| Plan Review Notes For Permit 16020096 |
| Permit Number |
16020096 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-10 18:56:18 | FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | THIS PLANS HAVE BEEN PASSED WITH A PROVISO | | | | | | - AFCI PROTECTION REQUIRED PER NEC 210.12 B | | | | | | - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | | 314 & 315 | | | | | | - TAMPER RESISITANT RECEPTACLES REQUIRED PER NEC 406.11 | | | | | | - FBC-ER 404.1.1 / 402.4.4 | | | RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT | | | AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE | | | BUILDING THERMAL ENVELOPE. ( 2 CFM ) | | | |
|