| Plan Review Notes For Permit 16010904 |
| Permit Number |
16010904 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-08 12:12:55 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010904 | | | 2/8/16 | | | | | | 1) SHEET M000: THE DRAWINGS AND PRINT IN DETAIL N0.3 IS | | | VERY FAINT AND NOT SUITABLE FOR PLAN REVIEW OR COMPUTER | | | FILE SCANNING- PLEASE SUBMIT LEGIBLE PLANS PER SECTION | | | 107.2 WPB AMENDMENTS TO THE FBC-14 BUILDING CODE. | | | 2) M100: THE PRINT ION THE SYMBOL LEGEND IS VERY FAINT | | | AND NOT LEGIBLE- PLEASE SUBMIT LEGIBLE PLANS. | | | 3) REFER TO SECTION 809.2 FBC-14 EXISITNG BUILDING AND | | | PROVIDE A VENTILATION CALCULATIONS FOR THE PROPOSED NEW | | | OFFICES- SHOW THE REQUIRED AND PROVIDED CFM'S OF O/A | | | AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|