| 2016-01-25 10:09:33 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16010693 |
| | W. P. B. PERMIT: 15070534 |
| | ADD: 4117 BROADWAY |
| | CONT: DREAMWORKS CONST. & REMOD. |
| | TEL: (813)249-5541 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W |
| | * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON./ JAN. 25/ 2016 |
| | SHOP DRAWINS: CANOPY INSTALATION |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PAPERWORK IS DRAWN ON 11X17 INCH |
| | PAPAER AND THE SCALE ON THE PLANS IS 1/16 INCH= 1 FOOT. |
| | THE PLANS ARE TO SMALL TO READ ANDFOR RECORD RETENTION. |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.2.1.4 QUALITY OF |
| | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| | MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR |
| | OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES. |
| | |
| | 2) THE PLANS INDICATE (3) SHEETS, ONE SET ONLT HAS THE |
| | SHEETS 1-2, NO 3RD SHEET. INCOMPLETE PAPERWORK. 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.2.1.3. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) PLEASE NOTE THIS SUMITTAL CAN NOT BE REVIEWED AND |
| | APPROVED UNTIL THE REVISION # 16010413 IS REVIEWD BY |
| | BOTH ZONING & BUILDING AND APPROVED, THERE SEEMS TO BE |
| | CODE ISSUES WITH THE REVISION THAT MAY AFFECT THIS |
| | SUBMITTAL. 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.1 APPROVAL OF CONSTRUCTION DOCUMENTS. WHEN THE |
| | BUILDING OFFICIAL ISSUES A PERMIT, THE CONSTRUCTION |
| | DOCUMENTS SHALL BE NOTED, IN WRITING OR BY STAMP, AS |
| | ?REVIEWED FOR CODE COMPLIANCE.? ONE SET OF CONSTRUCTION |
| | DOCUMENTS SO REVIEWED SHALL BE RETAINED BY THE BUILDING |
| | OFFICIAL. THE OTHER SET SHALL BE RETURNED TO THE |
| | APPLICANT, SHALL BE KEPT AT THE SITE OF WORK AND SHALL |
| | BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL OR A |
| | DULY AUTHORIZED REPRESENTATIVE. |
| | |
| | 4) SHOP DRAWING REVIEW: |
| | 4A) SHEET 2 OF 3 INDICATES THE USE OF WOOD BLOCKING TO |
| | ANCHOR THE AWNING TOO. THE PLANS DO NOT INDICATE THE |
| | TYPE OF BACKING NOR THE ANCHOR OF THE BLOCKING TO THE |
| | STEEL STUD, NOR THE SPACING OF THE STUD, IF THE STUD IS |
| | STRUCTURAL, GAUGE, NOR THE SPACING OF THE STUD OR THE |
| | TYPE OF SHEATHING THAT IS OVER THE STEEL SSTUD PARAPET |
| | WALL. THE PLANS ALSO FAIL TO INDICATE IF THERE ARE TIE |
| | BACK BRACING STRUTS REQUIRED FOR THE NEW PARAPET WALL. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4B) SHEET 2 OF 3 AND 3 OF 3 SHOW A FRAME WORK, SHEET 1 |
| | OF 3 HAS NOTES THAT THE FRAMEWORK IS TO BE 1 1/2X 1 1/2 |
| | INCH ALUMINUM. NOTE # 2 INDICATES THE WELDS ARE TO BE |
| | FULL CONTACT, FULL PENETRATION WELDS, THE PLANS SHEETS |
| | 2 & 3 DO NOT INDICATE THE TYPE OF WELD OR THE SIZE OF |
| | THE WELDS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE ROOFING |
| | MATERIAL TO BE INSTALLED ONTHE FRAME. STRUCTURAL |
| | ROOFING MATERIALS DO NOT REQUIRE ROOF SHEATHING VERSES |
| | ARCHITECTURAL PANELS DO REQUIRE ROOF SHEATHING, THE |
| | ROOF SHEATHING BEING SECURED TO THE FRAMEWORK. |
| | 2014 FBC-B 1703.4.1 RESEARCH AND INVESTIGATION. |
| | SUFFICIENT TECHNICAL DATA SHALL BE SUBMITTED TO THE |
| | BUILDING OFFICIAL TO SUBSTANTIATE THE PROPOSED USE OF |
| | ANY MATERIAL OR ASSEMBLY. IF IT IS DETERMINED THAT THE |
| | EVIDENCE SUBMITTED IS SATISFACTORY PROOF OF PERFORMANCE |
| | FOR THE USE INTENDED, THE BUILDING OFFICIAL SHALL |
| | APPROVE THE USE OF THE MATERIAL OR ASSEMBLY SUBJECT TO |
| | THE REQUIREMENTS OF THIS CODE. THE COSTS, REPORTS AND |
| | INVESTIGATIONS REQUIRED UNDER THESE PROVISIONS SHALL BE |
| | PAID BY THE APPLICANT. |
| | |
| | 2014 FBC-B 1703.4.2 RESEARCH REPORTS. |
| | SUPPORTING DATA, WHERE NECESSARY TO ASSIST IN THE |
| | APPROVAL OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY |
| | PROVIDED FOR IN THIS CODE, SHALL CONSIST OF VALID |
| | RESEARCH REPORTS FROM APPROVED SOURCES. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |