| 2016-03-14 11:04:37 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010825 | | | 3/14/16 | | | | | | 1) PLEASE INCLUDE THE MANUFACTURER'S SPECIFICATIONS FOR | | | DDCV BACKFLOW PREVENTER AND FOR COMPONENTS OF THE JOINT | | | RESTRAINT SYSTEMS. | | | 2) PLEASE CLARIFY WHY MANY OF THE FLOORS WERE LEFT OUT | | | OF THE UPLOADED HYDRAULIC CALUCLATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|