| Plan Review Notes For Permit 16010737 |
| Permit Number |
16010737 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-24 06:05:48 | 1)THE PLANS SHOW A 2 PSI TO 1/2 PSI REGULATOR SUPPLYING | | | THE DRYER AND RANGE.AT 1/2 PSI AND A AMX. RUN OF 130 | | | FT. ( THE 150 FT. COLUMN FROM TABLE 402.4 (2) MUST BE | | | USED FOR THE METALLIC PIPE DROP) THE MINIMUM SIZE REQD. | | | IS 3/4". | | | 2) THE MINIMUM SIZE CSST SUPPLYING THE RANGE SHALL BE | | | 1" (EHD 30) BASED ON TABLE 402.4 (15) FOR A 1/2 PSI | | | SYSTEM. | | | 3) THE MINIMUM SIZE CSST SUPPLYING BOTH THE RANGE AND | | | DRYER IS 1 1/4" (EHD 37) BASED ON TABLE 402.4 (15) FOR | | | A 1/2 PSI SYSTEM. | | | 4) SHOW THE LENGTH OF THE 1" METALLIC PIPE RISER | | | DOWNSTREAM OF THE 2-1/2 PSI REGULATOR. | | | 5) SHOW THE PIPE SIZE AND TYPE OF PIPE COMING FROM THE | | | GAS METER. | | | 6) THE PLANS SHOW A 1/2 PSI SECTION OF THE PIPING | | | SYSTEM BUT BOTH GAS TABLES REFERENCED ON THE PLAN ARE | | | FOR A 2 PSI SYSTEM. CLARIFY.THE BOUNDARY SURVEY ALSO | | | SHOWS THE GAS METER AS A 0.5" WATER COLUMN. WHICH IS | | | IT, 2 PSI OR 1/2 PSI? | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|