Plan Review Notes
Plan Review Notes For Permit 16020182
Permit Number 16020182
Review Stop M
Sequence Number 1
Notes
Date Text
2016-02-11 11:41:111ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020182
 2/11/16
  
 1) SHEET MP1: IT APPEARS THAT RETURN AIR IS BEING
 TRANSFERRED INTO THE EGRESS CORRIDOR, HOWEVER CORRIDORS
 CANNOT SERVE AS VENTILATION DUCTS- SECTION 601.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  