| 2016-02-10 08:01:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020182 |
| | ADD: 5500 VILLAGE BLVD. # 201 |
| | CONT: BLACK DIAMOND GENERAL CONTRACTING |
| | TEL: 561-746-3452 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 10/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A1.1 CODE SUMMARY, APPLICABLE CODES |
| | NOTE 1.3 FIRE SPRINKLER WORK SHALL COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 13, 2010 EDITION. UNDERTHE HEADING |
| | BUILDING CODES NOTE NEW CONSTRUCTION 2.2 TYPE IIB / NOT |
| | SPRINKLERED. SHEET 3.1 NOTE: NEW SPRINKLER HEAD FOR NEW |
| | RECESSED COMMON AREA. THERE IS A DISCREPANCY IN THE |
| | PLANS, PLEASE CORRECT. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 2) SHEET 3.1: |
| | 2A) THE MAIN ENTRY TO THE RECEPTION AREA SHOWS A PAIR |
| | OF DOUBLE DOORS ON MAGNETIC HOLD OPEN DEVICES AND A |
| | SECOND PAIR OF DOORS, THE ONE DOOR IS LABELED ENACTIVE. |
| | PLEASE PROVIDE THE TYPE OF HARDWARE ON THESE PAIRS OF |
| | DOORS. THE DOOR HARDWARE SHALL COMPLY WITH THE 2014 |
| | FBC-B SECTION 1008.1.9.1 HARDWARE. |
| | DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING |
| | DEVICES ON DOORS REQUIRED TO BE ACCESSIBLE BY CHAPTER |
| | 11 SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| | TWISTING OF THE WRIST TO OPERATE. |
| | THE INACTIVE DOOR MUST RELEASE WHEN A PERSON IN A |
| | WHEELCHAIR NEEDS TO EXIT THE TENANT SPACE. 2014 |
| | FBC-ACCESSIBILITY: |
| | |
| | 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| | OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | |
| | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) |
| | MAXIMUM. |
| | |
| | 2B) THE 2ND ISSUE IS WITH THE NEW DOOR # 218A. SINCE |
| | BOTH DOORS OF DOOR 200 HAVE TO BE ACTIVE THEY BLOCK THE |
| | EGRESS OF DOOR 218A. |
| | |
| | 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, |
| | SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7 |
| | INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE |
| | THE REQUIRED WIDTH BY MORE THAN ONE-HALF. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |