| Plan Review Notes For Permit 16020086 |
| Permit Number |
16020086 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-03 13:05:22 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PROVIDE AIR-BORNE AND IMPACT-BORNE SOUND TRANSMISSION | | | TEST RESULTS FROM AN ACCREDITED TESTING LABORATORY. | | | PROVIDE FLAME SPREAD DATA FOR UNDERLAYMANT AND | | | ADHESIVES. | | | | | | FBC 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | FBC 603.1 FLAME SPREAD | | | | | | | | | |
|