| Plan Review Notes For Permit 16020182 |
| Permit Number |
16020182 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-11 11:41:11 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16020182 | | | 2/11/16 | | | | | | 1) SHEET MP1: IT APPEARS THAT RETURN AIR IS BEING | | | TRANSFERRED INTO THE EGRESS CORRIDOR, HOWEVER CORRIDORS | | | CANNOT SERVE AS VENTILATION DUCTS- SECTION 601.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|