| Plan Review Notes For Permit 16010797 |
| Permit Number |
16010797 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-29 13:02:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1. SHEET A - 2, INDICATES TWO DOORS LABELED AS "C". THE | | | DOOR SCHEDULE DOES NOT INDICATE A "C" DOOR DESCRIPTION. | | | PLEASE CORRECT. | | | | | | 2. SHEET 3 - 1, INDICATES CARD READERS ON EXIT DOORS, | | | PROVIDE NOTE INDICATING THAT THEY SHALL DELAY OR | | | RESTRICT EGRESS. | | | | | | 3. SHEET 3 - 1, PROVIDE A NOTE INDICATING THAT FIRE | | | ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|