| Plan Review Notes For Permit 16020025 |
| Permit Number |
16020025 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-10 10:02:15 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - FBC- F907.1.2 FLOOR PLANS MUST HAVE EACH ROOM | | | PROPERLY LABELED | | | - NEC 240.24 LOCATION IN OR ON PREMISES.FACP NOT | | | LOCATED OVER STEPS. OVERCURRENT DEVICES SHALL NOT | | | BE LOCATED OVER STEPS OF A STAIRWAY. PLEASE CLARIFY IF | | | FACP IS OVER THE STAIRS ? |
|