| Plan Review Notes For Permit 16020141 |
| Permit Number |
16020141 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-09-07 15:25:38 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16020141 | | | 9/7/16 | | | | | | 1) THE RELOCATED GENERATOR ROOM EXHAUST DOES NOT APPEAR | | | TO BE A MINIMUM 10' ABOVE THE WALKWAY AS REQUIRED BY | | | SECTION 501.3.1 (2). PROVIDE A CLEARANCE DISTANCE | | | MEASUREMENT FROM THE ADJOINING GRADE PLANE TO THE | | | BOTTOM LIP OF THE DUCT OPENING. PLEASE NOTE THE EXHAUST | | | IS ALSO PROHIBITED FROM BEING DIRECTED ONTO WALKWAYS | | | PER SECTION 501.3.1.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|