| 2016-02-24 05:25:43 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. SHEET LT-1- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE |
| | WILL SUFFICE. |
| | 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR FIRE PUMP ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT |
| | NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE |
| | AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING |
| | STATIONS, ETC. A NOTE WILL SUFFICE. |
| | 3. PLEASE PROVIDE DATA SHEETS FOR THE EMERGENCY |
| | INVERTERS SHOWN ON DESIGN. FBC 107.3.5 |
| | 4. SHOW TWO MEANS OF ACCESS AND EGRESS FOR THE MAIN |
| | ELECTRICAL ROOM #1. COULD NOT DETERMINE SIZE OF THE |
| | ELECTRICAL EQUIPMENT IN ROOM. NEC 110.26C2 |
| | 5. SHEET E3.3- PLEASE LABEL RECEPTACLE IN WORK ROOM TO |
| | BE GFCI PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF |
| | SINK ALL TO BE GFCI. |
| | 6. SHEET E3.5- PLEASE LABEL RECEPTACLE IN KITCHEN AND |
| | PRIVATE LOUNGE TO BE GFCI PROTECTED PER NEC 210.8B5- IF |
| | WITHIN 6FT OF SINK, ALL TO BE GFCI. |
| | 7. ON UNIT PLANS DRAWINGS CORRECT TYPO ON APARTMENT |
| | FEEDER SCHEDULE TO INDICATE ALUMINUM CONDUCTORS BEING |
| | USED NOT COPPER. PLEASE CORRELATE FBC 107.3.5 |
| | 8. SHEET E5.2- RISER DIAGRAM; PLEASE CLARIFY MAIN 2 OF |
| | 2 3500A MCB WITH 6 SETS OF 600 ALUMINUM WIRES. 600AL IS |
| | GOOD FOR 340AMP AT 75 DEGREE TERMINAL RATINGS, NEC |
| | 310.15B16. UNDERSIZED AS SHOWN FOR A 3500 MCB. CLARIFY |
| | AND CORRECT. |
| | 9. NOTE THAT PER NEC 230.2 THIS PROJECT MEETS THE |
| | REQUIREMENTS FOR MULTIPLE SERVICES DUE TO CAPACITY |
| | LIMITS. REGARDLESS, SPECIAL PERMISSION FROM AHJ TO BE |
| | GRANTED PER DESIGN SHOWN. PROVIDE IN WRITING A REQUEST |
| | PER CODE SECTION CITED TO AHJ. GENERAL NOTES TO BE |
| | PLACED FOR FIRST RESPONDERS SAFETY. FIRE REVIEW MIGHT |
| | REQUIRE OTHER MEANS TO SHUNT SERVICES. FBC 107.3.5 |
| | 10. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL |
| | AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. NOTE NOT |
| | SUFFICIENT AT THIS TIME. FBC 107.3.5 |
| | 11. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 |
| | 12. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS |
| | NEC 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS |
| | AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS |
| | REQUIRED. |
| | 13. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS |
| | FOR FEEDERS AND BRANCH CIRCUITS. |
| | 14. CLARIFY SELECTION OF SERVICE AND FEEDER CONDUCTORS |
| | AS SHOWN ON RISER DIAGRAM. FOR EXAMPLE PANEL 3UDP SHOWS |
| | A 3500A MCB WITH SERVICE CONDUCTORS SIZED AT 2040AMP (2 |
| | SETS OF 4#600 AL.). THE CALCULATED LOADS ON SHEET E5.01 |
| | FOR THE METER CENTERS IS SHOWN AT 608+680=(1288) * 2= |
| | 2576AMPS DEMAND LOADS. PLEASE REVISIT LOADS AND |
| | CONDUCTOR SIZES AS SHOWN. SEE NEC 240.4C- PROTECTION OF |
| | CONDUCTORS. NEC 310.15B16 TABLE OF AMPACITIES BASED ON |
| | 75 DEGREE COLUMN FOR TERMINAL RATINGS. NEC 110.14C. |
| | VERIFY ENTIRE RISER DIAGRAM. |
| | 15. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |