2016-02-24 05:25:43INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHEET LT-1- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE
 WILL SUFFICE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR FIRE PUMP ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE
 AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING
 STATIONS, ETC. A NOTE WILL SUFFICE.
 3. PLEASE PROVIDE DATA SHEETS FOR THE EMERGENCY
 INVERTERS SHOWN ON DESIGN. FBC 107.3.5
 4. SHOW TWO MEANS OF ACCESS AND EGRESS FOR THE MAIN
 ELECTRICAL ROOM #1. COULD NOT DETERMINE SIZE OF THE
 ELECTRICAL EQUIPMENT IN ROOM. NEC 110.26C2
 5. SHEET E3.3- PLEASE LABEL RECEPTACLE IN WORK ROOM TO
 BE GFCI PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF
 SINK ALL TO BE GFCI.
 6. SHEET E3.5- PLEASE LABEL RECEPTACLE IN KITCHEN AND
 PRIVATE LOUNGE TO BE GFCI PROTECTED PER NEC 210.8B5- IF
 WITHIN 6FT OF SINK, ALL TO BE GFCI.
 7. ON UNIT PLANS DRAWINGS CORRECT TYPO ON APARTMENT
 FEEDER SCHEDULE TO INDICATE ALUMINUM CONDUCTORS BEING
 USED NOT COPPER. PLEASE CORRELATE FBC 107.3.5
 8. SHEET E5.2- RISER DIAGRAM; PLEASE CLARIFY MAIN 2 OF
 2 3500A MCB WITH 6 SETS OF 600 ALUMINUM WIRES. 600AL IS
 GOOD FOR 340AMP AT 75 DEGREE TERMINAL RATINGS, NEC
 310.15B16. UNDERSIZED AS SHOWN FOR A 3500 MCB. CLARIFY
 AND CORRECT.
 9. NOTE THAT PER NEC 230.2 THIS PROJECT MEETS THE
 REQUIREMENTS FOR MULTIPLE SERVICES DUE TO CAPACITY
 LIMITS. REGARDLESS, SPECIAL PERMISSION FROM AHJ TO BE
 GRANTED PER DESIGN SHOWN. PROVIDE IN WRITING A REQUEST
 PER CODE SECTION CITED TO AHJ. GENERAL NOTES TO BE
 PLACED FOR FIRST RESPONDERS SAFETY. FIRE REVIEW MIGHT
 REQUIRE OTHER MEANS TO SHUNT SERVICES. FBC 107.3.5
 10. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. NOTE NOT
 SUFFICIENT AT THIS TIME. FBC 107.3.5
 11. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 12. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS
 NEC 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 13. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 14. CLARIFY SELECTION OF SERVICE AND FEEDER CONDUCTORS
 AS SHOWN ON RISER DIAGRAM. FOR EXAMPLE PANEL 3UDP SHOWS
 A 3500A MCB WITH SERVICE CONDUCTORS SIZED AT 2040AMP (2
 SETS OF 4#600 AL.). THE CALCULATED LOADS ON SHEET E5.01
 FOR THE METER CENTERS IS SHOWN AT 608+680=(1288) * 2=
 2576AMPS DEMAND LOADS. PLEASE REVISIT LOADS AND
 CONDUCTOR SIZES AS SHOWN. SEE NEC 240.4C- PROTECTION OF
 CONDUCTORS. NEC 310.15B16 TABLE OF AMPACITIES BASED ON
 75 DEGREE COLUMN FOR TERMINAL RATINGS. NEC 110.14C.
 VERIFY ENTIRE RISER DIAGRAM.
 15. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  