Plan Review Notes
Plan Review Notes For Permit 16020182
Permit Number 16020182
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-02-09 14:23:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET 1.1 SECTION 2.2 INDICATES "NOT SPRINKLERED",
 HOWEVER, GENERAL NOTES INCLUDE MAJOR CONSTRUCTION FIRE
 SPRINKLERS.
 SHEET 3.1 INDICATES A TABLE NOTE "NOT SPRINKLERED";
 HOWEVER, A NOTE BOX INDICATES FIRE SPRINKLERS IN COMMON
 AREA.
  
 PLEASE BETTER CLARIFY AND PROVIDE CONSISTENT NOTES ON
 EACH SHEET.
  
 2. SHEET 3.1 INDICATES A NEW DOOR LEADING TO THE
 CORRIDOR. IT ALSO INDICATES AN EXISTING DOUBLE DOOR
 NEXT TO IT THAT INDICATES A FIXED DOOR LEAF.
  
 PER NFPA 101, CHAPTER 7, DOOR SWING DIRECTION,
 7.2.1.4.2, DOOR IS REQUIRED TO SWING IN THE DIRECTION
 OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER
 PERSONS.
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PROVIDE OCCUPANCY LOAD CALCULATIONS FOR THE EXISTING
 BUSINESS AND WITH LIFE SAFETY PLAN DETAILS THAT SHOW
 THAT THE DOUBLE DOOR LEAF CAN BE FIXED AND THAT BOTH
 DOORS ARE NOT REQUIRED TO BE OPENED FOR EGRESS
 CALCULATIONS. OTHERWISE THE NEW DOOR PLACEMENT EGRESS
 IS IN VIOLATION DUE TO THE THAT DOUBLE DOOR LEAF BEING
 OPENED.
  
 3. SHEET 10.1 DOOR SCHEDULE AND EXIT DEVICE NOTE.
 PROVIDE JUSTIFICATION THAT THE EXIT DEVICE ON DOORS 218
 AND 218A ARE NOT REQUIRED TO HAVE PANIC HARDWARE
 INSTALLED. SHOULD PANIC HARDWARE BE REQUIRED, PROVIDE
 AN ACCURATE NOTE.
  
 PER NFPA 101, CHAPTERE 7, 7.2.1.5.1 DOOR LEAVES SHALL
 BE ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE
 WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.10 A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION.
  
 4. SHEET 10.1 DOOR SCHEDULE. A DOOR CLOSER IS NOT
 INDICATED ON DOOR 218A; HOWEVER, IT IS A RATED DOOR AND
 REQUIRED TO HAVE A CLOSER PER NFPA 101, CHAPTER 7,
 7.2.1.8
  
 PETER LEDUC