE-DOWN OF ALL ROOF TOP |
| | MECHANICAL EQUIPMENT AND COMPONENTS INCLUDING THE ROOF |
| | AND EXTERIOR WALL-MOUNTED FANS, THE RTU'S, THE CU'S, |
| | THE RTU CURBS AND CU STANDS, THE DUCTWORK AND DUCT |
| | STANDS AND BRACKETS, ETC. . PLEASE NOTE THAT FLORIDA |
| | PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S ARE REQUIRED |
| | FOR THE CURBS AND STANDS WITH REVIEW AND APPROVAL |
| | SIGNATURES FROM THE DESIGN PROFESSIONAL OF RECORD- |
| | SECTION 301.15 MECHANICAL. |
| | 21) M-2.7A & 7B: PLEASE INDICATE THE LOCATION OF CU-8 |
| | ON THE ROOF PLAN. |
| | 22) M-2.7A & 7B: REFER TO SECTION 3004 FBC-14 |
| | MECHANICAL AND PROVIDE DETAILS FOR THE REQUIRED |
| | ELEVATOR HOISTWAY VENTING. SEE SECTION 3004.3 FOR |
| | SIZING. |
| | 23) M-3.1A: EXHAUST SYSTEMS ARE REQUIRED FOR THE DOG |
| | PARLOR AND THE ZOOM LOCKERS ROOM- TABLE 403.3 FBC-14 |
| | MECHANICAL. |
| | 24) M-3.1A: PROVIDE DIMENSIONED ELEVATION VIEWS OF THE |
| | O/A INTAKES FOR AC- 4, 4A, AND 5 TO VERIFY THE |
| | LOCATIONS MEET THE REQUIRED CLEARANCES AS OUTLINED IN |
| | SECTION 401.4 FBC-14 MECHANICAL. |
| | 25) M-3.1A: SHUT OFF DAMPER CONTROLS FOR THE O/A |
| | INTAKES ARE REQUIRED IN ACCORDANCE WITH SECTION |
| | C403.2.4.4 FBC-14 ENERGY CONSERVATION- INDICATE |
| | COMPLIANCE ON THE PLAN. |
| | 26) M-3.1A: PLEASE CLARIFY HOW O/A IS BEING SUPPLIED TO |
| | AHU-9 SERVICING THE RESIDENTIAL LOBBY-N. |
| | 27) M-3.1B: PROVIDE DIMENSIONED ELEVATION VIEWS OF THE |
| | O/A INTAKES FOR AC- 6, 7, & 8 TO VERIFY THE LOCATIONS |
| | MEET THE REQUIRED CLEARANCES AS OUTLINED IN SECTION |
| | 401.4 FBC-14 MECHANICAL. |
| | 28) M-3.1B: SHUT OFF DAMPER CONTROLS FOR THE O/A |
| | INTAKES ARE REQUIRED IN ACCORDANCE WITH SECTION |
| | C403.2.4.4 FBC-14 ENERGY CONSERVATION- INDICATE |
| | COMPLIANCE ON THE PLAN. |
| | 29) M-3.1B: PROVIDE A CLEAR AIR DISTRIBUTION PLAN WITH |
| | NOTES AND DETAILS FOR AHU-8. |
| | 30) M-3.1B: REFER TO SECTION 501.3.1 FBC-14 MECHANICAL |
| | AND INDICATE ALL REQUIRED CLEARANCE DISTANCE |
| | MEASUREMENTS FOR THE TOILET AND POOL BATHROOM EXHAUST |
| | FAN OUTLETS. CLARIFY IF CONDITIONED SUPPLY AIR OR |
| | MAKE-UP AIR WILL BE PROVIDED TO THE POOL BATHROOMS. |
| | 31) M-3.1C: THE CITY OF WPB DEVELOPMENT SERVICES |
| | DIVISION REQUIRES A SEPARATE PERMIT AND PLANS FOR |
| | COMMERCIAL KITCHEN HOOD AND EXHAUST SYSTEMS. PLEASE |
| | INDICATE THAT THE NOTES AND DETAILS ON THE PLANS ARE |
| | FOR REFERENCE ONLY. A) PROVIDE NOTES AND DETAILS ON THE |
| | PLAN INDICATING THAT THE KITCHEN HOOD SUPPLY AIR INTAKE |
| | AND EXHAUST FAN DISCHARGE ARE IN COMPLIANCE WITH |
| | SECTIONS 401.4 AND 506.3.13.3 FBC-14 MECHANICAL. |
| | 32) M-3.1C: VERIFY REQUIRED CLEARANCES FOR THE AHU-2 |
| | O/A INTAKE AT THE SOUTH WALL OF THE THEATER. |
| | 33) M-3.1C: PROVIDE WIND LOAD TIE-DOWN ENGINEERING FOR |
| | CU-2 & 3, & RTU- A & B- SECTION 301.15 FBC-14 |
| | MECHANICAL. |
| | 34) M-3.1C: THE 450 O/A CFM'S FOR RTU-B LISTED IN THE |
| | AIR BALANCE SCHEDULE DOES NOT MATCH WITH THE 325 CFM'S |
| | FOR THE CLUB LOUNGE LISTED IN THE O/A CALCULATIONS ON |
| | SHEET M-5.3. |
| | 35) M-3.1C: DEMAND CONTROLLED VENTILATION IS REQUIRED |
| | FOR THE FITNESS ROOM IN ACCORDANCE WITH SECTION |
| | C403.2.5.1 FBC-14 ENERGY CONSERVATION. INDICATE HOW |
| | COMPLIANCE WITH THIS SECTION WILL BE MET (I.E.) THE USE |
| | OF CO2 DETECTORS. |
| | 36) M-3.1C: PROVIDE ENLARGED TYPICAL DRAWINGS OF THE |
| | AHU'S IN THE CLOSETS INDICATING REQUIRED CLEARANCES, |
| | CONDENSATE DISPOSAL DETAILS, CLOSET CONSTRUCTION AND |
| | LOUVERED DOOR MATERIALS- REFER TO SECTION 602.1 FBC-14 |
| | MECHANICAL AND C403.2.7.2 FBC-14 ENERGY CONSERVATION. |
| | |
| | 37) RESIDENTIAL PLANS M-4.1, M-4.1, & M-4.3: |
| | A) PROVIDE AHRI CERTIFICATES FOR THE AC SYSTEMS. |
| | B) REFER TO COMMENT #2 OF THIS REVIEW FOR AC LOAD |
| | CALCULATION REQUIREMENTS. |
| | C) PLACE A NOTE THAT THE BEDROOM DOORS WILL EACH HAVE A |
| | 1" UNDERCUT PER SECTION 601.5 FBC-14 MECHANICAL. |
| | D) REFER TO COMMENT #3 FOR O/A CALCULATIONS REQUIRED |
| | FOR THE RESIDENTIAL UNITS AND SHOW COMPLIANCE. |
| | E) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A INTAKES. |
| | F) PROVIDE CLEARANCE DISTANCE MEASUREMENTS OR NOTES ON |
| | THE PLAN INDICATING COMPLIANCE WITH SECTIONS 401.4 |
| | FBC-14 MECHANICAL. |
| | G) INDICATE COMPLIANCE WITH SECTION 401.5 FOR THE O/A |
| | OPENING PROTECTION. |
| | H) PROVIDE A PRODUCT APPROVAL OR NOA FOR THE O/A |
| | LOUVER. |
| | I) KITCHEN VENTILATION: SHOW COMPLIANCE WITH TABLE |
| | 403.3 FOR REQUIRED EXHAUST RATE IN THE KITCHENS. IF |
| | RANGE HOODS ARE TO BE USED, PROVIDE AN EQUIPMENT |
| | SCHEDULE ON THE PLAN AND SUBMIT SPECIFICATIONS REVIEWED |
| | AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. |
| | J) INDICATE THE TOTAL RUN LENGTHS OF THE DRYER EXHAUST |
| | RUNS AND SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | DRYERS REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL |
| | OF RECORD. |
| | |
| | 39) M-7.1: DETAIL 10- INDICATE THAT THE LOUVERED CLOSET |
| | DOORS WILL BE NON-COMBUSTIBLE FOR ALL AC CLOSETS |
| | INCLUDING THE RESIDENTIAL UNITS. |
| | 40) M-7.2: PROVIDE FIRESTOPPING DETAILS FOR DUCTS |
| | PENETRATING FIRE-RATED WALLS AND SHAFTS. |
| | 41) M-7.2, DETAIL 5: THE NOA #07-0509.09 SPECIFIED IS |
| | OUTDATED AND HAS BEEN SUPERSEDED. PLEASE PROVIDE A |
| | CURRENT NOA #. |
| | 42) M-7.2, DETAIL 5: THE ASCE 7-05 REFERENCED IN THE |
| | DETAIL IS OUTDATED. ASCE 7-10 IS THE CURRENT STANDARD |
| | IN EFFECT. |
| | 43) PROVIDE REFRIGERANT PIPING RISER DRAWINGS FOR THE |
| | AMENITY AC SYSTEMS 4-9, AND MANUFACTURER?S LINE LENGTH |
| | SPECIFICATIONS AND LIMITATIONS. B) PROVIDE THE TYPE AND |
| | SIZE OF REFRIGERANT PIPE INSULATION AND INDICATE HOW |
| | THE INSULATION SHALL BE PROTECTED FROM UV AND |
| | WEATHERING DEGRADATION. |
| | 44) REFER TO SECTION C403.2.10 FBC-14 ENERGY |
| | CONSERVATION AND PROVIDE EVIDENCE OF COMPLIANCE- |
| | C403.2.10.1 ALLOWABLE FAN MOTOR HORSEPOWER. |
| | EACH HVAC SYSTEM AT FAN SYSTEM DESIGN CONDITIONS SHALL |
| | NOT EXCEED THE ALLOWABLE FAN SYSTEM MOTOR NAMEPLATE HP |
| | (OPTION 1) OR FAN SYSTEM BHP (OPTION 2) AS SHOWN IN |
| | TABLE C403.2.10.1(1). THIS INCLUDES SUPPLY FANS, |
| | RETURN/RELIEF FANS, AND FAN-POWERED TERMINAL UNITS |
| | ASSOCIATED WITH SYSTEMS PROVIDING HEATING OR COOLING |
| | CAPABILITY. SINGLE ZONE VARIABLE-AIR-VOLUME SYSTEMS |
| | SHALL COMPLY WITH THE CONSTANT VOLUME FAN POWER |
| | LIMITATION. |
| | EXCEPTION: THE FOLLOWING FAN SYSTEMS ARE EXEMPT FROM |
| | ALLOWABLE FAN FLOOR HORSEPOWER REQUIREMENT. |
| | 1. HOSPITAL, VIVARIUM AND LABORATORY SYSTEMS THAT |
| | UTILIZE FLOW CONTROL DEVICES ON EXHAUST AND/OR RETURN |
| | TO MAINTAIN SPACE PRESSURE RELATIONSHIPS NECESSARY FOR |
| | OCCUPANT HEALTH AND SAFETY OR ENVIRONMENTAL CONTROL |
| | SHALL BE PERMITTED TO USE VARIABLE VOLUME FAN POWER |
| | LIMITATION. |
| | 2. INDIVIDUAL EXHAUST FANS WITH MOTOR NAMEPLATE |
| | HORSEPOWER OF 1 HP OR LESS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |