Plan Review Notes
Plan Review Notes For Permit 16010845
Permit Number 16010845
Review Stop G
Sequence Number 3
Notes
Date Text
2016-03-27 03:00:111) THERE ARE TWO GAS DRAWINGS THAT SHOW THE PIPING TO
 THE WATER HEATER AS 1/2 INCH AND ALSO AS 3/4 INCH. THE
 GAS LINE TO THE WATER HEATER MUST BE A MINIMUM OF 3/4
 INCH, NOT 1/2 INCH.
 2) SUBMIT A CCOPY OF THE GAS SIZING TABLE THAT YOU USED
 TO SIZE THE PIPE TO THE WATER HEATER. 2014 FBCR
 SEC.G2413.
  
 I SUGGEST CONTACTIN ME TO SET UP AN APPOINTMENT TO
 REVIEW YOUR PLANS AND FIX THE ERRORS SO I CAN ISSUE
 YOUR PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  