| 2016-05-19 18:38:57 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PROJECT IS LOCATED WITHIN 600 FEET OF THE |
| | INTER-COASTAL WATERWAY. SURFACE ROUGHNESS D PREVAILS IN |
| | THE UPWIND DIRECTION FOR AT LEAST 5,000 FEET. |
| | THEREFORE, THIS PROJECT IS CONSIDERED TO BE EXPOSURE |
| | CATEGORY D. FBC-R301.2.1.4.3 THE EXPOSURE CATEGORY HAS |
| | NOT BEEN CHANGED ON THE PLANS. |
| | |
| | 2) REVIEW THE COMPONENT AND CLADDING WIND PRESSURES FOR |
| | EXPOSURE D AND REVISE AS REQUIRED. FBC-R301.2.1 THE |
| | COMPONENT AND CLADDING WIND PRESSURES HAVE NOT BEEN |
| | CHANGED ON THE PLANS. |
| | |
| | 3) THE WINDOWS OF THE PROPOSED SECOND FLOOR BEDROOM |
| | ABOVE THE EXISTING LIVING ROOM ARE REQUIRED TO COMPLY |
| | WITH FBC-R310 FOR EMERGENCY ESCAPE AND RESCUE, THIS IS |
| | NOT INDICATED ON THE PLANS. |
| | |
| | 4) PROVIDE DETAILS OF THE GUARDRAIL FOR THE MASTER |
| | BEDROOM BALCONY. FBC-R312 |
| | |
| | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| | THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, |
| | STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. NO PRODUCT |
| | APPROVALS WERE SUBMITTED FOR THE STRUCTURAL MULLIONS. |
| | |
| | 6) THE PLANS SPECIFY CEMENT ROOF TILES AND PRODUCT |
| | APPROVALS FOR TAMKO ASPHALT ASPHALT SHINGLES (NOA NO. |
| | 11-1228.01) WERE SUBMITTED. THE PLANS WILL NEED TO BE |
| | REVISED AND THE ASPHALT SHINGLES WILL NEED TO BE |
| | APPROVED BY THE HISTORIC PLANNER. |
| | |
| | 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2016-05-12 09:12:05 | 5/3/16 REVIEW COMMENTS DO NOT APPLY, PLEASE DISREGARD. |
| 2016-05-03 13:14:25 | |
| | |
| | |
| | 1. NEED TO HAVE A CLEAN OUT AT THE BASE OF THE THREE |
| | INCH STACK FBC/ PLUMBING 708.3.4 |
| | |
| | 2 NEED DETAIL ON TUB DRAIN CONNECTION INSIDE SHOWER PAN |
| | AREA. CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | 2010107.2.1 |
| | |
| | |
| | 3 NEED TO HAVE A VENT FOR THE W/M DISCHARGE FBC |
| | PLUMBING 901.2.1 |