| 2016-02-18 14:31:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16020105 |
| | ADD: 1001 S. FLAGLER DR. STAIR PRESSURIZATION |
| | CONT: HILL YORK SERVICES |
| | TEL: 561-689-7355 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. FEB. 18/2016 |
| | ACTION: DENIED |
| | |
| | 1) A MEETING WAS HELD TODAY WITH THE CONTRACTOR CHRIS |
| | TYSON AND THE PRESIDENT OF P.B.A.U. AND MYSELF ON THE |
| | TOPIC OF STAIR PRESSUREIZATION AND THE COORDINATING OF |
| | THE PLANS FOR THE VARIOUS TRADES, WHO WILL BE THE |
| | DESIGNER OF RECORD FOR THE WHOLE PROJECT AND THE SHOP |
| | DRAWING OF THE APPROVAL BY THE DESIGNER OF RECORD. THE |
| | (2) SUBMITTED STAIR PRESSURE DESIGN DOCUMENTS WILL |
| | REFLECT THE SAME EQUIPMENT AND DESIGN, NOT TO DIFFERENT |
| | DESIGNS. |
| | 2) WE ALSO TALKED ABOUT THE REQUIREMENT ON THE NEXT |
| | SUBMITTAL ALL EXISITNG PERMIT APPLICATIONS AND THE |
| | ADDITIONAL ELECTRICAL AND FIRE ALARM. |
| | 3) THE CGC PERMIT APPLICATION WILL NEED TO BE MODIFIED |
| | IN THE SCOPE OF WORK TO REFLECT WHAT CAN BE COVERED |
| | UNDER THE CGC LICENSURE. |
| | 4) THE CGC PERMIT AND PLANS WILL ALSO NEED TO REFLECT |
| | THE ROOF TOP CURBS, AND INTAKE FANS, AS WEL AS THE NEW |
| | A/C STANDS THAT WERE ADDED UNDER THE ROOFING PERMIT |
| | WHICH DOES NOT SHOW ANY OF THESE PRODUCT APPROVALS |
| | SUBMITTED UNDER THAT PERMIT IN FILE NET THE BUILDING |
| | DEPARTMENT RECORD RETENSION PROGRAM. |
| | THE ROOFING PERMIT ALSO INDICATES THE INSTALATION OF A |
| | NEW DOOR ITEM # 18 CORRIN DOOR, NO PRODUCT APPROVAL HAD |
| | BEEN SUBMITTED. |
| | , 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 5) THE NEW HOLES IN EITHER THE ROOF SLAB AND OR WALL |
| | WILL ALSO NEED TO BE ADDRESSED AND THE REQUIRED |
| | ANCHORING OF THE ROOF TOP EXHAUST BACK DRAFT DAMPER. |
| | PLEASE PROVIDE THE WIND DESIGN CRITERIA AND ANCORING. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 6) WORK TO BE DETREMINED BY OTHERS: |
| | 6A) NEW POWER WIRING, ELECTRICAL PLANS, DISCONNECTS BY |
| | ELECTRICAL CONTRACTOR. |
| | 6B) CONTROL WIRING BY ELECTRICAL CONTRACTOR. |
| | 6C) ROOF FLASHING FOR ROOF CURBS AND WALLS |
| | 6D) INTERFACE OF NEW STAIRWELL PRESSURIZATION SYSTEM |
| | INTO THE EXISTING FIRE ALARM |
| | 6E) EMERGENCY POWER FOR NEW STAIRWELL PRESSURIZATION |
| | FAN ( NOT HIGHRISE, MAY NOT HAVE A BACKUP GENERATOR)? |
| | 6F) DOOR CLOSER AND ADJUSTMENTS |
| | |
| | 7) 2014 FBC-B 909.2 GENERAL DESIGN REQUIREMENTS. |
| | BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS |
| | CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL |
| | HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE |
| | APPLICABLE REQUIREMENTS OF SECTION 909 AND THE |
| | GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF |
| | ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION |
| | DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND |
| | DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE |
| | DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE |
| | SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE |
| | ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO |
| | DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS. |
| | |
| | 8) 2014 FBC-B 909.4 ANALYSIS. A RATIONAL ANALYSIS |
| | SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE |
| | EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS |
| | SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE |
| | UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION |
| | DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE |
| | ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6. |
| | |
| | 9) PLEASE SEE THE REQUIREMENTS FOR ROOF TOP GUARDS, |
| | 1013.6 MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 10) 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE |
| | THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 |
| | MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE |
| | AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. |
| | THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE |
| | PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |