Date Text
2016-02-23 14:42:02 
 SHOW LOCATION OF THE MAIN ELECTRICAL DISCONNECT AND
 ELECTRICAL PANELS. VERIFY ALL REQUIRED SAFETY
 CLEARANCES. NEC 110.26; FBC R E3405.3
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOM.
 NEC 210.11 (C) (3); FBC R E3703.4
  
 PROVIDE A 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2);
  
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED FOR THE NEW
 ELECTRICAL SERVICE. NEC 250.52; FBC R E3608.1.4
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014
 FBC R 314, 315
  
 PROVIDE A ADDITIONAL COUNTER TOP RECEPTACLE FOR THE
 ISLAND COUNTER TOP ON THE OPPOSITE SIDE. NEC 210.52(C)
 (2); FBC R E3901.4.3
  
 RECESSED LIGHTS IN CONTACT WITH INSULATION MUST BE IC
 LISTED. NEC 410.116; FBC R 4004.8
  
 CEILING ELECTRICAL BOXES IF INTENDED FOR SUPPORT OF
 PADDLE FANS MUST BE LISTED FOR THAT USE. NEC 422.18;
 FBC R 3905.9
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  