| 2016-02-09 14:02:20 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE A FEEDER DETAIL AND A SUMMARY LOAD CALCULATION | | | FOR THIS OCCUPANCY. INDICATE THE LOCATION AND SIZE OF | | | THE MAIN BREAKER. NEC 215.5 | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | VERIFY THAT ALL RECEPTACLE OUTLETS ARE TAMPER | | | RESISTANT. NEC 406.13 | | | VERIFY THE BATH LIGHTING IN THE TUB/SHOWER AREA IS | | | LISTED FOR DAMP LOCATION AND LOCATED AT THE CORRECT | | | HEIGHT. NEC 410.10(D) | | | PROVIDE A DETAIL FOR THE CLOSET LIGHTING INDICATING THE | | | TYPE OF FIXTURES AND THE LOCATION FROM THE STORAGE | | | AREA. NEC 410.16 | | | VERIFY THAT ALL RECEPTACLE OUTLETS ARE PROPERLY SPACED. | | | THE GUEST BEDROOM REQUIRES AN ADDITIONAL RECEPTACLE. | | | NEC 210.52 | | | VERIFY THAT ALL CEILING ELECTRICAL BOXES ARE LISTED FOR | | | HANGING PADDLE FANS. NEC 422.18 | | | VERIFY THERE IS A GFCI PROTECTED OUTLET LOCATED ON THE | | | PATIO. NEC 210.8 | | | PROVIDE A DEDICATED LAUNDRY CIRCUIT AND RECEPTACLE. NEC | | | 210.11(C)2 | | | PROVIDE A DEDICATED 20 AMPERE BRANCH CIRCUIT TO THE | | | BATHROOMS. NEC 210.11(C)3 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-373-3701 | | | |
|