| 2016-03-10 16:43:50 | ****CORRECTIONS**** |
| | REVISED 3/25/16 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | GOVERNING CODE: FBC 5TH EDITION (FBC 2014) |
| | |
| | 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A |
| | THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: |
| | |
| | A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| | THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY |
| | THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS |
| | 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED |
| | TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT |
| | ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL |
| | INFORMATION. |
| | FORMS WERE SENT TO: [email protected] ON 3/1/16. |
| | |
| | C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW |
| | BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE |
| | RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY |
| | SAMANTHA HILL), 561-805-6666, [email protected], |
| | [email protected] |
| | |
| | ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE |
| | CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN |
| | THE SPECIAL INSPECTOR AGREEMENT. |
| | |
| | D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL |
| | ([email protected], [email protected]). |
| | |
| | 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE |
| | ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD AND |
| | THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE |
| | SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE |
| | ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO |
| | INSPECTION. THE CITY APPROVED (CITY STAMPED) |
| | SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE |
| | JOB AT THE TIME OF INSPECTION. |
| | |
| | 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A |
| | SHORING/RESHORE GUARD RAIL DETAIL IS TO BE SUBMITTED |
| | FOR PLAN REVIEW. THIS SHOULD BE SUBMITTED WITH THE |
| | SHORING/RESHORE ENGINEERING. |
| | |
| | 5. PRIOR TO PERMIT ISSUANCE, IMPACT FEE ASSESSMENT BY |
| | PALM BEACH COUNTY IS REQUIRED. PLEASE CONTACT |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 6. THE PROPOSED CONSTRUCTION CROSSES PROPERTY LINE, FBC |
| | 705.8. PLEASE ADVISE; HAS A REPLAT BEEN FILED? |
| | |
| | 7. TWO DOCUMENTS WERE UPLOADED AS LAND AND TITLE SURVEY |
| | (003-01 AND 004-02) BUT BOTH DOCUMENTS ARE ONE PAGE, |
| | FIRST PAGE OF A TWO PAGE SURVEY. PROVIDE THE SECOND |
| | PAGE, FBC 107. |
| | |
| | 8. ADVISORY ONLY; DEMOLITION OF EACH BUILDING REQUIRES |
| | A SEPARATE PERMIT. PLEASE SEE THE DEMOLITION PERMIT |
| | APPLICATION CHECKLIST ON OUR WEBSITE: HTTP://WPB.ORG/DE |
| | PARTMENTS/DEVELOPMENT-SERVICES/CONSTRUCTION/PERMITS |
| | |
| | 9. DOOR 101 TO RESIDENTIAL LOBBY 143, PLEASE REVISE |
| | PLAN TO SHOW MANEUVERING CLEARANCE (18IN MINIMUM), PULL |
| | SIDE, SEE ANSI 117.1 FIG.B4.13.5 (PER FAIR HOUSING |
| | ACCESSIBILITY GUIDELINES, REQUIREMENT 3, USABLE DOORS). |
| | |
| | 10. STAIR 2, A2.1 AND LS 0.1, DOES NOT HAVE A DOOR, |
| | WEST SIDE, SEE FBC 1022.3.1. |
| | |
| | 11. LS0.1, A SURFACE MOUNT FIRE EXTINGUISHER IS |
| | DEPICTED ON THE RAMP (S2 TO BUSINESS/RESIDENTIAL) BUT |
| | DOES NOT APPEAR ON SHEET A2.1; THIS DOES NOT APPEAR TO |
| | COMPLY WITH FBC 1003.3, 1012.8, FBC 5TH ED. |
| | ACCESSIBILITY 405.5. |
| | |
| | 12. FIRST FLOOR, IT IS NOT CLEAR WHICH PARKING SPACES |
| | SERVE THE BUSINESS OCCUPANCY AND RESIDENTIAL OCCUPANCY, |
| | REVISE PLAN TO CLARIFY AND SHOW COMPLIANCE WITH FBC 5TH |
| | EDITION ACCESSIBILITY TABLE 208.2, FHA REQUIREMENT 2. |
| | PROVIDE THE TOTAL NUMBER OF PARKING SPACES (FOR |
| | BUSINESS AND RESIDENTIAL), NUMBER OF ACCESSIBLE SPACES |
| | (FOR BUSINESS AND RESIDENTIAL), SHEET GA2.1. NOTE THAT |
| | ALL OF THE VAN ACCESSIBLE PARKING SPACES ARE ON THE |
| | PUBLIC SIDE OF THE VEHICLE BARRIER GATE ARM AS WELL AS |
| | SEVERAL ACCESSIBLE SPACES. MORE INFORMATION REGARDING |
| | PARKING FOR RESIDENTS AND BUSINESS VISITORS IS NEEDED. |
| | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. |
| | |
| | 13. GA PAGES, FAIR HOUSING ACT REQUIREMENT 2, |
| | ACCESSIBLE AND USABLE COMMON USE AREA, STATES THAT THE |
| | BUILDING BE DESIGNED SO THAT THE PUBLIC AND COMMON USE |
| | AREAS ARE READILY ACCESSIBLE TO AND USABLE BY |
| | HANDICAPPED PERSONS. NONE OF THE ACCESSIBLE SPACES |
| | INCLUDE A CHARGING STATION, AND NONE OF THE CHARGING |
| | STATION SPACES INCLUDE AN ACCESS AISLE; PLEASE REVISE |
| | TO COMPLY WITH THIS REQUIREMENT. |
| | |
| | 14. FBC 5TH EDITION ACCESSIBILITY 207, REVISE PLAN TO |
| | STATE WHICH METHOD OF COMPLIANCE IS ELECTED FOR |
| | ACCESSIBLE MEANS OF EGRESS (OFFICE SPACE). |
| | |
| | 15. LS0.1, NOTE UNDER PARKING GARAGE (MECHANICALLY |
| | VENTILATED) STATES "AREA OF REFUGED #1", PLEASE |
| | CLARIFY. |
| | |
| | 16. LS 0.1, REVISE PLAN TO INCLUDE GRILL AREA OCCUPANT |
| | LOAD, FBC 1004. |
| | |
| | 17. LS 0.1, IT APPEARS THAT INTERMEDIATE HANDRAILS ARE |
| | REQUIRED AT THE STAIR AT DOOR 115, FBC 1012.9. REVISE |
| | THIS SHEET AND PROVIDE A DIMENSIONED DETAIL FOR THE |
| | STAIR, FBC 107. |
| | |
| | 18. LS 0.1, THE HANDRAIL FOR THE RAMP IS SHOWN |
| | GRAPHICALLY AS A PROTRUSION INTO THE PATH OF TRAVEL. |
| | |
| | 19. LS 0.1, THE CLUBHOUSE DOORS 170 AT THE VESTIBULE |
| | ARE DOUBLE DOORS, BUT GATE 160 IS 3FT; FBC 1005.4. SEE |
| | ALSO FBC 1008.2; GATES USED AS A COMPONENT IN A MEANS |
| | OF EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS |
| | FOR DOORS. |
| | |
| | 20. LS 0.1, REVISE PLAN TO INCLUDE THE SIDEWALK WIDTH |
| | FROM GATE 160 TO THE PUBLIC WAY, FBC 1005.4. |
| | |
| | 21. LS 0.1, REVISE PLAN TO CLARIFY THE NUMBER OF |
| | OCCUPANTS EXITING THROUGH GATE 160. EXIT STAIR 4, EXIT |
| | STAIR 6, POOL AREA, CLUBHOUSE, 1ST FLOOR RESIDENTIAL |
| | LEAD TO THIS EXIT. |
| | |
| | 22. LS 0.1, EXIT STRATEGY FOR POOL DECK AMENITY AREA |
| | AND CLUBHOUSE IS NOT CLEAR. EGRESS CAPACITY TABULATIONS |
| | DOES NOT INCLUDE POOL DECK AREAS; REVISE TO INCLUDE. |
| | |
| | 23. LS 0.1, TOTAL OCCUPANTS IN THE POOL AREA IS 414 |
| | (NOT INCLUDING THE GRILL AREA), WHICH REQUIRES 82.8IN |
| | OF EGRESS WIDTH, 1005.3.2; 68IN PROVIDED. SEE ALSO FBC |
| | 1005.5 (REGARDING LOSS OF ONE EXIT); IT APPEARS THAT |
| | BOTH GATES (160, 161) ARE REQUIRED TO BE WIDER. |
| | |
| | 24. LS 0.1, WILL RESIDENTS HAVE ACCESS FROM THE STREET |
| | SIDE OF GATE 160? THIS GATE LACKS THE MANEUVERING |
| | CLEARANCE REQUIRED BY ANSI 117.1 (FHA), 18IN PULL SIDE, |
| | ANSI 117.1 FIG.B4.13.5. |
| | |
| | 25. LS 0.1, IT IS NOT CLEAR IF GATE 160A HAS THE |
| | MANEUVERING CLEARANCE REQUIRED BY ANSI 117.1 (FHA), |
| | 18IN PULL SIDE, ANSI 117.1 FIG.B4.13.5. REVISE PLAN TO |
| | CLARIFY. |
| | |
| | 26. LS 0.2 AND OTHER SHEETS, A SURFACE MOUNT FIRE |
| | EXTINGUISHER IS SHOWN WHERE IT APPEARS TO OBSTRUCT THE |
| | ACCESSIBLE PARKING ACCESS AISLE. PROVIDE DIMENSIONS TO |
| | SHOW THAT THE ACCESS AISLE IS NOT OBSTRUCTED. |
| | |
| | 27. LS 0.2, LS 0.4, UNITS A1 AND C2, TENANT / OCCUPANCY |
| | SEPARATION BETWEEN THE R2 UNITS AND THE A2 CORRIDOR IS |
| | LACKING, FBC TABLE 508.4. |
| | |
| | 28. LS 0.4, THE DOORS SERVING THE NORTH ROOF DECK ARE |
| | TO SWING IN THE DIRECTION OF EGRESS TRAVEL, FBC |
| | 1008.1.10. |
| | |
| | 29. LS 0.4 IS LABELED LEVELS 4 THROUGH 7, BUT THE 4TH |
| | FLOOR IS NOT THE SAME AS FLOORS 5 THROUGH 7, PLEASE |
| | CORRELATE. |
| | |
| | 30. LS 0.5, UNIT C1 TO CORRIDOR LACKS THE 1 HOUR RATING |
| | REQUIRED BY FBC 1018, PLEASE REVISE. |
| | |
| | 31. SHEET S1 2A, SPECIFY FLOOR LOADS FOR THE ASSEMBLY |
| | AREAS (CLUBHOUSE ROOF DECK, GYM, EXERCISE ROOM). |
| | |
| | 33. SHEET A2.9 SPECS MIAMI DADE NOAS 14-0618.03, |
| | 13-0529.02 (JM TPO) ROOF SYSTEM. ADVISORY ONLY; A |
| | SPECIFIC REFERENCE TO A ROOFING PRODUCT WILL REQUIRE A |
| | REVISION IF A DIFFERENT PRODUCT IS SELECTED AT TIME OF |
| | INSTALLATION. IT IS RECOMMENDED THAT, IF UNSURE OF |
| | FINAL PRODUCT TO BE INSTALLED, REFERENCES ARE LEFT OFF |
| | OF THE PLAN AND PRODUCT APPROVALS (REVIEWED BY DESIGNER |
| | OF RECORD) SUBMITTED PRIOR TO INSTALLATION. THIS |
| | COMMENT DOES NOT NEED TO BE ADDRESSED SUBJECT TO |
| | DESIGNER?S DISCRETION. |
| | |
| | 34. ROOF PRODUCT APPROVALS WERE SUBMITTED BUT THE |
| | ASSEMBLY PROPOSED WAS NOT SELECTED AND ENGINEERING FOR |
| | ENHANCED FASTENING WAS NOT PROVIDED. IF THIS |
| | INFORMATION IS NOT PROVIDED AT THIS TIME, THE |
| | INFORMATION WILL BE REQUIRED AT TIME OF ROOF SUB PERMIT |
| | SUBMITTAL. |
| | |
| | 35. DETAIL 9-A2.9 SPECIFIES PLYWOOD SHEATHING; 1-S4.1 |
| | SPECS WOOD FRAMED CANOPY (ALSO OTHER DETAILS THROUGH |
| | PLANS). PLEASE SEE FBC 603 AND REVISE. |
| | |
| | 36. S6.0, WALL PRESSURES SPECIFIED AND SOME PRODUCT |
| | APPROVALS WERE SUBMITTED BUT THE CHART IS A GENERAL |
| | ONE, NOT SPECIFIC TO EACH OPENING. THE PRODUCT |
| | APPROVALS ARE NOT MARKED TO INDICATE WHICH OF THE |
| | OPTIONS IS PROPOSED. EITHER PROVIDE A SCHEDULE TO SHOW |
| | DESIGN PRESSURES FOR EACH OPENING AND PRODUCT APPROVALS |
| | MARKED TO SHOW WHICH OPTION PROPOSED FOR EACH OPENING |
| | (OR ONE TO BE USED FOR ALL OPENINGS TO COMPLY WITH |
| | WORST CASE), OR THIS WILL BE A PROVISO ITEM (PROVIDE |
| | FOR REVIEW PRIOR TO INSTALLATION). |
| | |
| | 37. DETAIL 1-S4.1, PROVIDE A DETAIL FOR THE SOFFIT (OR |
| | ADVISE AS TO WHERE THIS INFORMATION IS LOCATED). PLAN |
| | STATES ?STUCCO & OTHER FINISHES, REF. ARCHITECTURAL.? |
| | |
| | 38. SHEET S1.9A IS INCORRECTLY NAMED AS 8TH FLOOR |
| | PARTIAL PLAN (BUT IS A PARTIAL ROOF PLAN), PLEASE |
| | ADDRESS. |
| | |
| | 39. SHEET S6.1 STATES THAT PARAPET PRESSURES ARE BASED |
| | ON A SOLID PARAPET WITH NO INTERNAL PRESSURE AND THAT |
| | INTERNAL PRESSURE MAY NEED TO BE ADDED. THE PARAPETS |
| | SHOWN ON S4.1 ARE WOOD FRAME. IT APPEARS THAT SOME OF |
| | THE PARAPETS ARE NOT SOLID. PLEASE INCLUDE PARAPET |
| | DESIGN PRESSURES FOR FRAME PARAPETS. |
| | |
| | 40. DETAIL 6-4.0, 1-S7.0 SPECIFIES A LINTEL, BUT I WAS |
| | UNABLE TO LOCATE A LINTEL SCHEDULE, FBC 16, FBC 107, |
| | PLEASE DIRECT OR REVISE TO INCLUDE LINTEL |
| | SPECIFICATION. |
| | |
| | 41. SEE PLUMBING COMMENTS REGARDING FAIR HOUSING. ALL |
| | COMMENTS ARE ALSO APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 42. SEE MECHANICAL COMMENTS REGARDING ENERGY CALCS. ALL |
| | COMMENTS ARE ALSO APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 43. SHEET LS 0.1 STATES THAT STAIRS ARE PRESSURIZED BUT |
| | I WAS UNABLE TO LOCATE STAIR PRESSURIZATION DETAILS, |
| | PLEASE CLARIFY. |
| | |
| | 44. A5.3.1, ITEM 22, WOOD COMPOSITE PANELS ON METAL |
| | CHANNELS, PLEASE ADVISE; IS THIS APPLICABLE FOR THIS |
| | JOB, AND WHERE? FBC 603. |
| | |
| | 45. A5.4, SEE FBC TABLE 716.5, DOORS 106, 106A ARE |
| | REQUIRED TO HAVE A 1.5 HR RATING AS THEY ARE LOCATED IN |
| | A 2 HOUR WALL, 45 MINUTES SPECIFIED. DOOR 110 ON THE |
| | PLAN IS DEPICTED IN A 1 HOUR WALL, BUT THE DOOR |
| | SCHEDULE DOES NOT SPECIFY A FIRE RATING. CHECK ALL AND |
| | REVISE AS NECESSARY PRIOR TO RESUBMITTAL. |
| | |
| | 46. FBC 501.2, ADDRESS IDENTIFICATION REQUIRED. |
| | |
| | 47. THE SOILS REPORT IS NOT DIGITALLY SIGNED. THE |
| | REPORT ALSO LACKS THE ENGINEERING COMPANY CERTIFICATE |
| | OF AUTHORIZATION ON THE DOCUMENT. PLEASE REVISE TO |
| | INCLUDE. IF THE ENGINEER (RAMAKUMAR V. VEDULA, PE) HAS |
| | A DIGITAL SIGNATURE, PLEASE PROVIDE A DIGITALLY SIGNED |
| | SOILS REPORT. IF THE ENGINEER DOES NOT HAVE A DIGITAL |
| | SIGNATURE, PLEASE PROVIDE AN ORIGINAL SIGNED AND SEALED |
| | SOILS REPORT. FS471, FAC61G15. |
| | |
| | THE STRUCTURAL CALCS ARE NOT DIGITALLY SIGNED; PLEASE |
| | ADDRESS. |
| | |
| | 48. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD, FBC 107. IF THE DESIGNER DOES NOT HAVE A |
| | REFERENCE IN THE PLAN TO A SPECIFIC PRODUCT, A SHOP |
| | DRAWING REVIEW STAMP ON EACH PRODUCT APPROVAL OR A |
| | LETTER IS REQUIRED. THE ROOF PRODUCT APPROVALS AND SOME |
| | WINDOWS AND DOORS (A4.7) ARE SPECIFICALLY REFERENCED IN |
| | THE PLAN SO DO NOT REQUIRE DOR REVIEW STAMP. FOR ALL |
| | OTHER ITEMS, PLEASE PROVIDE EVIDENCE OF DOR REVIEW. |
| | |
| | 49. NOA 14-0923.10 (AND OTHER PRODUCT APPROVALS) WERE |
| | PRINTED AND UPLOADED WITH THE DRAWING PAGES REDUCED TO |
| | HALF SIZE. THIS RESULTS IN ILLEGIBLE PRODUCT APPROVALS |
| | WHEN PRINTED. PRODUCT APPROVALS IN THE FIELD ARE |
| | REQUIRED FOR INSPECTION PURPOSES. PLEASE REPRINT THE |
| | DRAWING PAGES IN LANDSCAPE ORIENTATION AND UPLOAD. THE |
| | PAGES ON THE MIAMI DADE WEBSITE ARE DESIGNED TO BE |
| | PRINTED 11X17, SO THE PAGES PROVIDED ARE 25% OF THE |
| | INTENDED SIZE. CHECK ALL PRODUCT APPROVALS AND UPLOAD |
| | AS NEEDED. PLEASE CONTACT ME IF YOU NEED ADDITIONAL |
| | INFORMATION. |
| | |
| | 50. ADVISORY ONLY; SOME (BUT NOT ALL) PRODUCT APPROVALS |
| | HAVE BEEN SUBMITTED. APPLICANT MAY ELECT TO DEFER |
| | PRODUCT APPROVAL SUBMITTAL. THEY CAN BE SUBMITTED AFTER |
| | PERMIT ISSUANCE, PRIOR TO INSTALLATION, WITH NO |
| | ADDITIONAL FEES. |
| | |
| | 51. SEE ROOF REVIEW COMMENTS: |
| | |
| | ROOF NOAS FOR JM TPO SUBMITTED; 14-0618.03, 13-0529.02 |
| | |
| | A. ROOF PRODUCT APPROVALS WERE SUBMITTED BUT THE |
| | ASSEMBLY PROPOSED WAS NOT SELECTED AND ENGINEERING FOR |
| | ENHANCED FASTENING (WOOD DECK) WAS NOT PROVIDED. IF |
| | THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT |
| | ISSUANCE, THE INFORMATION WILL BE REQUIRED AT TIME OF |
| | ROOF SUB PERMIT SUBMITTAL. AN "N" WILL BE ENTERED FOR |
| | THE ROOF PLAN REVIEW. |
| | |
| | ROOF ASSEMBLIES SELECTED TO COMPLY WITH THE (VULT) |
| | PRESSURES SPECIFIED ON SHEET S6-1. |
| | |
| | B. SHEET S6-1, CLARIFY THE DIFFERENCE BETWEEN THE "ROOF |
| | MEMBRANE DESIGN PRESSSURE" VS. "GROSS UPLIFT DESIGN |
| | PRESSURES." THE DESIGN PRESSURES TO BE UTILIZED FOR THE |
| | TPO ROOF IS NOT CLEAR. |
| | |
| | C. SHEET S6-1, IT APPEARS THAT ROOF PRESSURES SPECIFIED |
| | USE ZONE 2 PRESSURES FOR ZONE 3. THE STAIR ROOFS, |
| | ELEVATOR ROOFS, CANOPIES (DETAIL 1-S4.1, A SHEETS |
| | BUILDING SECTIONS, OTHER PLACES) DO NOT INCLUDE A 3FT |
| | PARAPET, FBC 1609, ASCE7 10 30.6-1 NOTE 7. SEE ALSO |
| | ROOF REVIEW COMMENTS. IT IS NOT CLEAR WHICH DESIGN |
| | PRESSURES ARE SPECIFIED FOR THE ROOF. |
| | |
| | D. PLAN SHEET S1.9C AND OTHER SHEETS INCLUDE AN |
| | INDICATOR FOR DETAIL 1 S9.1A; UNABLE TO LOCATE THIS |
| | SHEET (S9.1A). PLEASE PROVIDE SHEET OR REVISE DETAIL |
| | INDICATOR TO CORRECT LOCATION. |
| | |
| | |
| | 52. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT |
| | VIA EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES |
| | 78-123, 78-126. |
| | |
| | THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT, |
| | WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE |
| | PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN |
| | AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO |
| | DOCUMENT THE PERMIT FILE. |
| | |
| | PLEASE VERIFY THAT APPLICANT UNDERSTANDS THE |
| | REQUIREMENTS. PLEASE FEEL FREE TO CONTACT ME FOR MORE |
| | INFORMATION. |
| | |
| | 53. PROVISO; SEPARATE PERMITS (APPLICATION, PLANS, |
| | FEES, REVIEW) REQUIRED FOR POOL. THE PLANS HAVE BEEN |
| | MARKED ?VOID? AND HAVE NOT BEEN REVIEWED. |
| | |
| | 54. PROVISO; THE FOLLOWING PRODUCT APPROVALS OR SITE |
| | SPECIFIC ENGINEERING ARE REQUIRED TO BE SUBMITTED AND |
| | REVIEWED PRIOR TO INSTALLATION: |
| | |
| | MECHANICAL LOUVERS |
| | WINDOWS |
| | SERIES 8000 ALUMINUM WINDOW WALL SYSTEM (15-0727.05, |
| | SHEET A5.5) |
| | DOORS |
| | GENSTORM OPTION #1 LOUVER OUTSWING STEEL DOOR, DOUBLE |
| | (A5.4) |
| | OHD |
| | BAR TELS FRAMELESS DOORS (A5.4) |
| | ALL OTHER COMPONENTS AND CLADDING NOT SUBMITTED AND |
| | REVIEWED PRIOR TO PERMIT ISSUANCE |
| | |
| | GREEN SCREEN ALUMINUM FRAME SYSTEM |
| | 2ND LEVEL METAL CANOPY |
| | TRELLIS |
| | SHADE STRUCTURES |
| | RAILINGS |
| | PRECAST CONCRETE (S7.0, DELEGATED ENGINEERING |
| | CONNECTIONS) |
| | PRECAST STAIRS AND LANDINGS |
| | AWNINGS AND CANOPIES |
| | OTHER DELEGATED ENGINEERING ITEMS |
| | |
| | 55. PROVISO, THE FOLLOWING TEST REPORTS FOR THE |
| | FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO |
| | INSTALLATION (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR |
| | SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR |
| | LESS ARE ACCEPTABLE): STC (FBC 1207.2), IIC (FBC |
| | 1207.3), ASTM E 84 (FBC 603.1). |
| | |
| | 56. ADVISORY ONLY, FS 553.79(7)(C) ALL SHORING AND |
| | RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED |
| | TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| | SHORING/RESHORE ENGINEERING IS TO BE SUBMITTED AT EACH |
| | LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE |
| | BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH |
| | LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS |
| | BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A |
| | NOTE BE INCORPORATED INTO THE PLAN. |
| | |
| | 57. ADVISORY ONLY, WINDOW AND DOOR PRODUCT APPROVALS |
| | SPECIFIED ON SHEET A4.7: |
| | NOAS 15-0611.10, 15-0629.01, 13-0617.28, 14092309.09 |
| | SPECIFIED. CHANGES FROM THE WINDOW AND DOORS SPECIFIED |
| | WILL REQUIRE A REVISION (REVISED PLAN SHEET, NEW |
| | PRODUCT APPROVALS). |
| | |
| | 58. A2.1, THE DOOR FOR UNIT 140 AND OTHER UNITS ARE NOT |
| | LABELED, FBC 107. THE INDEX SHOWS A DOOR SCHEDULE FOR |
| | THE AMENITY AREA. PLEASE ADVISE AS TO WHERE THE UNIT |
| | ENTRY DOOR SCHEDULE IS LOCATED OR PROVIDE. |
| | |
| | 59. FBC 424.1.3.1.9, 424.2.17, POOL BARRIER PROPOSED IS |
| | NOT CLEAR (WINDOWS LOCATED IN THE WALL WHICH SERVES AS |
| | THE POOL BARRIER). |
| | |
| | 60. SHEET A6.1, ITEM 68 SPECIFIES RIGID INSULATION, NOA |
| | 11-0516.02; THIS IS THE NOA NUMBER FOR WATERPROOFING, |
| | REVISE; ALSO SEE OTHER COMMENTS REGARDING NOA NUMBERS |
| | ON THE PLAN. |
| | |
| | 61. PROVIDE A GRAB BAR BACKING DETAIL, FBC 107. |
| | |
| | 62. FHA, NOT ALL OF THE SLIDING GLASS DOORS PROPOSED |
| | ARE 6FT; FOR INSTANCE, SEE UNIT S2, SHEET A4.1. SEE |
| | PAGE 3.10 OF THE FAIR HOUSING ACT DESIGN MANUAL AND THE |
| | GUIDANCE REGARDING SLIDING GLASS PATIO DOORS (SECONDARY |
| | DOOR) AND REVISE PLAN TO DEMONSTRATE COMPLIANCE. |
| | |
| | |
| | 63. DETAIL 2-S4.1 GRAPHICALLY DEPICTS AN EMBEDDED STRAP |
| | BUT DOES NOT SPECIFY. PLEASE EITHER PROVIDE INFORMATION |
| | AS TO WHERE THIS INFORMATION CAN BE FOUND OR REVISE |
| | PLAN TO SPECIFY CONNECTORS. |
| | |
| | 64. DETAILS 1 AND 2, S4.1, PLEASE PROVIDE DIRECTION AS |
| | TO WHICH PLAN VIEW SHEET THE DETAIL INDICATOR FOR THESE |
| | DETAILS ARE LOCATED. |
| | |
| | 65. FIRST FLOOR (LS 0.1 AND OTHER SHEETS), ADJACENT TO |
| | STAIR 3, A RAMP IS SHOWN BUT NO STAIR TO ACCESS THE |
| | RESIDENTIAL CORRIDOR FROM THE GARAGE. IT IS SUGGESTED |
| | THAT AN ACCESSIBLE STAIR BE ADDED. THE RAMP ADDS |
| | DISTANCE TO THE PATH OF TRAVEL WHICH COULD BE A |
| | HARDSHIP FOR SOMEONE WHO IS DISABLED OR COMPROMISED, |
| | DOES NOT USE A WHEELCHAIR AND IS ABLE TO NAVIGATE A |
| | STAIR. |
| | |
| | 66. SEE THE ROOF REVIEW: |
| | |
| | ROOF NOAS FOR JM TPO SUBMITTED; 14-0618.03, 13-0529.02 |
| | |
| | A. ROOF PRODUCT APPROVALS WERE SUBMITTED BUT THE |
| | ASSEMBLY PROPOSED WAS NOT SELECTED AND ENGINEERING FOR |
| | ENHANCED FASTENING (WOOD DECK) WAS NOT PROVIDED. IF |
| | THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT |
| | ISSUANCE, THE INFORMATION WILL BE REQUIRED AT TIME OF |
| | ROOF SUB PERMIT SUBMITTAL. AN "N" WILL BE ENTERED FOR |
| | THE ROOF PLAN REVIEW. |
| | |
| | ROOF ASSEMBLIES SELECTED TO COMPLY WITH THE (VULT) |
| | PRESSURES SPECIFIED ON SHEET S6-1. |
| | |
| | B. SHEET S6-1, CLARIFY PURPOSE OF "ROOF MEMBRANE DESIGN |
| | PRESSSURE" VS. "GROSS UPLIFT DESIGN PRESSURES." THE |
| | DESIGN PRESSURES TO BE UTILIZED FOR THE TPO ROOF IS NOT |
| | CLEAR. |
| | |
| | C. SHEET S6-1, ROOF PRESSURES SPECIFIED USE ZONE 2 |
| | PRESSURES FOR ZONE 3. IT APPEARS THAT THE STAIR ROOF, |
| | ELEVATOR ROOF DO NOT INCLUDE A 3FT PARAPET, FBC 1609, |
| | ASCE7 10 30.6-1 NOTE 7. |
| | |
| | |
| | |