| Date |
Text |
| 2016-02-08 11:36:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010945 |
| | ADD: 2000 CONTINENTAL DR. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??????? |
| | E-MAIL: ?????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 08/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A2.0 AND A6.1. BOTH PAGES SHOW DETAILS OF A |
| | NEW MEZZANINE: |
| | 1A) SHEET A2.0 SHOWS AN ALATERNATIVE TO EXPAND THE |
| | MEZZANINE. PLEASE SEE 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION OF |
| | CONSTRUCTION DRAWINGS. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES. |
| | IF THE DESIGNER WISHES TO EXPAND THE MEZZANINE AFTER |
| | THE PERMIT ISSUANCE IT MAY COME IN AS A REVISION. |
| | |
| | 1B) PLEASE PROVIDE THE SQUARE FEET OF AREA IN ROOMS113 |
| | & 114 THAT WILL COMMUNICATE WITH THE MEZZANINE TO SEE |
| | IF THERE IS CODE COMPLIANCE WITH: |
| | 2014 505.2.1 AREA LIMITATION. THE AGGREGATE AREA OF A |
| | MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL BE NOT |
| | GREATER THAN ONE-THIRD OF THE FLOOR AREA OF THAT ROOM |
| | OR SPACE IN WHICH THEY ARE LOCATED. THE ENCLOSED |
| | PORTION OF A ROOM SHALL NOT BE INCLUDED IN A |
| | DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH |
| | THE MEZZANINE IS LOCATED. IN DETERMINING THE ALLOWABLE |
| | MEZZANINE AREA, THE AREA OF THE MEZZANINE SHALL NOT BE |
| | INCLUDED IN THE FLOOR AREA OF THE ROOM. THE ALTERNATE |
| | DESIGN FOUND ON SHEET A2.0, A2.1, A2.2, A2.3 & A2.5 OF |
| | 358 SQ. FT. APPEARS THE SQUARE FOOTAGE IS OVER THE |
| | ALLOWABLE 33% OF THE FLOOR AREA. |
| | |
| | 1C) SHEET A2.0 & LS2.0 BOTH SHOW THE CORRIDOR 110 WITH |
| | A 1 HOUR FIRE RATING. THE PLANS ONLY STATE FOR THE |
| | CEILING 1 LAYER OF TYPE X 5/8 GYPSUMFOR BOTH SIDES OF |
| | THE CEILING. THE PLANS DO NOT PROVIDE A GYPSUM |
| | ASSOCIATION OR UL LISTING FOR THE CEILING ASSEMBLY NOR |
| | THE WALL ASSEMBLY. FBC-B 1018.1. |
| | |
| | 1D) SHEET A2.0 SHOWS THE COORIDOR ON THE RIGHT SIDE |
| | THERE IS 2 DOORS 111 & 112 BOTH SHOW AS A 45 MINUE |
| | RATED DOOR, BUT TO THE RIGHT SIDE OF THE CORRIDOR THERE |
| | IS NO DOOR SEPARATING THE CORRIDOR FROM THE TREATMENT |
| | ROOMS. FBC-B 1018.6 CORRIDOR CONTINUITY. |
| | |
| | 2) SHEET A6.1: |
| | 2A) SHEET A6.1 SHOWS A CUT ELEVATION THROUGH THE |
| | MEZZANINE LEVEL. THE PLANS INDICATE THE SCALE AS 3/4 |
| | INCH EQUALS A FOOT, I BELIEVE THIS IS A TYPO AND SHOULD |
| | BE 3/8 INCH EQUALS A FOOT. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2B) THE DESIGNER OF RECORD HAS NOTED THAT THE MEZANINE |
| | IS A DESIGN BUILD. A MANUFACTURED MEZANINE SYSTEM, |
| | SHALL INCLUDE COLUMNS, BEAMS AND BAR GRATINGFLOOR, |
| | RAILINGS, SHIPS LADDER FROM THE MEZANINE MANUFACTURER. |
| | WITH THE FOOTING DESIGN PER THE MANUFACTURERS |
| | RECOMMENDATIONS OR MANUFACTURERS STRUCTURAL CONSULTANT. |
| | THE DESIGNER OF RECORD HAS NOT PROVIDED THE MEZZANINE |
| | MANUFACTURER THE REQUIRED DESIGN CRITERIA FOR THE |
| | MEZZANINE MANUFACTURER TO DESIGN TOO. 2014 FBC-B TABLE |
| | 1607.1 (31) 125PSF OR 250 PSF (FOOTNOTE M) MINIMUM |
| | UNIFORMLY DISTRIBUTED LIVE LOADS. |
| | |
| | 2C) 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR |
| | WHICH EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR |
| | INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED |
| | 50 PSF (2.40 KN/M2), SUCH DESIGN LIVE LOADS SHALL BE |
| | CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH |
| | STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT |
| | SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES |
| | 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL |
| | NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY |
| | SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 2D) PLEASE NOTE ONLY LICENSED FLORIDA P.E. CAN PRCATICE |
| | ENGINEEERING IN THE STATE OF FLORIDA. FLORIDA STATUTE |
| | 471.015. THE STEEL MEZZANINE STAIRS, HANDRAIL, |
| | GUARDRAIL SYSTEM AS WELL AS FOUNDATION WILL ALL NEED TO |
| | BE ENGINEERED. |
| | |
| | 2E) BEFORE THE MEZZANINE DRAWING ARE TO BE SUBMITTED |
| | TOTHIS OFFICE THEY MUST BE REVIEWED BY THE ARCHITECT OF |
| | RECORD AND SHOP DRAWING STAMP OF APPROVAL AFFIXED. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |