| 2016-02-29 14:25:46 | 1ST REVIEW: FBC 2014 RESIDENTIAL MECHANICAL |
| | PERMIT #16010755 |
| | 2/29/15 |
| | |
| | 1) ON OF THE SUBMITTED PLANS SETS IS MISSING THE |
| | ARCHITECT'S RAISED SEAL ON SHEETS 1, T1, AND M1. |
| | 2) SUBMIT AC COOLING AND HEATING CALCULATIONS IN |
| | ACCORDANCE WITH ACCA MANUAL J & S OR OTHER APPROVED |
| | CALCULATION METHODOLGIES- SEE SECTION R403.6 FBC-14 |
| | ENERGY CONSERVATION. |
| | 3) PROVIDE ENERGY EFFICIENCY CALCULATIONS FOR THE NEW |
| | ADDITON IN COMPLIANCE WITH SECTION R101.4.3 AND |
| | R101.5.1. *ADVISORY*- "AIR HANDLING UNITS SHALL NOT BE |
| | INSTALLED IN THE ATTIC WHEN A HOME IS BROUGHT INTO CODE |
| | COMPLIANCE BY SECTION R402. |
| | 4) IF THE AIR HANDLER IS TO REMAIN IN THE ATTIC, REVISE |
| | THE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING R403.2.4 |
| | REQUIREMENTS: |
| | A) THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| | B) A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| | UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| | PROPERLY. |
| | C) THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER. |
| | D) A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: |
| | |
| | 4) PROVIDE THE DIMENSIONS OF THE MAIN R/A GRILL AND |
| | INDICATE HOW AIR WILL BE RETURNED TO THE AIR HANDLER- |
| | THERE IS NO DUCT FROM THE GRILL TO THE UNIT. |
| | 5) THE SUPERIOR WOOD BURNUING FIREPLACE MUST BE IN |
| | COMPLIANCE WITH R1005.3 SOLID-FUEL APPLIANCES. |
| | FACTORY-BUILT CHIMNEYS INSTALLED IN DWELLING UNITS WITH |
| | SOLID-FUEL-BURNING APPLIANCES SHALL COMPLY WITH THE |
| | TYPE HT REQUIREMENTS OF UL 103 AND SHALL BE MARKED |
| | "TYPE HT" AND "RESIDENTIAL TYPE AND BUILDING HEATING |
| | APPLIANCE CHIMNEY" |
| | 6) THE SUPERIOR FIREPLACE MUST BE IN COMPLIANCE WITH |
| | EITHER SECTION G2434.1 OR G2435.1 WHICH REQUIRES |
| | APPROVALS IN ACCORDANCE WITH ANSI Z21.50 OR Z21.88 |
| | RESPECTIVELY. THE SUBMITTAL FOR THE FIREPLACE IS |
| | INDICATING COMPLIANCE WITH ANSI Z21.60 OR Z21.84. |
| | 7) INDICATE HOW OUTSIDE OR EXTERIOR AIR FOR COMBUSTION |
| | WILL BE PROVIDED TO THE FIREPLACE- REFER TO SECTION |
| | R1006.1.) |
| | 8) REFER TO SECTION M1401.4 AND PROVIDE THE |
| | MANUFACTURER'S SPECIFICATIONS FOR ANCHORING THE |
| | EXTERIOR CONDENSER. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |