| Plan Review Notes For Permit 16020054 |
| Permit Number |
16020054 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-22 14:47:06 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | - SUBMIT ELECTRICAL DIAGRAM & SPECIFICATIONS SHOWING A | | | DEDICATED 20 AMP CIRCUIT WITH A DISCONNECTING MEANS AT | | | THE SIGN LOCATION NEC 600.5 , 600.6 | | | | | | - PROVIDE A ASTRONAMICAL TIME CLOCK OR COMBINATION | | | PHOTOCELL WITH TIMER FOR EXTERIOR LIGHTING CONTROLS | | | FBC-E SECTION C 405.2.4 |
|