2016-03-08 13:24:10THE FOLLOWING COMMENTS WERE SUBMITTED BY ROY LINDOW(
 [email protected]), FIRE INSPECTOR, BUREAU OF FIRE
 PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 1) -SHEET 043- LS 0.5
 ONE HOUR RATED WALL IS NOT PROVIDED FOR CORRIDOR OF SE
 CORNER OF BUILDING ACROSS FROM STAIR #4.
  
 2) -SHEET 043- LS 0.5
 ADD REQUIRED EXIT SIGNS TO SOUTH AND NORTH CORRIDOR.
 DISTANCE EXCEEDS MAXIMUM OF 100 FT.
  
 3) -SHEET 043- LS 0.5
 ACCOUNT FOR CAPACITY OF EACH EXIT DOOR AND HOW
 OCCUPANCY LOAD IS SPLIT UP.
  
 4) -SHEET 042- LS-0.4
 ADD REQUIRED EXIT SIGNS TO SOUTH AND NORTH CORRIDOR.
 DISTANCE EXCEEDS MAXIMUM OF 100 FT.
  
 5) -SHEET 042- LS-0.4
 EXIT DOORS SWING WRONG DIRECTION FOR ASSEMBLY SPACE AT
 NORTH SIDE OF BUILDING (TERRACE FLOOR 4).
  
 6) -SHEET 042- LS-0.4
 ONE HOUR RATED WALL IS NOT PROVIDED FOR CORRIDOR OF SE
 CORNER OF BUILDING ACROSS FROM STAIR #4.
  
 7) -SHEET 042- LS-0.4
 PROVIDE ONE HOUR RATING TO SEPARATE THE ASSEMBLY
 OCCUPANCY FROM APARTMENT OCCUPANCY.
  
 8) -SHEET 042- LS-0.4
 ACCOUNT FOR CAPACITY OF EACH EXIT DOOR AND HOW
 OCCUPANCY LOAD IS SPLIT UP.
  
 9)-SHEET 041-LS-0.3
 ADD REQUIRED EXIT SIGNS TO SOUTH AND NORTH CORRIDOR.
 DISTANCE EXCEEDS MAXIMUM OF 100 FT.
  
 10)-SHEET 041-LS-0.3
 ACCOUNT FOR CAPACITY OF EACH EXIT DOOR AND HOW
 OCCUPANCY LOAD IS SPLIT UP.
  
 11) -SHEET 040-LS-0.2
 PER SECTION 6.1.14.4.1
 PROVIDE ONE HOUR RATING TO SEPARATE THE ASSEMBLY
 OCCUPANCY FROM APARTMENT OCCUPANCY.
  
 12) -SHEET 040-LS-0.2
 PROVIDE ONE HOUR RATING TO SEPARATE CORRIDOR FROM
 GARAGE.
  
 13) -SHEET 040-LS-0.2
 ADD REQUIRED EXIT SIGNS TO SOUTH CORRIDOR. DISTANCE
 EXCEEDS MAXIMUM OF 100 FT.
  
 14) -SHEET 040-LS-0.2
 ACCOUNT FOR CAPACITY OF EACH EXIT DOOR AND HOW
 OCCUPANCY LOAD IS SPLIT UP.
  
 15) -SHEET 039- LS-0.1
 TWO HOUR ENCLOURE FOR STAIR #2 MISSING DOOR.
  
 16) -SHEET 039- LS-0.1
 ADD REQUIRED EXIT SIGNS TO GARAGE. DISTANCE EXCEEDS
 MAXIMUM OF 100 FT.
  
 17) -SHEET 039- LS-0.1
 ADD REQUIRED EXIT SIGNS TO SOUTH CORRIDOR. DISTANCE
 EXCEEDS MAXIMUM OF 100 FT.
  
 18) -SHEET 039- LS-0.1
 ELECTRIC ROOM, PER NFPA 70, PROVIDE REQUIRED PANIC
 HARDWARE.
  
 19) -SHEET 039- LS-0.1
 ACCOUNT FOR CAPACITY OF EACH EXIT DOOR AND HOW
 OCCUPANCY LOAD IS SPLIT UP.
  
 20) -SHEET 039- LS-0.1
 COMMON PATH OF TRAVEL EXCEEDED IN PARKING GARAGE(100
 FEET).
  
 21) -SHEET 039- LS-0.1
 PLANS SHOW "AREA OF REFUGED#1"? PROVIDE ADDITIONAL
 INFORMATION PERTAINING TO THIS AREA.
  
 22) -SHEET 092-A5.2.2
 GAS FIREPLACE IS NOT PERMITTED.
 PER SECTION 10.11.8.1- INCINERATORS, OUTDOOR
 FIREPLACES, PERMANENT BARBECUES,
 AND GRILLS SHALL NOT BE BUILT, INSTALLED, OR MAINTAINED
 WITHOUT
 PRIOR APPROVAL OF THE AHJ.
  
 23) -SHEET 044-A-2.1
 3' GATE IN THE MEANS OF EGRESS USED FOR ACCESS CONTROL
 REQUIRED TO COMPLY WITH FFPC PER SECTION 7.2.1.6.2
  
 24) -SHEET-090-A-5.1.6
 CONDITION SHOWN ON PLAN.SEPARATE FIRE SUPPRESSION AND
 EXHAUST HOOD PLANS REQUIRED.
  
 25) -SHEET-249-E-4.1
 PLAN SHOWS SMOKE DETECTORS WHERE SMOKE ALARMS ARE
 REQUIRED.
  
 26) -SHEET-012-C-09
 FIRE HYDRANTS ARE TO BE ON THE SAME SIDE OF THE STREET
 AS FIRE DEPARTMENT CONNECTION.
  
 27) -ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR
 THIS DEVELOPMENT SHALL BE CLEARLY INDICATED
 AND IDENTIFIED ON THE PLAN AND CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 28) -ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED
 AND COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 29) -LIFE SAFETY PLANS AND ELECTRICAL PLANS. SHOW ALL
 EMERGENCY LIGHTING. PLANS NEED TO BE SIMILAR IN
 LOCATION AND IN CONCEPT.
  
 30) - DOOR SCHEDULE DOES NOT INCLUDE ALL RATED DOORS IN
 BUILDING. VERIFY ACCURACY TO INCLUDE ALL RATED DOORS.
  
  
  
 GENERAL COMMENTS NOTED BELOW:
  
 -ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A.
  
 -ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 KEYWAY
 SYSTEM.
  
 -CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS.
 A PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER
 RELATED TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 -SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 -THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM ALL
 ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. ADDRESS
 NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 -DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE REMOVED
 FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 -ALL STAIRWELL ENCLOSURES.
 PER SECTION 7.2.2.5.4 - STAIRWAY IDENTIFICATION: NEW
 ENCLOSED STAIRS SERVING THREE OR MORE STORIES AND
 EXISTING ENCLOSED STAIRS SERVING FIVE OR MORE STORIES
 SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 -FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
 -PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 -SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 -PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 -PROVIDE A KNOX KEY SWITCH TO ALLOW GATE ACCESS TO
 EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 -PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 -PER SECTION 8.3.2.4
 EACH NEW FIRE WALL, FIRE BARRIER, FIRE PARTITION, SMOKE
 BARRIER, SMOKE PARTITION, OR ANY OTHER NEW WALL
 REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR
 STENCILING ABOVE ANY DECORATIVE CEILING AND IN
 CONCEALED SPACES
 WITH THE WORDING, "FIRE AND SMOKE BARRIER PROTECT
 ALL OPENINGS" OR SIMILAR LANGUAGE. SUCH SIGNS OR
 STENCILING
 SHALL BE IN 4 INCH HIGH LETTERS, ? INCH STROKE, AND NOT
 MORE THAN 15
 FEET ON-CENTER.
  
  
  