2016-02-17 14:42:36PERMIT #16020161
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PLANS ARE MISSING THE ENGINEER OF RECORD'S SEAL.
 PLANS ARE SIGNED, BUT NOT SEALED.
  
 2) A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 3) PARKING GARAGE AREAS HAVE INADEQUATE NOTIFICATION
 COVERAGE IN VARIOUS AREAS. REVIEW AND CORRECT.
  
 4) AUDIBLE DEVICES ARE NEEDED IN THE PUBLIC RESTROOMS.
 IF THE STALLS ARE TO BE EQUIPPED WITH FULL HEIGHT
 WALLS, NOTIFICATION DEVICES WILL BE NEEDED INSIDE THE
 STALLS, AS WELL.
  
 5) BDA RADIO COVERAGE NEEDED. PHONE JACKS MAY BE USED
 AS BACK-UPS.
  
 6) ANNUNICIATOR PANEL NEEDED AT 1ST FLOOR MAIN
 ENTRANCE.
  
 7) NOTIFICATOIN DEVICES (A/V) NEEDED IN TRASH ROOMS.
  
 8) NOTIFICATION DEVICES (A/V) NEEDED IN BIKE STORAGE
 ROOMS.
  
 9) NOTIFICATOIN DEVICES (A/V) NEEDED ON TERRACES.
  
 10) ADDITIONAL SMOKE DETECTORS NEEDED IN CORRIDORS.
 (SEE SHEET FA-05)
  
 11) 14TH FLOOR (SHEET FA-14) MISSING A SMOKE DETECTOR
 IN THE CORRIDOR.
  
 12) SPECIAL INSPECTOR AND REPORTS NEEDED FOR SMOKE
 CONTROL SYSTEM.
  
 13) SEE PLAN REVIEW COMMENTS ON PLANS FOR SPECIFIC
 LOCATIONS AND/OR AREAS OF CONCERN.
  
  