| Plan Review Notes For Permit 16010845 |
| Permit Number |
16010845 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-03 06:44:32 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 | | | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G | | | 2407. | | | | | | 2).INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | | SEC. G2413.2. . | | | | | | 3) .SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE | | | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS | | | SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.ALL | | | VENTS SHALL BE LISTED AND LABELED. | | | | | | 4) IS THE WATER HEATER LOCATED INSIDE THE LAUNDRY ROOM? | | | CLARIFY. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|