| 2016-02-18 16:31:59 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ENGINEER OF RECORD TO PROVIDE ORIGINAL SEAL AND |
| | SIGNATURE TO ALL DRAWINGS AS REQUIRED BY CHAPTER 471 |
| | FL. ST. RUBBER STAMP IS NOT ALLOWED. |
| | |
| | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW EXTERIOR OPENINGS INFILL CONSTRUCTION. SPECIFY ALL |
| | FRAMING MEMBERS, CONNECTORS, SHEATHING AND EXTERIOR AND |
| | INTERIOR FINISHES, ETC. SEC. R301 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | 3- PROVIDE COMPLETE FRAMING DETAILS FOR ALL NEW |
| | EXTERIOR DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS |
| | AND CONNECTORS. SEC. R301 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 4- PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW REAR |
| | DECK. SPECIFY ALL FRAMING MEMBERS, CONNECTORS, |
| | FOOTINGS, ETC. SEC. R301 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 5- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | THE NEW DECK GUARDRAIL SHOWING COMPLIANCE WITH THE LIVE |
| | LOADS OF FOOTNOTES "D" AND "F" OF TABLE R301.5 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW DECK GUARDRAIL SHOWING COMPLIANCE WITH SEC. R312 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW DECK STEPS SHOWING COMPLIANCE WITH SEC. R311.7.5 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 7- SINGLE HUNG WINDOW NOA 15-0512.09 SUBMITTED: |
| | A) CLARIFY WHERE IS THIS TYPE OF WINDOW GOING TO BE |
| | INSTALLED. PLANS DON'T SHOW ANY NEW SINGLE HUNG |
| | WINDOWS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) GLAZED OPENINGS NEED LARGE MISSILE IMPACT PROTECTION |
| | AS REQUIRED BY SEC. R301.2.1.2 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). NOA 15-0512.09 IS FOR SMALL MISSILE |
| | IMPACT PROTECTION. IT CAN'T BE USED. |
| | |
| | 8- CLARIFY WHERE IS ALUMINUM "INSWING" DOOR NOA |
| | 14-1103.06 SUBMITTED GOING TO BE INSTALLED. PLANS DON'T |
| | SPECIFY ANY "INSWING" DOOR. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR ALL SIMPSON OR USP STRUCTURAL |
| | CONNECTORS SPECIFIED ON THE STRUCTURAL PLANS AND |
| | DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | LIST THE FLORIDA PRODUCT APPROVAL NUMBER (2014 CODE |
| | VERSION) NEXT TO EACH SPECIFIED CONNECTOR. |
| | |
| | 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |