| Plan Review Notes For Permit 16010797 |
| Permit Number |
16010797 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-12 08:02:31 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE UPDATE REFERENCE ON ELECTRICAL SPECS TO | | | INDICATE NEW SECTIONS OF THE FLORIDA ENERGY | | | CONSERVATION CODE 2014 5TH EDITION. SECTIONS HAVE BEEN | | | MOVED OVER TO FBC EC 405.7 NOT SECTION 505 | | | 2. PROVIDE A NOTE TO INDICATE THE CARD READERS AND | | | DATA/PHONES TO BE ON SEPARATE PERMIT. A NOTE WILL | | | SUFFICE. FBC 107. | | | 3. PROVIDE A NOTE TO MAINTAIN FIRE RATING ON DEMISING | | | WALLS. NEC 300.21 | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|