2016-02-24 11:21:09JOB PERMIT NUMBER: 16020161
 JOB ADDRESS: 333 FERN STREET
 WEST PALM BEACH
 DATE: FEB 24 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1 THE ELECTRICAL REVIEW IN ENTIRELY IS RESERVED PENDING
 RESPONSES TO FIRE COMMENTS. (PUBLIC BATHROOMS MIGHT
 HAVE ADA ISSUES DEPENDING ON STALL HEIGHT EXTRA
 NOTIFICATION DEVICES WILL BE REQUIRED.)
 2 SITE CURRENT CODE STANDARDS NEC 2011, FBC 2014, NFPA
 72 2010, AND NFPA 101 2012.
 3 SMOKE DETECTION IS REQUIRED IN ALL MECHANICAL,
 ELECTRICAL / COMMUNICATION ROOMS. IN FRONT OF ALL FACP
 AND ELEVATORS WHICH IS MISSING IN 2ND & 4TH FLOOR FOR
 ELEVATOR 4. FBC SECTION 907
 4 ILLUMINATION IS REQUIRED IN FRONT OF ALL FACP NEC
 110.26 D AND THE LOCATION OF ANY REMOTELY LOCATED POWER
 SUPPLY SHALL BE IDENTIFIED AT THE MASTER CONTROL UNIT.
 NFPA 72 CHAPTER 10.5
 5 THE BRANCH CIRCUIT FEEDING THE FIRE ALARM SHALL BE
 DEDICATED AND LABELED IN"RED" MECHANICAL PROTECTION OF
 BREAKER WILL BE NEEDED. NEC 760.41 , 760.121
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 1ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  