| 2016-02-11 10:27:20 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - PLEASE PROVIDE A FLOOR PLAN THAT INDICATES THE USE OF | | | ALL ROOMS. FBC 907.1.2 FIRE ALARM SHOP DRAWINGS | | | | | | - FACP NOT LOCATED OVER STEPS. OVERCURRENT DEVICES | | | SHALL NOT BE LOCATED OVER STEPS OF A STAIRWAY. NEC | | | 240.24 F | | | MUST ALSO COMPLY WITH NEC 110.26 WORKING CLEARANCE. | | | PLEASE CLARIFY IF THIS PANEL IS OVER STEPS ? |
|