2016-02-09 14:02:20PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A FEEDER DETAIL AND A SUMMARY LOAD CALCULATION
 FOR THIS OCCUPANCY. INDICATE THE LOCATION AND SIZE OF
 THE MAIN BREAKER. NEC 215.5
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
 VERIFY THAT ALL RECEPTACLE OUTLETS ARE TAMPER
 RESISTANT. NEC 406.13
 VERIFY THE BATH LIGHTING IN THE TUB/SHOWER AREA IS
 LISTED FOR DAMP LOCATION AND LOCATED AT THE CORRECT
 HEIGHT. NEC 410.10(D)
 PROVIDE A DETAIL FOR THE CLOSET LIGHTING INDICATING THE
 TYPE OF FIXTURES AND THE LOCATION FROM THE STORAGE
 AREA. NEC 410.16
 VERIFY THAT ALL RECEPTACLE OUTLETS ARE PROPERLY SPACED.
 THE GUEST BEDROOM REQUIRES AN ADDITIONAL RECEPTACLE.
 NEC 210.52
 VERIFY THAT ALL CEILING ELECTRICAL BOXES ARE LISTED FOR
 HANGING PADDLE FANS. NEC 422.18
 VERIFY THERE IS A GFCI PROTECTED OUTLET LOCATED ON THE
 PATIO. NEC 210.8
 PROVIDE A DEDICATED LAUNDRY CIRCUIT AND RECEPTACLE. NEC
 210.11(C)2
 PROVIDE A DEDICATED 20 AMPERE BRANCH CIRCUIT TO THE
 BATHROOMS. NEC 210.11(C)3
  