2016-03-16 17:26:31PERMIT # 16010825
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO
  
 1) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 2) PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 3) PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 4) PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 5) SHEET FP5: PER NFPA 13 - 8.16.1.2.2: PRESSURE GAUGES
 SHALL BE INSTALLED ON THE INLET AND OUTLET SIDES OF
 EACH PRESSURE-REDUCING VALVE.
  
 6) SHEET FP7: THE LOCATION OF THE BACKFLOW PREVENTER
 FOR FIRE SUPPRESSION SYSTEMS MUST COMPLY AS LISTED
 BELOW. THE CURRENT LOCATION (ROOM 143) DOES NOT APPEAR
 TO BE A FULLY ENCLOSED FIRE-RATED ROOM.
  
 PER NFPA 24 - 6.2.11
 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
  
 (1)* A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
  
 (2) A WALL POST INDICATOR VALVE
  
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
  
 (4)* A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT
 (12 M) BUT AT LEAST AS FAR FROM THE BUILDING AS THE
 HEIGHT OF THE WALL FACING THE BACKFLOW PREVENTER.
  
 (5)* A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE
 VALVE WITH AN APPROVED ROADWAY BOX, COMPLETE WITH
 T-WRENCH, LOCATED NOT LESS THAN 40 FT (12 M) FROM THE
 BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE VALVE
 WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH,
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT
 (12 M) BUT AT LEAST AS FAR FROM THE BUILDING AS THE
 HEIGHT OF THE WALL FACING THE BACKFLOW PREVENTER.
  
 (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
  
 (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
  