| 2016-02-12 10:55:18 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT 316010815 |
| | 2/12/16 |
| | |
| | 1) THE PERMIT APPLICATION AND PLANS WERE FORWARDED TO |
| | ME FOR MECHANICAL REVIEW BECAUSE A NEW ADDITION AT THE |
| | REAR OF THE BUILDING HAS BEEN CONSTRUCTED. PLEASE REFER |
| | TO SECTION 202 DEFINITIONS FBC-14 ENERGY CONSERVATION: |
| | ADDITION. AN EXTENSION OR INCREASE IN THE CONDITIONED |
| | SPACE FLOOR AREA OR HEIGHT OF A BUILDING OR STRUCTURE. |
| | AS STATED IN SECTIION R101.4.3 A NEW RESIDENTIAL |
| | ADDITION SHALL CONFORM TO THE PROVISIONS OF THE ENERGY |
| | CODE AS THEY RELATE TO NEW CONSTRUCTION. IN ORDER TO |
| | SHOW COMPLIANCE AS REQUIRED THE PLANS MUST BE REVISED |
| | TO SHOW COMPONENTS OF THE ADDITION'S THERMAL ENVELOPE |
| | AND MEP SYSTEMS, AND DOCUMENTATION OF ENERGY EFFICIENCY |
| | COMPLIANCE USING EITHER THE PRESCRIPTIVE OR PERFORMANCE |
| | BASED METHOD SHALL BE SUBMITTED. PLEASE SEE TABLE |
| | R101.5.1 AND SUBMIT DUPLICATE COPIES OF FORM R402 OR |
| | FORM R405.. |
| | 2) ALTHOUGH A NEW AC SYSTEM IS NOT SHOWN ON THE PLANS, |
| | DUE TO THE INCREASE IN CONDTIIONED FLOOR AREA, PLEASE |
| | PROVIDE AC COOLING AND HEATING CALCULATIONS AS OUTLINED |
| | IN SECTION R403.6.1.1. THE CALCULATIONS MUST INDICATE |
| | THAT THE EXISTING SYSTEM IS CAPABLE OF SUPPORTING THE |
| | ADDED LOAD, OR THE INSTALLATION OF A LARGER CAPACITY OR |
| | SUPPLEMENTAL SYSTEM MAY BE REQUIRED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |